You are on page 1of 9

NERC POLICIES AFFECTING THE POWER INDUSTRY

Richard C. Schaefer
IEEE SENIOR MEMBER
Xcel Energy Basler Electric
5828 W. Meadow Lake Rd. Route 143, Box 269
New Hope, Minnesota, USA, 55428 Highland, Illinois, U.S.A. 62249
Tel: 612-633-4266 Tel: 61 8-654-2341
Fax: 612-630-4369 Fax: 618-654-2351
email: david.s.kral Oxcelenergy.com email: richschaefer@basler.com

Abstract - This paper discusses a portion of the guidelines for generator testing to verify models and
NERC Policy involving Generator Testing. The paper performance of synchronous machines.
details an explanation regarding the types of tests that
are required, operating modes of the excitation In its original form, NERC involved a membership
system, and discussion regarding how these tests program consisting mostly of utilities with volunteer
help ensure increased transmission system reliability. participation. Today with the many changes due to de-
regulation, the power industry has changed. Many
utilities have divested their geineration to holding
WHAT IS NERC companies and an increasingly large number of lPPs
(Independent Power Producers) are becoming more
responsible for power produced into the transmission
In 1965 major blackouts in the Northeast spurred the system.
need to establish a council to create standards to help
ensure the reliability of the bulk power generated in In western North America, inoluding Canada, utilities
North America. This commission was designated as and lPPs are being mandated to follow the guidelines
the North American Electric Reliability Council (NERC) established by NERC[13], while in other parts of the
that represents 10 regions in the United States. See country, participation by IPPS is still voluntary, hence
Fig. 1 from the NERC web site (http://www.nerc.com). compliance with the policies varies. To increase
involvement, a comprehensive electricity legislation bill
was proposed in April 2002, which already has passed
in the Senate and is currently being considered in the
House of Representatives[l31. The bill states that all
power producers will be required to adhere to the
policies and guidelines defined by NERC policies.

WHO WILL BE REQUIRED TO COMPLY

The NERCpolicy wili apply to anyone who seiis power


or is connected into the transmission grid and is one
stepdown transformer removed from the system.
Hence, IPPS, utilities, and industry all will be required
to comply with policy standards. The extent of the
policy guidelines will vary from region to region
depending upon specific standards for that area. For
example, MAPP speaks of machines lOMVA and
Fig. 1: North American Electric Reliability Council's above to comply while in yet other regions, the starting
Ten Regions range maybe much larger. But what does this mean to
the owners? Since "Reliability" is the primary issue,
Over the years, standards and policies have been machine capability and anticipated performance during
created by the efforts of the council to promote and after a fault is important to predict system
reliability with the interconnected systems. These response. To accomplish this requirement, information
policies provide guidelines for reporting machine is required of the machines interconnectedto the
availability due to either scheduled or unscheduled system. This information includes:
outages, transmission capability concerns, system e Reactive capability range of the machine.
performance expectations, and among other things, Excitation system models with data validated
by test.

0-7503-7931-4/03/$17.000 2003 IEEE 214


Generator characteristics including smaller the impedance, the larger the voltage drop. In
synchronous, transient, subsynchronous, and response, the voltage regulator will sense the lower
reactance, that is verified by test data. terminal voltage and increase the voltage into the field
Excitation Limiters must be modeled and of the generator in an attempt to raise the generator
verified. terminal voltage and force current into the fault needed
Generator Protection Relays must be tested for relay tripping and coordination. Fig. 2 provides a
and verified that they coordinate with the typical block diagram of a generator and excitation
excitation limiters, such as the VoltsiHertz system with automatic voltage control that has been
limiter versus VoltsIHertz protection. subject to a fault in the system.
The excitation system must be operated in
automatic voltage regulation mode to help GENERATOR
provide voltage support to the system in the
event of a disturbance.
SUS
For excitation and generator systems
operating in western United States, a power
system stabilizer must be enabled and TRANSFORMER
operating and a verified model provided.
I.___

This paper will discuss what is involved in


accomplishing the various tests and reasons for Fig. 2: Generator Paralleled to the Infinite Bus with a
operating in the suggested characteristic modes Fault to Ground, Impedance Limited

After the fault clears, a very fast voltage regulator with


WHY THE NERC REQUIREMENTS rapid response will be able to maximize the
synchronizing torque of the generator to stabilize the
rotor and allow for its recovery back to its steady state
In 1996, a major power blackout in the northwestern position[lZ]. See Fig. 3.
United States occurred and resulted in millions of
residential homes and businesses to be suddenly
without power. After the blackout. investigations were Stored Kinetic Energy
made to determine cause of failure. The problem, Causes Overspeed
many generators were operating in manual control in
lieu of the automatic voltage regulator, and for those lnsutficlent
systems that were equipped with power system
stabilizers to provide system damping, many of the
power system stabilizers were turned off, creating an
even larger potential of an eventual system collapse.
Since the 1996 blackout, performance policies have
been written to help define the expectations of the
generator connected to the transmission system.

VOLTAGE REGULATOR PERFORMANCE


EXPECTATIONS machlne loses

Most excitation systems are equipped with two


operating modes, the automatic voltage regulator and
manual control. While automatic voltage regulator
helps provide reactive and voltage support for Power Angle- 6
disturbances and relay fault clearing, manual control
tends to make the generator a follower, providing no Fig. 3: Generalized Diagram of Transient Stability
voltage support that can jeopardize relay tripping after a Fault, as the Rotor Regains Steady State
coordination. Additionally, the potential for tripping on Operating Point
loss of field or slipping a pole on the synchronous
machine exist due to too little excitation for the MW This term is described as transient stability. Transient
being produced. stability is primarily concerned with the immediate
effects of a transmission line disturbance on generator
Hence, the need to operate in automatic voltage synchronism. Fig. 3 illustrates the typical behavior of a
regulator mode becomes apparent. When a system generator in response to a fault condition. Starting
voltage dip occurs due to a system fault. the generator from the initial operating condition (point l ) , a close-in
voltage will decrease by the percentage of the transmission fault causes the generator electrical
impedance between generator and the fault. The output power Pe to be drastically reduced. The

21 5
resultant difference between electrical power and the
mechanical turbine power causes the generator rotor
to accelerate with respect to the system, increasing the
power angle (point 2). When the fault is cleared, the
electrical power is restored to a level corresponding to
the appropriate point on the power angle curve (point
3). Upon clearing the fault, one or more transmission
elements may be removed from service and at least I
temporarily weaken the transmission system. After
clearing the fault, the electrical power out of the
generator becomes greater than the turbine power.
This causes the unit to decelerate (point 4), reducing
the momentum the rotor gained during the fault. If
there is enough retarding torque after fault clearing to
make up for the acceleration during the fault, the
generator will be transiently stable on the first swing
and will move back toward its operating point. If the
retarding torque is insufficient, the power angle will
continue to increase until synchronism with the power
system is lost. Power system stability in the Fig. 4: Transient Response - Top Graph.Highlights
transmission system after a fault depends upon a the Initial Swing Damping by the Voltage Regulator -
number of factors including, whether the system is in Lower Graph Illustrates MW Oscillation Increases
manual control or automatic voltage control, relay after First Swing
tripping time to clear the fault. the power angle of the
transmission system at the time of the fault, and the To address this problem, a power system stabilizer is
severity of the disturbance. utilized in conjunction with the voltage regulator to
provide positive damping when these MW oscillations
Another problem known as small signal stability also occur. With the aid of a power system stabilizer, the
may exist. It is most often associated with NERC excitation system will vary the generator flux to apply
council regions located in western United States. While torque into the rotor coincidental with the rotor MW
fast excitation systems are important to improve oscillation. The MW oscillation!; after the fault may vary
transient stability following large impact disturbances in frequency from .1 to .7 Hz. which is known as the
to the system, a fast responding excitation system also interarea mode oscillation, and .7 to 2 Hz for local
can contribute a significant amount of negative mode oscillation. In the Western United States and
damping that reduces the natural damping torque of Canada, interarea and local mode oscillations are of
the system causing undamped MW oscillations after a primary concern for damping and hence require power
disturbance. This can occur if the machine is system stabilizers.
interconnected to a weak or high impedance
transmission line where the loads are far from the
POWER SYSTEM STABILIZER REQUIREMENTS
generating plants, typical in areas of the western
United States. Thus an excitation system has the
potential to contribute to small signal instability of In the Western United States machines are being
power systems. Small signal stability is defined as the required to have power system stabilizers to improve
ability of the power system to remain stable in the the dynamic stability of the system. Over the years, the
presence of small disturbances. These disturbances size of the machines where the power system
could be minor variations in load or generation on the stabilizer is utilized has dropped progressively. With
system. If sufficient damping torque doesn't exist, the the limited transmission capability and high loading
result can be rotor angle oscillations of increasing expectations of the system, the transmission lines are
amplitude. Where these MW oscillations grow, the stressed; which makes them particularly vulnerable to
machine can eventually result in a trip caused by a high loading margins and the likelihood of a sustained
loss of unit synchronism or damage to the turbine or growing oscillation after a fault. See Fig. 4. Power
shaft. See Fig. 4. system stabilizers (PSS)have proven to provide
needed damping for these weak transmission systems.
With the very old electromechanical excitation NERCl WECC polices dictate today that machines that
systems, the transient response was relatively slow exceed 30 MVA or group of machines that exceed
compared to systems introduced today. This slow 75MVA with excitation systems installed after
response has minimal effect in reducing the damping November 18, 1993 require power system stabilizers
torque. to be added if the excitation meets the performance
criteria. Specifically if the excitation system has a
bandwidth of not more than 135 degrees phase lag at
1 Hertz. For these systems, a F'SS is a candidate for
the application [141. When a power system stabilizer is

216
utilized, the excitation system response is tuned to be UEL Step Response, PSS ON Dsm109
very aggressive to terminal voltage deviation to
improve the transient stability of the system for the first >
rotor swing. As the transient stability is enhanced, the
natural damping in the system is restored by the PSS.
gz
1

When power system stabilizers are utilized, voltage


step responses need to be performed to verify
satisfactory performance and effectiveness afler
tuning. Limiters also are verified to ensure a stable
system. Fig. 5 demonstrates the underexcitation limiter
performance prior to the power system stabilizer being
enabled. Note the MW swing that grows in magnitude
after a -2% voltage step change has been introduced
with the generator connected to the transmission
p
system. The test demonstrates that without the PSS, OnxiPo
the excitation gains have introduced power system
instability. Note how the power swings grow in
magnitude.
9-
LOlD

, .

P
403
200

' 2 3 4 5 6 7 8 9 ?U
T h lreC+ki#

Fig. 6: -2% Step Change Demonstrates UEL Limiter


Stability with PSS
Fig, 5: UEL Step Test demonstrates Excessive
Gain, Note MW Increasing Oscillation Without a
According to NERCMECC requirements where PSS
Power System Stabilizer
are utilized, their activity are to be reported every three
hours without exception, the PSS should never be
In Fig! 6 the PSS is enabled during the underexcitation
turned offexcept below the power threshold that is
limiter step test. Here the MW swings are stable with
deemed appropriate for the system.
the aid of the power system stabilizer to dampen unit
oscillations to achieve good unit performance.
MODEL VERIFICATION TESTING

One of the important areas of NERC Planning


Standards ensuring a more reliable interconnected
transmission system is to realistically simulate the
electrical behavior of the components in the
interconnected networks. In order to predict the
behavior of the system during and after a fault,
generator and excitation models have become
increasingly important tools for system transmission
studies. The models provide transmission planners the
ability to analyze generator performance as well as
overall response of the interconnected system during
disturbances. It is important that the information used
in the model be correct. Hence, it is extremely
important to have accurate data that can be used in
the models that represent the generator, the excitation
equipment and the system.

217
". Once this information is collected, performance data is
compared with the simulated data produced by
5.
analytical studies. Generator response is monitored
when performing a 2% voltage step change into the
voltage regulator while the generator is open circuited
(generator breaker open) to rnonitor the response of
the synchronous machine with the gains established
for the generatorlexcitations:qstem. For a well4uned
excitation system, the generator should never
Fig. 7 : Model Diagram for Digital Excitation System
experience more than 10% voltage overshoot during
with Rotating Rectifier Excitation System Type ST4B
the voltage step change [1911171. Correlation of the
Fig. 7 represents a sample model of a digital excitation data, actual test data versus the mathematical model
simulation should provide close approximation of the
system [4][16]. The variables in the model change as
information. Fig. 8 illustrates generator voltage, exciter
a function of the application (for example, whether the
field voltage and current response after a 2% voltage
generator has a rotating exciter or static exciter
step change has occurred. Simulated versus actual
working into the main field) and the speed of the
measured performance shows close correlation of the
voltage regulator response. Collected test data of the
data.
generator and excitation system is used to validate the
model for various conditions that need to be examined. Open Cucuil -2%Step Response
This includes the following test to be performed by the
test engineer:
1. Open circuited field voltage, field current
generator saturation curve to determine the
generator air gap saturation characteristics.
See Fig. 7

Fig. 7: Open Circuit Generator Saturation Curve -


Northern States Power High Bridge Unit 5 [20] Fig. 8: Measured 2% Open Circuit Voltage Step
Response Versus Simulation Study Minnesota
2. Unit trip with 0 MW and absorbing 20% vars Power 8, Light, Boswell Unit 1 [191
in the voltage regulator mode to estimate
excitation parameters. REACTIVE POWER TRANSFER REQUIREMENT,
3. Unit trip with 0 MW load in manual control to VOLTAGE SUPPORT
estimate internal oenerator reactances such
as X d , Xd, T'd, and T'do. The ability to maintain system voltage support can
4. Generator trip at 10% MW to determine
require the full utilization of the generator reactive
inertia constant and governoh performance.
capability limit of the synchronous machine to establish
5. Excitation response in AVR mode and limits under both pre and post contingency conditions
manual mode by performing voltage step to avoid voltage instability or :system collapse. When
changes with the generator open circuit.
the system is lightly loaded or a line fault has open

21 8
circuited a portion of the transmission line, the result UEL Step Response, PSS ON
can be an increase in system voltage. In order to lowet
the system voltage, reactive power needs to be 2
Bp
absorbed into the machine in the under excited region
of the generator. The voltage regulator provides
J-
corrective action by acknowledging the high terminal
voltage and causes a reduction in field excitation. Too
much corrective action by the voltage regulator can
result in an insufficient excitation to maintain
synchronizing torque for the generator power output,
which may cause a trip by loss of field relaying. To
prevent this from occurring, the voltage regulator is
equipped with an underexcitation limiter [UEL) that
limits the maximum reactive power that can be 0-

absorbed into the generator based upon the MW load l5 "0


of the machine [121. The greater the MW loading, the
fewer the vars that can be absorbed into the machine.
e' .oms
0

Hence co-ordination of the limiter versus the maximum . .


.+++1.
l l j i ! ! ! !
reactive capability limit, loss of field relay and steady ......
.. . i ..... ....... . ........ ;.........4. .. ...,. .......
i
I

state stability limit is critical for machine stability.


, , , I :

Tests are conducted to determine the maximum


reactive power that a generator can absorb under
normal conditions. Since the underexcited region
representsthe least stable operating point of the
machine, both steady state and dynamic tests are Ih,lr-
performed to verify system stability when the
underexcitation limiter is active when the machine is Fig. 10: -2% Step Change Demonstrates UEL Limiter
absorbing reactive power and the generator is Stability
producing maximum M W . Dynamic testing of the underexcitation limiter is
important to verify unit stability when the system is
suddenly forced into the underexcitation limit during a
disturbance. As shown, a -2% voltage step change is
introduced through the voltage regulator summing
point with the synchronous machine interconnected to
the system. The test verifies a stable underexcitation
limiter. Test plans may vary to verify stability at load
limits less than full load capability.

The maximum vars available from a generator is of


concern to ensure short time boost as well as
extended var capability of a machine at rated MVA.
During a fault, the generator excitation system will be
required to provide field forcing to help support the
depressed system voltage to maximize voltage
support. During this period, the generator will be
Fig. 9: UEL Testing Verifies Generator Capability expected to extend its var capability for a short period
Curve Against UEL Limiter Action of time to restore the depressed voltage back to
normal. As the field is heating, maximum excitation
Fig. 9 representsthe capability curve of the generator limiters need to limit the heating effects to a safe value
whose capability curve is programmed into the voltage to prevent damage to the field. Testing again is
regulator underexcitation limiter. Testing verifies that required to verify parameters. When performing step
the machine is stable as the voltage setpoint is tests to verify the machine ai its maximum capability,
lowered to verify the machine capability curve as machine safety will be a concern. To verify unit
shown. stability, verification is often performed at lower levels
of excitation and machine output to ensure safety of
the system. Testing requires evaluation of generator
protective relays, such as generator overvoltage, field
overvoltagelovercurrent versus limiter operation to
verify coordination

219
Fig. 1 1 highlights step test of an overexcitation limiter
(OEL) as the generator is forced into the overexcited VAWPOWER FACTOR CONTROLLER
region of the machine. The overexcitation limiter APPLICATION CONSIDERATIONS
illustrates three decreasing limit levels of field current.

I I Over the years, Var or power factor control has


become popular alternative controls used in lieu of the
automatic voltage regulator for small machines. Small
machines tend to be classifiecl as voltage followers
that have little to minimum affect on thesystem voltage
stability [151. The var controller provides a
supplementary control into the automatic voltage
regulator loop to cause the system to regulate constant
vars in lieu of the terminal voltage regulator mode. See
Fig. 13. Operation at unity povver factor will extend life
of the machine because the machine will run cooler.

Fig. I I : 2% Step Change with Over Excitation Limiter


Response

The maximum vars the generator is capable of


delivering is important to verify the system contingency
needs during stressed transmission voltage levels.

Limiters such as VoltslHertz are tested for functionality


and performance verification. Here, terminal frequency
is varied or terminal voltage is raised below the level of
the volts per hertz relay to verify proper coordination of
the two devices. See Fig 12. ..................................................................................... .
-
Fig. 13: Model for Var Control Supplementary
Control Loop into the PI[) Controller Input

Unfortunately, during a fault the var controller


counteracts the voltage suppoit action of the regulator
depending upon the gain settirig of the device, instead
the var controller maintains constant vars and a
voltage collapse may occur jeopardizing relay co-
ordination. For large machines that are critical to
system stability, var control is iiot an acceptable mode
of operation. Proposed guidelines by NERC today
suggest that var control can orily be used on machines
that are transformer connected to system voltages of
less than 69 kV. Hence, var mode would apply mostly
to distributed generation.
Fig. 12: VoltdHertz Ratio Limiter Must Be
Coordinated with VoltslHertz Protection Another problem that can occur where var controllers
are used is compatibility with a power system stabilizer
Where stator current limiters are utilized. step tests are control. There action tends to be opposite in
performed that ensure machine stability is not correction. Power system stabilizers want,to push vars
comprised while limiting in both the under and to stabilize MW swings, while the var controller wants
overexcited region of the generator. The importance of to maintain constant vars. This opposing action can
the limiter test is to verify that no instability develops lead to undamped system instability. Hence, var
with the limiters active due to excessive gains. control always should be disabled when a power
system stabilizer is required.

220
VALIDATING EVERY FIVE YEARS [4] IEEE Task Force on Digital Excitation Systems,
'"ComputerModels for Representation of Digital-
Based Excitation Systems", IEEE Transactions
NERC requires revalidating all tests described above On Energy Conversion, Vol. 11, No. 3,
every five years. Oscillography internal to the September. 1996, pp. 607-615.
excitation system provides a means to store files after
[5] K. Kim, A. Godhwani, M.J. Basler,
performance testing has been accomplished and "Supplemental Control in a Modern Digital
compare old performance to new test data when Excitation System", presented at the IEEEIPES
needs dictate. Today, many new digital systems offer Summer Meeting, Singapore, July, 2000.
built in features to perform step tests and automatically
[6] Godhwani, M.J. Basler, K. Kim "Commissioning
log the data into COMTRADE or log files to speed Experience with a Modern Digital Excitation
testing and commissioning requirements. System", IEEE Transactions On Energy
Conversion, Vol. 13, No. 2, June, 1998, pp.
Knowing what happens during and after a disturbance 183-187.
is equally important for analyzing unit trips.
171 F.P. de Mello, C. Concordia, "Concept of
Oscillography triggers can be set to monitor MW, line Synchronous Machine Stability as Affected by
current, generator voltage, vars, field voltage and field Excitation Control", IEEE Transactions On PAS,
current in order to analyze the behavior of the system Vol. PAS-88, No. 4, April, 1969, pp. 316-329.
during the event and understand the cause and
[E] F.P. de Mello, L.N. Hannett, J.M. Undrill,
reaction of the generatorlexcitation system. "Practical Approaches to Supplementary
Stabilizing from Accelerating Power", IEEE
'I,

CONCLUSION Transactions On PAS, Vol. PAS-97, No. 5,


SepVOct, 1978, pp. 1515-1522.
[SI H. Vu, J.C. Agee. "Comparison of Power
In the next five years, performance testing of the
System Stabilizers for Damping Local Mode
generator excitation system likely will become
Oscillations", Paper presented at the 1992 PES
mandatory for all power producers selling power into
Summer Meeting.
the grid regardless of region, depending upon size of
[lo] R.C. Schaefer, K. Kim "Digital Excitation System
machine. Today, testing requirements or specific
Provides Enhanced Tuning Over Analog
features requirements, (such as a power system
Systems". IEEE Transactions On Industry
stabilizer) may vary depending upon region but testing
Applications, Vol. 37, No. 4, JulyIAug, 2001.
and verification of system models will be impoliant
[ l l ] P. Kundur, D.C. Lee, H.M. Zein El-Din, "Power
tools to ensure future reliability of the transmission
System Stabilizers for Thermal Units: Analytical
system. This paper describes many of the
Techniques and On-Site Validation", IEEE
requirementsfor generator testing as stated in NERC
Transactions On PAS, Vol. PAS-100, No. 1,
Planning Standard 11.6 today. Currently, auditing
January, 1981, pp. 81-95
programs exist in all regions to verify compliance. As
[12] Michael J. Basler, Richard C. Schaefer. Kiyong
new electrical legislation passes, the congressional
Kim, Russell Glenn, "Voltage Regulator with
body will mandate auditing to be sure machines are
Dual PID Controllers Enhance Power System
meeting the policy standards suggested. The need for
Stability", Hydrovision Conference, Poriland,
these policies is based upon the ability to provide
OR 2002
uninterrupted and reliable power for homes and
[13] NERC Standards web site -
businesses now and for years to come.
httD://www.nerc.com NERCNVECC Publication
doc. httD://www.wecc.biz
REFERENCES: [14] WSCC Modeling Working Group, "Criteria to
[ l ] Rasheek M. Rifaat, "Independent Power Determine Excitation System Suitability for PSS
Producers (IPP) Perspectives and Experiences in WSCC System", presented in San Diego, CA,
With WSCC Requirements for Generator Model January 20, 1993
Validation". IEEE Transactions On Industry [15j Thomas W. Eberly, Richard C. Schaefer,
Applications, Vol. 37 N0.4, pp.1210-1215 "Voltage Versus VAWPower Factor Regulation
JulylAugust 2001. on Synchronous Generators", IEEE
[2] T.W. Eberly and R.C. Schaefer, " Transactions 2002, IEEE Pulp and Paper
MinimumlMaximum excitation limiter Conference, June 2002
performance goals for small generation" IEEE 1161 IEEE Std. 421.5-1992, IEEE Recommended
Trans. Energy Conversation, vol. 10, pp.714- Practice for Excitation System Models for Power
721, Dec. 1995 System Stability Studies.
[3] IEEE Task Force on Digital Excitation Systems [I71 IEEE Std. 421.2-1992, IEEEGuide for
"Digital Excitation Technology - A Review of Identification, Testing, and Evaluation of the
Features, Functions and Benefits" IEEE Dvnamic Performance of Excitation Control
Summer Power Meeting, Panel Session on &terms
Digital Excitation System Applications and
Models, January 23, 1996, Baltimore, MD.
..
1181 IEEE Std. 421.4-1990. /€€€Guide for the
Preparation of Excitation System Specifications

221
[19] Les Hajagos Kestrel Engineering, "Power
System Tuning and Modeling Minnesota Power
8 Light, Boswell Unit 1, Report Number
K2002-07, Dated August 21,2002.
[20] Les Hajagos, Senior Research Engineer,
"Power System Tuning and Modeling Northern
States Power, High Bridge Unit 5, Report
Number WO 8329-020, Dated 31 May - 1 June,
2000".

222

You might also like