Professional Documents
Culture Documents
NERC Policies Affecting The Power Industry PDF
NERC Policies Affecting The Power Industry PDF
Richard C. Schaefer
IEEE SENIOR MEMBER
Xcel Energy Basler Electric
5828 W. Meadow Lake Rd. Route 143, Box 269
New Hope, Minnesota, USA, 55428 Highland, Illinois, U.S.A. 62249
Tel: 612-633-4266 Tel: 61 8-654-2341
Fax: 612-630-4369 Fax: 618-654-2351
email: david.s.kral Oxcelenergy.com email: richschaefer@basler.com
Abstract - This paper discusses a portion of the guidelines for generator testing to verify models and
NERC Policy involving Generator Testing. The paper performance of synchronous machines.
details an explanation regarding the types of tests that
are required, operating modes of the excitation In its original form, NERC involved a membership
system, and discussion regarding how these tests program consisting mostly of utilities with volunteer
help ensure increased transmission system reliability. participation. Today with the many changes due to de-
regulation, the power industry has changed. Many
utilities have divested their geineration to holding
WHAT IS NERC companies and an increasingly large number of lPPs
(Independent Power Producers) are becoming more
responsible for power produced into the transmission
In 1965 major blackouts in the Northeast spurred the system.
need to establish a council to create standards to help
ensure the reliability of the bulk power generated in In western North America, inoluding Canada, utilities
North America. This commission was designated as and lPPs are being mandated to follow the guidelines
the North American Electric Reliability Council (NERC) established by NERC[13], while in other parts of the
that represents 10 regions in the United States. See country, participation by IPPS is still voluntary, hence
Fig. 1 from the NERC web site (http://www.nerc.com). compliance with the policies varies. To increase
involvement, a comprehensive electricity legislation bill
was proposed in April 2002, which already has passed
in the Senate and is currently being considered in the
House of Representatives[l31. The bill states that all
power producers will be required to adhere to the
policies and guidelines defined by NERC policies.
21 5
resultant difference between electrical power and the
mechanical turbine power causes the generator rotor
to accelerate with respect to the system, increasing the
power angle (point 2). When the fault is cleared, the
electrical power is restored to a level corresponding to
the appropriate point on the power angle curve (point
3). Upon clearing the fault, one or more transmission
elements may be removed from service and at least I
temporarily weaken the transmission system. After
clearing the fault, the electrical power out of the
generator becomes greater than the turbine power.
This causes the unit to decelerate (point 4), reducing
the momentum the rotor gained during the fault. If
there is enough retarding torque after fault clearing to
make up for the acceleration during the fault, the
generator will be transiently stable on the first swing
and will move back toward its operating point. If the
retarding torque is insufficient, the power angle will
continue to increase until synchronism with the power
system is lost. Power system stability in the Fig. 4: Transient Response - Top Graph.Highlights
transmission system after a fault depends upon a the Initial Swing Damping by the Voltage Regulator -
number of factors including, whether the system is in Lower Graph Illustrates MW Oscillation Increases
manual control or automatic voltage control, relay after First Swing
tripping time to clear the fault. the power angle of the
transmission system at the time of the fault, and the To address this problem, a power system stabilizer is
severity of the disturbance. utilized in conjunction with the voltage regulator to
provide positive damping when these MW oscillations
Another problem known as small signal stability also occur. With the aid of a power system stabilizer, the
may exist. It is most often associated with NERC excitation system will vary the generator flux to apply
council regions located in western United States. While torque into the rotor coincidental with the rotor MW
fast excitation systems are important to improve oscillation. The MW oscillation!; after the fault may vary
transient stability following large impact disturbances in frequency from .1 to .7 Hz. which is known as the
to the system, a fast responding excitation system also interarea mode oscillation, and .7 to 2 Hz for local
can contribute a significant amount of negative mode oscillation. In the Western United States and
damping that reduces the natural damping torque of Canada, interarea and local mode oscillations are of
the system causing undamped MW oscillations after a primary concern for damping and hence require power
disturbance. This can occur if the machine is system stabilizers.
interconnected to a weak or high impedance
transmission line where the loads are far from the
POWER SYSTEM STABILIZER REQUIREMENTS
generating plants, typical in areas of the western
United States. Thus an excitation system has the
potential to contribute to small signal instability of In the Western United States machines are being
power systems. Small signal stability is defined as the required to have power system stabilizers to improve
ability of the power system to remain stable in the the dynamic stability of the system. Over the years, the
presence of small disturbances. These disturbances size of the machines where the power system
could be minor variations in load or generation on the stabilizer is utilized has dropped progressively. With
system. If sufficient damping torque doesn't exist, the the limited transmission capability and high loading
result can be rotor angle oscillations of increasing expectations of the system, the transmission lines are
amplitude. Where these MW oscillations grow, the stressed; which makes them particularly vulnerable to
machine can eventually result in a trip caused by a high loading margins and the likelihood of a sustained
loss of unit synchronism or damage to the turbine or growing oscillation after a fault. See Fig. 4. Power
shaft. See Fig. 4. system stabilizers (PSS)have proven to provide
needed damping for these weak transmission systems.
With the very old electromechanical excitation NERCl WECC polices dictate today that machines that
systems, the transient response was relatively slow exceed 30 MVA or group of machines that exceed
compared to systems introduced today. This slow 75MVA with excitation systems installed after
response has minimal effect in reducing the damping November 18, 1993 require power system stabilizers
torque. to be added if the excitation meets the performance
criteria. Specifically if the excitation system has a
bandwidth of not more than 135 degrees phase lag at
1 Hertz. For these systems, a F'SS is a candidate for
the application [141. When a power system stabilizer is
216
utilized, the excitation system response is tuned to be UEL Step Response, PSS ON Dsm109
very aggressive to terminal voltage deviation to
improve the transient stability of the system for the first >
rotor swing. As the transient stability is enhanced, the
natural damping in the system is restored by the PSS.
gz
1
, .
P
403
200
' 2 3 4 5 6 7 8 9 ?U
T h lreC+ki#
217
". Once this information is collected, performance data is
compared with the simulated data produced by
5.
analytical studies. Generator response is monitored
when performing a 2% voltage step change into the
voltage regulator while the generator is open circuited
(generator breaker open) to rnonitor the response of
the synchronous machine with the gains established
for the generatorlexcitations:qstem. For a well4uned
excitation system, the generator should never
Fig. 7 : Model Diagram for Digital Excitation System
experience more than 10% voltage overshoot during
with Rotating Rectifier Excitation System Type ST4B
the voltage step change [1911171. Correlation of the
Fig. 7 represents a sample model of a digital excitation data, actual test data versus the mathematical model
simulation should provide close approximation of the
system [4][16]. The variables in the model change as
information. Fig. 8 illustrates generator voltage, exciter
a function of the application (for example, whether the
field voltage and current response after a 2% voltage
generator has a rotating exciter or static exciter
step change has occurred. Simulated versus actual
working into the main field) and the speed of the
measured performance shows close correlation of the
voltage regulator response. Collected test data of the
data.
generator and excitation system is used to validate the
model for various conditions that need to be examined. Open Cucuil -2%Step Response
This includes the following test to be performed by the
test engineer:
1. Open circuited field voltage, field current
generator saturation curve to determine the
generator air gap saturation characteristics.
See Fig. 7
21 8
circuited a portion of the transmission line, the result UEL Step Response, PSS ON
can be an increase in system voltage. In order to lowet
the system voltage, reactive power needs to be 2
Bp
absorbed into the machine in the under excited region
of the generator. The voltage regulator provides
J-
corrective action by acknowledging the high terminal
voltage and causes a reduction in field excitation. Too
much corrective action by the voltage regulator can
result in an insufficient excitation to maintain
synchronizing torque for the generator power output,
which may cause a trip by loss of field relaying. To
prevent this from occurring, the voltage regulator is
equipped with an underexcitation limiter [UEL) that
limits the maximum reactive power that can be 0-
219
Fig. 1 1 highlights step test of an overexcitation limiter
(OEL) as the generator is forced into the overexcited VAWPOWER FACTOR CONTROLLER
region of the machine. The overexcitation limiter APPLICATION CONSIDERATIONS
illustrates three decreasing limit levels of field current.
220
VALIDATING EVERY FIVE YEARS [4] IEEE Task Force on Digital Excitation Systems,
'"ComputerModels for Representation of Digital-
Based Excitation Systems", IEEE Transactions
NERC requires revalidating all tests described above On Energy Conversion, Vol. 11, No. 3,
every five years. Oscillography internal to the September. 1996, pp. 607-615.
excitation system provides a means to store files after
[5] K. Kim, A. Godhwani, M.J. Basler,
performance testing has been accomplished and "Supplemental Control in a Modern Digital
compare old performance to new test data when Excitation System", presented at the IEEEIPES
needs dictate. Today, many new digital systems offer Summer Meeting, Singapore, July, 2000.
built in features to perform step tests and automatically
[6] Godhwani, M.J. Basler, K. Kim "Commissioning
log the data into COMTRADE or log files to speed Experience with a Modern Digital Excitation
testing and commissioning requirements. System", IEEE Transactions On Energy
Conversion, Vol. 13, No. 2, June, 1998, pp.
Knowing what happens during and after a disturbance 183-187.
is equally important for analyzing unit trips.
171 F.P. de Mello, C. Concordia, "Concept of
Oscillography triggers can be set to monitor MW, line Synchronous Machine Stability as Affected by
current, generator voltage, vars, field voltage and field Excitation Control", IEEE Transactions On PAS,
current in order to analyze the behavior of the system Vol. PAS-88, No. 4, April, 1969, pp. 316-329.
during the event and understand the cause and
[E] F.P. de Mello, L.N. Hannett, J.M. Undrill,
reaction of the generatorlexcitation system. "Practical Approaches to Supplementary
Stabilizing from Accelerating Power", IEEE
'I,
221
[19] Les Hajagos Kestrel Engineering, "Power
System Tuning and Modeling Minnesota Power
8 Light, Boswell Unit 1, Report Number
K2002-07, Dated August 21,2002.
[20] Les Hajagos, Senior Research Engineer,
"Power System Tuning and Modeling Northern
States Power, High Bridge Unit 5, Report
Number WO 8329-020, Dated 31 May - 1 June,
2000".
222