You are on page 1of 214

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery

Generator Protections
Basic Information & Recommendations
Part-I
Kamin Dave
Senior Application Engineer
DOBLE ENGINEERING COMPANY
Generator Protections

¾ Stator Protections
¾ Rotor Protections
¾ Exciter Protections
¾ Backup Protections

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections

¾ Stator Protections:-
1. Generator differential Protection (87G)
2. Generator Split Phase differential Prot(50D)
3. Over Voltage Protection (59)
4. Over all Generator-Transformer differential
Protection (87GT)
5. 0 – 95% Stator E/F & 100% Stator E/F
Protection (59N/27TN)
6. Protection against Stator winding over
Heating & over loading (51O/L)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections

¾ Rotor Protections:-
1. 1st & 2nd Rotor E/F Protection (64F1/64F2)
2. Stator Unbalanced current Protection (NPS-46)
3. Loss of Excitation Protection (LOF-40G)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections

¾ Abnormal Operating Conditions:-


1. Reverse Power Protection (32R)
2. Low forward Power Protection (37L/32L))
3. Under Frequency Protection (81U/F)
4. Over Frequency Protection (81O/F)
5. Out of Step or Pole-Slip Protection (78)
6. Generator Over Speeding Protection

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections

¾ Other Miscellaneous Protections:-


1. Generator – Transformer Over fluxing
Protection (24)
2. Restricted E/F Protection if it required
3. Back up Impedance Protection or Back up
Protection using Voltage Dependent (Voltage
restrain / Voltage controlled) over current
unit (21/51V)
4. Breaker Flash over Protection
5. Voltage Balance Scheme (LOP-60)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection schemes are recommended for
Generator Prot based on Size:-
PROTECTION ANSI SMALL MEDIUM LARGE REMARKS
CODE (Up to 10MW) (Up to 10MW) (Above 10MW)

Stator Over heat 51 O/L Yes Yes Yes Only for alarm

Voltage 51V Yes Yes Yes


dependent
O/C
Under Impedance 21 - Optional either Yes Required above
or Back up 21 or 51V 50MW & GT
Impedance unit

Over voltage or 59 or 24 (99) - Yes Yes


Over fluxing

Under Voltage 27 - Yes Yes Only for alarm

Over frequency 81O - Yes Yes

Under frequency 81U Yes Yes Yes

Generator 87G Yes Yes Yes Less than 1MW


differential optional

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection schemes are recommended for
Generator Prot based on Size:-
Generator- 87GT - Yes Yes
Transformer
combined
differential

Negative Phase 46 - Yes Yes


sequence

Restricted earth 64R Optional either - -


fault 87G or 64R

Stator E/F 0-95% 51N & 27N & Yes Yes Yes
& 100% 59GN

Rotor E/F-1st & 2nd 64F1 & 64F2 - Yes Yes Stage-1 for alarm
& Stage-2
for Trip

Reverse Power 32 Yes Yes Yes

Low forward 37 - Yes Yes


Power

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection schemes are recommended for
Generator Prot based on Size:-
Field failure 40 - Yes Yes

Pole slipping 78 - - Yes Above 50MW


single unit

Over speed 12 Yes Yes Yes

Turn to Turn 50/51 - - Yes Above 250MW


fault in single unit
stator

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection schemes are recommended for
Generator Prot based on Size:-
ROTOR AND BEARING PROTECTION:

PROTECTION ANSI CODE SMALL (UP MEDIUM (UP LARGE REMARKS


TO 1MW) TO 10MW) (ABOVE
10MW)

Vibration Indicator - Yes Yes Yes

Bearing 26 or 38 Yes Yes Yes


temperature &
alarm trip

Bearing Insulation 26 or 38 Yes Yes Yes

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection schemes are recommended for
Generator Prot based on Size:-
REQUIRED ALARMS:
ABNORMAL AIR COOLED HYDROGEN REMARKS
CONDITION COOLED
Bearing Oil pressure Yes Yes
low

Bearing temperature Yes Yes


high

Stator winding Yes Yes


temperature high

Lubricating oil Yes Yes Sp. For diesel


temperature low generator

Governor oil pressure Yes Yes Sp. For STG


low

Cooling water inlet Yes Yes


pressure low

Battery voltage low Yes Yes Sp. For battery


starting engine

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Tripping Criteria:
¾ Class-A Tripping:
ƒ Turbine Trip + GCB Trip + Field Breaker
Trip
¾ Class-B Tripping:
ƒ Turbine & Boiler Trip
¾ Class-C Tripping:
ƒ GCB Trip only or GCB & FB Trip
¾ GCB = Generator Circuit Breaker
¾ FB = Field Breaker

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Tripping Criteria

TRIP TYPE: TT GCB FB


¾ DIFFRENTIAL
¾ STATOR EARTH
¾ ROTOR EARTH
¾ OVERVOLTAGE
¾ OVERCURRENT
¾ UNBALANCE
¾ UNDERFREQUENCY

Knowledge Is Power SM
Apparatus Maintenance and Power Management
ACA - PROT - 2 / 45 for Energy Delivery
Tripping Criteria

TRIP TYPE TT GCB FB


¾ UNDEREXCITATION
W / O LOSS OF FIELD
WITH LOSS OF FIELD
¾ REVERSE POWER
LONG TIME (STAGE-1)

SHORT TIME (STAGE-2)

(OPERATES ONLY AT TT)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
ACA - PROT - 3 / 45 for Energy Delivery
Technical Specification: Generator

¾ 588 MVA, 16.2 kA, 21 kV, 0.85 PF


¾ Hydrogen gas pressure : 3.5 bar
¾ Excitation : 340 V, 4040 A
¾ Critical speeds : 864, 1806
(exciter), 2388 rpm
¾ Short circuit ratio : 0.52
¾ Sub-transient reactance Xd” : 7.2 %
¾ Negative Sequence reactance(XG2) : 8%
¾ Transient reactance Xd’ : 24.1 %
¾ Synchronous reactance Xd : 231 % (1/0.52)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Generator
¾ Zero Sequence Reactance (X0) : 13%
¾ Time (Td”) short circuit : 0.032s
¾ Time (Td’) short circuit : 0.75s
¾ Short Circuit Ratio (SCR) : 0.52
¾ Capacitance between Stator Winding & Ground : 0.385 microF
¾ Surge Capacitance betn Step-up Tr & GCB : 0.25 microF/Phase
¾ Capacitance bewn TR winding & Ground : 0.2 microF/Phase

NB:
¾ Sub-transient reactance Xd” is used for Breaker rating calculations.
¾ Transient reactance Xd’ is used for O/C & E/F relay co-ordination &
motor starting studies.
¾ Higher SCR, lower the reactance, higher the machine size & higher the
cost. Lower the SCR, higher the reactance, low the machine size & lower
the cost

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Generator

¾ Unity PF lag capability: 433 MVA


¾ Unity PF lead capability: 250 MVA
¾ Total losses 6920 kW;
ƒ Break up:
• Iron: 600kW;
• Short circuit: 2800kW
• Excitation: 1390kW; Windage: 1680kW
• Bearing and shaft seals: 450 kW

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: PMG-Pilot
Exciter
¾ Low excitation power-400 HZ permanent magnet
generator is provided as pilot exciter with
brushless exciters.
¾ The PMG ELP 50/42-30/16 is rated : 65 KVA,
220 V, 3 Ph, 91 A and 158 A for field forcing.
¾ Frame has laminated core with 3ph wdg. Rotor has
mounted poles. Permanent magnets are screwed
to poles.

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Brushless
Exciter for 500MW-BE70/90-30/6-20
¾ Rating: 3840 kW, 6300 A, 600 V
¾ 10 seconds output: 7050 kW
ƒ Current & voltage: 8600 A, 820 V.
¾ Nominal current : 4030 Amp.
¾ Response ratio: >2
¾ 60 diodes per wheel (20 per arm)
¾ Current per diode: 67 A, and
with 6 out of 20 diodes failed: 96 A
¾ Armature dia: 70 cm; Length 90 cm

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Generator Capability Curve
450 0.4 0.7
400 MAX 0.85
RATED
LAG 300 0.9

200 0.95

100
MVAR
100 200 300 400 500 1.0
0
MW 588
100
LEAD 0.95
200
250 Knowledge Is Power SM
0.85 P.F
A. C. ARON Apparatus Maintenance and Power Management
99 07 31 for Energy Delivery
Technical Specification: 500MW
Generator Efficiency
99

η % 98.5
98

97.5

97
0 25% 50% 75% 100%
LOAD IN MW : % FULL LOAD
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Generator

¾Flux density stator & rotor : 2 - 2.5 Tesla


¾H2 coolers heat load : 4424 kW
¾Continuous unbalanced load :8%
¾Short time negative sequence I2t : 10s

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Unbalanced Load – Time Curve
10
6

2
I2 t = 10 sec
1
I2
PU

0.1
0.08
t in Seconds
0.03
0.3 1 10 100 1000
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Current Limit: 3-Phase
Balanced Load

2.2 Stator O/C Curve of 500MW


I 2.0 Machine
PU
1.8
1.6
1.4
1.2

10 20 40 60 100 200
t in Seconds
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Current Limit: 3-Phase
Balanced Load

Stator O/C Curve Limit as per


ANSI C50.13-1989

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
PERMISSIBLE LOADING

RATED MVA min: 1 2 5 10


+5%
SHORT TIME
RATED MVA

-10% -5% 0 +5%


FREQ. DEVIATION VOLTS
2
CONTINUOUS1
3 RATED MVA - 5%
%MVA 90 95 97 100 -5% SPEED +3%
PF=RATED
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Generator Data for Relay Setup

¾IRating = 16200 Ampere


¾CTR = 20000/5A
¾IRating on secondary = (IRating)/ (CTR)
= (16200) / (4000)
= 4.05A
¾VRated = 21000V
¾PTR = 21/0.110kV

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Generator Data for Relay Setup

¾VRating on secondary = (VRating)/ (PTR)


= (21000) / (190.90)
= 110V (L-L)

¾VRating on secondary = (VRating)/ (PTR*1.7325)


= (21000) / (190.90*1.7325)
= 63.5V (L-N)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: PT Input “Line to Line
Voltage”

VL-L = 21000V

VNOMINAL = 110VL-L
VAB

VBC Relay
VCA
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: PT Input “Line to Line
Voltage”

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: PT Input “Line to
Ground Volatge-3 wire”

VL-L = 21000V

VNOMINAL = 110VL-L
VAB

VBC
Relay
VCA
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: PT Input “Line to
Ground Voltage”
VL-L = 21000V

VL-N = 21000V/1.7325

VNOMINAL = 63.5VL-N

VAN

VBN
Relay
VCN
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: PT Input “Line to
Ground Voltage”

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection
(51O/L)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection (51O/L)

¾ Causes:
ƒ Over Loading of Generator
ƒ Stator Over Current
ƒ Short-circuited laminations
ƒ Failure of core bolt insulation
ƒ Failure of Ventilation
ƒ Coolant circuit failure
¾ Setting Criteria: Based on Generator O/L
Curve (Say: 115% for 30s)
¾ RTD or PT100 is required to sense over
temp.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection (51O/L)

¾What is the difference between Stator


Over Load & Over Current???
¾Stator Over Load:
ƒ Power Output of Machine (KVA or KW)
exceeds it’s maximum continuous over
load power limit
ƒ PMAX(KW) = 1.7325*VL-L*ILOAD*COS (Ang)
ƒ Machine voltage is not much reduce during
over load condition (i.e. 85-95% of VRated)
ƒ Phenomenon is much harmful for Prime
over (i.e. Turbine/Engine)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection (51O/L)

¾What is the difference between Stator


Over Load & Over Current???
¾Stator Over Current:
ƒ Stator current exceeds it’s maximum limit
during faults
ƒ Machine voltage collapse & reduced below
30% (Depends on Faults & Location)
ƒ PMAX(KW) = 1.7325*VL-L*ILOAD*COS (Ang)
ƒ Phenomenon is much harmful for Stator
winding (Slide22 shows; ANSI limit)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection (51O/L)

+VE 2.5s – 25s


-VE
51O/L-Timer
51O/L-1
R

3 R 51O/L 51O/L-Timer-1
75-200%
Annunciation ckt.

DC Circuit

G
Power Circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overvoltage Protection
(59)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Voltage Protection (59)

¾Causes:
ƒ Transient Over Voltages
• Surge Voltages mainly originate in
Transmission System because of
Lightning Strokes
ƒ Power Frequency Over Voltages
• Defective operation of AVR
• Sudden Load thrown off
¾Protection is normally offered by other
relays like over fluxing relay
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Voltage Protection (59)
¾ Setting Criteria: Based on Generator Open
circuit voltage characteristic Curve.
¾ Normally, Inverse Characteristic element is
used for Stage-1 for Alarm/Trip (Say: 105%
to 110% of Un for 45s to 50s)
¾ Definite Time element is used for Stage-2
for Tripping (115% to 125% for 500ms to
3000ms). Stage-2 must e set below the
maximum stator voltage possible, taking in to
account magnetic core saturation.

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Voltage Protection (59)

¾Advisable to provide surge diverters


for TG also - to be connected
between phases & earth. Design value
(1.2 - 1.4)*Un allows 50 Hz over voltage
on load rejections.
¾Surge diverters to be explosion proof
or other constructional measures be
taken to avoid danger to persons or
near by components in case of over
voltages.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer
Overfluxing Protection (24)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer Over Fluxing
Protection (24)
¾Causes:
ƒ Generator Regulator Problem
• AVR or Voltage Regulator Fails
• Operating Error during off line manual
regulator operation
• Loss of VT supply of AVR
ƒ System Problem
• Unit Load Rejection: Full Load or –
Partial Load
• Power System Islanding during Major
disturbances in Grid
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer Over Fluxing
Protection (24)
¾Fundamental Voltage & Flux relation:
EAVE = N*Flux*Frequency

But, Foam Factor (ERMS/EAVE) is 1.11;

ERMS = 1.11*N*Flux*Frequency

Flux = (ERMS) / (1.11*N*Frequency)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer Over Fluxing
Protection (24)
¾ Flux = (VN / FN)---Æ (Volts/Hz)
ƒ Flux increases when System voltage rises
at Rated Frequency
ƒ Flux increases when System Frequency
fall at Rated Voltage
¾ Saturation of Magnetic Core of the GT due to
exceeded the V/Hz ratios
¾ Serious Over heating will occur in bolts &
support structure of machine which destroys
their own insulation as well as coil insulation
if the phenomenon persist for longer duration
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer Over Fluxing
Protection (24)
¾Specific Over Fluxing Protection is not
Mandatory & It is generally offered as
an optional by other Protection like
Over Voltage. Protection should be in
circuit whenever field CB is closed
¾IEEE C50.13 Generator should
continuous withstand 105% of rated
excitation at full load
¾Normally Inverse & DMT type relays
are used for application
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer Over Fluxing
Protection (24)
¾Setting Criteria: Based on Generator
V/Hz with stand capability Curve (Say:
1.05 V/Hz or 1.1 V/Hz of Un/Fn)
¾Normally, Inverse Characteristic
element is used for Stage-1 (1.05 to
1.1 V/Hz for Alarm/Trip for 45-50s)
¾Definite Time element is used for
Stage-2 for Tripping (1.15 to 1.25
V/Hz for 2s - 6s)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer Over Fluxing
Protection (24)

Setting Criteria for Inverse Time Over Fluxing relay

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency
Protection (81)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81)

¾ Causes:
ƒ Demand of Active Power suddenly Increases in
Power Grid
ƒ Islanded system, inadequate input quantity and
quality of fuel (i.e. Problem occur in Steam valve
in Steam Turbine or Fuel Pump in Diesel
Engine/Gas Engine etc.)
ƒ Islanded system, Two or more Machines are
running in parallel on more than 70% load &
outage of machine due to machine fault, increases
load on another machine to create under freq. on
running machine

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81)

¾It’s a Prime-mover Protection. Each


turbine is having critical speed.
Operation of machine at a speed which
is close to critical speed would causes
excessive vibration in Primemover &
also it produces mechanical stress in
turbine blades
¾Prolonged operation at under
frequency would result in to damage of
Primemover
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81)

¾As per IEC, BS and ANSI standards,


limits of voltage & frequency variation
within which the generator can operate
at full load without exceeding specified
temperature by more than 10 degree
¾A typical example of Under freq
withstanding capability of ABB
generator as shown below slide;

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81)

Frequenc Rated P.F.=1.0, P.F.=0.8, No Load


y in % Voltage P = PN P = PN P=0
100% 100% Cont. Cont. Cont.
96% 100% Cont. Cont. Cont.
95% 100% Cont. 30Min. Cont.
92.5% 100% 30Min. 2 Min. Cont.
90% 100% 2 Min. - Cont.
87.5% 100% - - 30Min.
85% 100% - - 2 Min.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81)

¾ Setting Criteria: Based on Generator


Permissible Loading Curve (Say: 48.5Hz for
50Hz)
¾ Normally, Stage-1 is the delayed tripping
(Say: 48.5Hz for 3s-10s)
¾ Stage-2 element is also delayed but
operating is lesser than Stage-1 element
(Say: 48Hz for 0.5s - 5s)
¾ Operation at Frequency below 47.5Hz
allowed only for 2-hours in entire life of set
(Turbine)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Over Frequency
Protection (81)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Over Frequency Protection (81)

¾ Causes:
ƒ Full or Partial Load Rejection (Load
thrown off)
ƒ Overshedding of Load during a major
system disturbance
¾ Condition is not a serious problem since
control system or operator action can be
used to quickly restore generator speed but,
if it is not then Machine may pull out of step
condition & it is required to trip on over freq.
protection

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Over Frequency Protection (81)

¾Setting Criteria: Based on Transient


Stability (Say: 50.5Hz for 50Hz)
¾Normally, Stage-1 is the delayed
tripping (Say: 50.5Hz for 3s-10s)
¾Stage-2 element is also delayed but
operating is lesser than Stage-1
element (Say: 51Hz for 0.5s - 5s)
¾Operation at Frequency above 51.5Hz
allowed only for 2-hours in entire life
of set (Turbine)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under/Over Frequency Protection
(81)
+VE 0.5s – 5s
-VE
2/81-Timer
52 81G-1
T

0.5s – 5s
2/81-Timer
81G-2
T

Reverse active clutch & Time Motor


86F-2 81G-2
TM

DC Circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under/Over Frequency Protection
(81)
+VE -VE
86F
TM-1 2/81-1 86F-2
R
86F-3
Annunciation ckt.

86F-1
Trip ckt.

DC Circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection
(32R)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
MVAR MW

FMachine < FSystem G D Y

MVAR

-MW MW

Relay setting Threshold


-MVAR
Machine Act as a Synchronous Motor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
MVAR MW
VMachine < VSystem
FMachine < FSystem G D Y

MVAR

-MW MW

Relay setting Threshold


-MVAR
Machine Act as a Induction Motor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)

¾ Causes:
ƒ Two or more machines are running in
parallel & Prime-mover of one of the
machine fails. Turbine has Problems;
exhaust hood temperature on steam
turbines
ƒ Sometimes the condition appear during
synchronization of machine, if incoming
machine frequency is lesser than bus
frequency

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)

¾ Protection against the motoring action of the


generator while the generator looses it’s
Prime-mover input
¾ Protection is applied for Prime-mover
¾ Normally, Protection is applied only when
machines are operating in parallel with each
other as well as Power Grid
¾ Generator unaffected by reverse power, but
act as a Synchronous Motor (Exporting
Reactive Power & Importing Active Power)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)

¾ Effect:
ƒ Steam Turbine:-
• Steam turbine tends to overheat, when steam
supply is cut off and the turbine still rotates as
the generator runs as motor. Steam turbine, act
as a pump and the steam is trapped. The
turbulence losses in the trapped steam may
then built up a high temperature in low-
pressure stage. Hence, the turbine blades are
overheated due to windage or air friction.
However, the heat caused by turbulence of the
trapped steam can de-temper turbine runner.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
¾ Effect:
ƒ Hydro Turbine:-
• In case of hydro turbine, the flow of water
starts reducing or complete cut off and hence
bubbles are formed causing cavitations in the
turbine resulting to damage turbine runner.
ƒ Diesel Engine:-
• In case of diesel driven set, loss of motive
power is likely to be cause by some
mechanical failure, such as bearing over
heating leading to closure of fuel valves, and
continued running is likely to cause several
damages in engine.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R): Allowable
limit
Prime Mover Allowable limit of %P of
Reverse Power
Diesel (Two cycle-2 25% of rated power
stroke) stroke)
Diesel (Four cycle-4 15% of rated power

Gas turbine (Single shaft) 100% of rated power

Gas turbine (Double shaft) 10% to 15% of rated power

Steam turbine 0.5% to 7.5% of rated power

Hydro turbine 1% to 3% of rated power


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)

¾ Sequential Tripping:
ƒ Used on Steam Turbine Generator to Prevent
Overspeed
ƒ This trip mode only used for boiler/reactor or
turbine mechanical problems

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
¾ Sequential Tripping:
ƒ Step 1:
• Abnormal Turbine/Boiler/Reactor condition is
detected
ƒ Step 2:
• Turbine Valves closed; Generator allowed to
briefly “Motor” (i.e. Importing Active Power
from Grid)
ƒ Step 3:
• A Reverse Power relay in Series with Turbine
Valves position switches confirms all Valves
have closed
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)

¾ Sequential Tripping:
ƒ Step 4:
• Generator is required to Isolate from Power
System

G D Y
MW
GCB
MVARs

ƒ Consider
• Export High MVARs
• Import Low MW
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
Sequential Tripping Logic:

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
¾ Setting Criteria: As the overheating of the
turbine blade does not occur
instantaneously while the generator starts
motoring, so it is not required to trip
instantaneously.
ƒ Set Point 1:
• -P<0.5% for Steam Turbine Generator
• Operating Time 10s
ƒ Set Point 2:
• -P<0.5% for Steam Turbine Generator
• Operating Time 2s
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Low Forward Power
Protection (37L)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Low Forward Power Protection (37L)
MVAR MW

G D Y

MVAR

-MW MW

Relay setting Threshold

-MVAR

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential
Protection (87G)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Protection Against Internal Faults in Machine
¾ Operating Criteria: Differential protection
relay operate when the current at two ends
of feeder differ or mismatch by more than
threshold value of relay (Idiff>Idiffset)

NGR CT1 CT2


G Y D
GCB
E I1 F1 I2
R
Idiff = (I1 – I2)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Protection Against Internal Faults
I1 I2
NGR CT1 CT2
G1 D Y

3
3
GCB
E F1

I1 I1 I2
R
I2 Idiff = I1+I2

NGR
G2 D Y
GCB
E
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Protection Against Internal Faults
I1 L
NGR CT1 CT2
G1 Y D
O

3
3
A
GCB
F1
D
E

I1 I1 R
Idiff = I1

Note: I2 is very less compared to I1 so it will be neglected

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Stable for External Faults
I1 I2
NGR CT1 CT2
G1 D Y

3
3
GCB
I2 F2
E
I2
I1
R
I1 Idiff = I1+I2 = 0

NGR
G2 D Y
GCB
E
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Mainly Two Types of Differential
Schemes;
ƒ High Impedance Differential Protection
Schemes
ƒ Low Impedance Differential Protection
Schemes

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G): High Impedance Scheme

3 3 3

3 3 3
G

Pickup Setting:
5%-25% of IFLC
R Y B

Metrosil &
Stabilizing Resistor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G): High Impedance Scheme

Distorted CT output &


Low resistance Path

Stabilizing resistor provide stability: Negligible


Current flows through relay coil

External fault & one of the CT Saturated


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ High Impedance Differential Scheme;
ƒ Simple & Low cost Scheme
ƒ Only Pickup setting & Easy to set it
ƒ Stabilizing resister Increases stability of relay
against high through fault current
ƒ Operating on current balance principal
ƒ Non-linear resistor or Metrosil is required for surge
voltage absorb during internal & through fault
condition
ƒ Special PS class CTs (With low turn ratio errors) of
identical ratio & ratings required for scheme
ƒ CAG34, MFAC34, MCAG34, etc. relays are used as
high impedance differential relays.
ƒ Much suitable for Generator/Motor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Essential Requirement for High Impedance
Differential Scheme are;
ƒ Equal CT Ratio
ƒ Low CT secondary winding resistance
ƒ Adequate knee-point voltage output from CTs
ƒ Low lead burdens
¾ Harmonic Settings are not available, so
scheme is difficult to applied for
Transformer
¾ Three Winding differential protection scheme
become a more complex than low impedance
scheme
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G): High Impedance Scheme
¾Setting Criteria: Typical Recommended
setting is 10% or 20%
¾Relay Operating Time should be less
than 50ms.
¾Ensure through fault stability by
adjusting proper value of stabilizing
resistor

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Low Impedance Differential Scheme;
ƒ Complex & Higher cost Scheme compared to High
impedance scheme
ƒ Settings are more complex & %Slope Characteristics
settings are differ from manufacturer’s to manufacturer’s
ƒ The scheme is also called as a percentage differential
scheme
ƒ For External faults-----Æ High restraint current
ƒ For internal faults-----Æ Low restraint current
ƒ High sensitivity during internal faults
ƒ Chance of mal-operation of relay during high through fault
current
ƒ 7UT62/MICOMP632/DUOBIAS/SPAD346 etc. relays are
used as low impedance differential relays
ƒ Much suitable for Transformer

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Low Impedance Differential Scheme;
ƒ Normally, Single Slope Characteristic is sufficient
if the Protection is applied for Generator/Motor
because both the CTs are on same voltage level,
so we can minimize %CT error during an external
fault
ƒ Dual Slope Characteristic is required if the
Protection is applied for Transformer

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection (87G):
Low Impedance Differential Protection in MICOM P345 Relay

Slope is not start from origin & depends on “IS2”


setting. Turn point for slope is easy to set
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection (87G):
Low Impedance Differential Protection in 7UM62 Relay

IBias = I1 + I2
First slope is always starts from origin & 2nd slope is depends on
Base Point2 setting. Turn point for 2nd slope is set in following way;
For example; Base point2 = 2.5A then 2nd slope starts after 5A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection (87G):
Low Impedance Differential Protection in REG316 Relay

Slope is starts from origin & cut of point is depends on


“b” setting
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Phase Sequence
Protection (46)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)

¾ Unbalance phase currents create Negative


Sequence current in Generator Stator

¾ Negative Sequence current interacts with


normal positive sequence current to induce
a double freq. (120Hz) current in Rotor
winding & it causes surface heating

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)

¾ Generator withstand capacity;


I22t = K
Where;
K = Constant (Large Generator has smaller
“K” value) & It’s differ Manufacturer’s to
Manufacturer’s
I2 = Negative Sequence current
Table-I shows unbalance withstand capacity
of machine as per ANSI C50.13-1989

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Type of Generator Permissible NPS current
(I2) Percentage of stator
winding
Salient Pole
With connected amortisseur windings 10
Without connected amortisseur 5
windings
Cylindrical Rotor
Indirectly Cooled 10
Directly Cooled to 960MVA 8
961 to 1200 MVA 6
1201 to 1500 MVA 5
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Type of Generator Permissible I22t

Salient Pole Generator 40


Synchronous Condenser 30
Cylindrical Rotor Generators
Indirectly Cooled 30
Directly Cooled up to 800MVA 10
Directly Cooled (801 to 1600 MVA) See curve in
Slide 82

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)

¾Adjust Definite Time Tmax & Tmin


in relay shown in below slides

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)

Tmin is
the Generator Withstand Curve
Definite
Time
Relay Characteristic Inverse
to be set below

Generator Cont.
Withstand capacity

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)

Tmax (Definite Time)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)

¾Back up Protection: Relay Operation


reqd. to co-ordinate for HV fault as
well as Auxiliaries

500MVA/21KV GT

F1

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)

Xd” = 7.2%
XG2 = 8%
XT = 9.5%

I1 = I2 = 100 / (Xd” + XG2 + 2XT)


I1 = I2 = 100 / (7.2 + 8 + 2*9.5)
I1 = I2 = 2.92 P.U.
Relay operating time is required to co-ordinate
on HV faults.

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection
(40)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):

¾Loss of Excitation Magnetic Coupling


between Stator MMF & Rotor Field
Lost
¾Prime Mover still driving unit
¾Large slip frequency current induced in
rotor

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
Basic Diagram

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
Basic Diagram of Brushless Excitation
Auto
BALANCING Manual
R Y B M GEN VOLT INSTMT.
SET POINT
DV M SET POINT
VT MEASURING
CIRCUIT GEN VOLT
COMPENSATE CONTROLLER CONTROLER
CT

FOLLOW UP
CONTROL
G GATE GATE
CONTROL CONTROL

DE-EXCITN AUTO-
MANUAL
CONTROL SELECTOR

EXC
THYR.
PMG
FB
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
Basic Diagram of 210MW Static Exciter
RECTIFIER TRANSFORMER
2500 KVA 15.75 KV/575V DYN 5
TY1
AVR ~
=
TY2
AUTO
FCB CEX 3000 MANU
TY3
1200V 3000A ~
=
COIL 220V DC
TY4

NO LOAD 917A, 95 V
FULL LOAD 2500A, 300 V
5 KVA 415 / 35V
220 V BATTERY
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾How Excitation System Works???


Start

Output Terminal Voltage (VG) of Machine Detected

Reactive Current (IQ) of Machine Detected

Reference Voltage (VGREF) of Output Terminal of Machine is


Set according to Reactive Current (IQ), Reference Voltage VHREF
Of High Voltage side of Transformer & Transfer function FH of
Phase Compensation

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾How Excitation System Works???

Output Terminal Voltage (VG) is subtracted from reference


VGREF of output terminal of Machine

A timing signal is produced according to difference signal


Output from subtracting unit

Field Current is supplied to Field Winding according to


Timing signal

End
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
How Excitation Fails???

If it Open!!!

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
How Excitation Fails???

If it Fails!!!

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
How Excitation Fails???

If it Fails!!!

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
How Excitation Fails???
If it Shorts or Open!!!

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾ Causes:
ƒ Field Open Circuit (Field current is zero)
ƒ Field Short Circuit (Field current is too high)
ƒ AVR Control Failure
ƒ Accidental Tripping of field breaker
¾ Momentary; It will Import Reactive & Real
Power (Motoring Action)
¾ After Motoring Action; Importing Reactive
Power & Exporting Real Power
¾ Synchronous Generator Becomes Induction
Generator
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G)
MVAR MVAR

G D Y

MW

-MW MW

-MVAR
Machine Act an Induction Generator
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G)
MVAR MVAR

G D Y

MW

-MW MW

-MVAR
Machine Act an Induction Motor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾ Slip Induced Eddy Currents Heat Rotor
Surface
¾ System Voltage Collapse due to Reactive
Power demand Increasing in Power System
¾ Reactive power is drawn from grid
proportional to short circuit ratio. Power
factor is low, end zone heating increases.
¾ Partial loss of excitation may cause pole
slipping-highly detrimental to the machine.
¾ During failure of field, field suppression
shall be cut off from circuit and active
load decreased to 60% rated within 30 sec
and to 40% in next 1.5 minutes.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾ THW -210 can operate at 40% rated load for a


total period of 15 minutes. Set to be tripped
there after.
¾ Excitation to be removed when speed is 2000 rpm,
to prevent rotor overheating.
¾ Problem more severe for Steam Turbine
¾ Problem less severe for hydro turbine (Salient Pole)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

How to set Relay????

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

Rotor Limit

Over Excited
Stator Limit

PF=0.85
Under Excited

Generator Capability Curve


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

Generator Capability Curve


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

X Rotor Limit

Over Excited
Stator Limit

PF=0.85
Under Excited

-R R

-X Z = (KV2/MVA)*(CTR/PTR)

Generator Capability Curve: R-X Plot


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

Generator Capability Curve


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

Initially it’s a Motoring Stator Limit


Action when excitation fails

Xd

Rotor Limit
Generator Capability Curve: R-X Plot
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

After Motoring Action Stator Limit


Machine start to work as
An Induction Generator

Xd

Rotor Limit
Generator Capability Curve: R-X Plot
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾ ZPU = (MVABase*ZOhms)/(KVBase2)

¾ ZOhms = ((KVBase2)*(ZPU)/(MVABase)

¾ Xd’Ohms = (21)2*(0.241)/(588)

¾ Xd’Ohms = 0.18075 Ohms-Æ Primary side

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾ Xd’Ohms = 0.18075*(CTR/PTR)

¾ Xd’Ohms = 0.18075*(4000/190.90)

¾ Xd’Ohms = 3.7871 Ohms-Æ Secondary side

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾ ZPU = (MVABase*ZOhms)/(KVBase2)

¾ ZOhms = ((KVBase2)*(ZPU)/(MVABase)

¾ Xd Ohms = (21)2*(2.31)/(588)

¾ Xd Ohms = 1.7325 Ohms

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾ Xd Ohms = 1.7325*(CTR/PTR)

¾ Xd Ohms = 1.7325*(4000/190.90)

¾ Xd Ohms = 36.3 Ohms-Æ Secondary side

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾Offset Setting;

¾ (Xd’Ohms )/2= 1.893 Ohms-Æ Secondary side

¾Circle Diameter Setting;

¾ Xd Ohms = 36.3 Ohms-Æ Secondary side

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾Modern Numerical Relay have Dual


Characteristics

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

Machine Operating
Limit in Leading PF

Zone 2 setting crosses


Steady state Stability
Limit

Setting Criteria: 1 for Dual Characteristics


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾ OFFSET Setting:

¾ ZPU = (MVABase*ZOhms)/(KVBase2)

¾ ZOhms = ((KVBase2)*(ZPU)/(MVABase)

¾ Xd’Ohms = (21)2*(0.241)/(588)

¾ Xd’Ohms = 0.18075 Ohms-Æ Primary side

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾ OFFSET Setting:

¾ Xd’Ohms = 0.18075*(CTR/PTR)

¾ Xd’Ohms = 0.18075*(4000/190.90)

¾ Xd’Ohms = 3.7871 Ohms-Æ Secondary side

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾ ZONE 1 Setting:

¾ ZPU = (MVABase*ZOhms)/(KVBase2)

¾ ZOhms = ((KVBase2)*(ZPU)/(MVABase)

¾ Xd Ohms = (21)2*(1)/(588)

¾ Xd Ohms = 0.75 Ohms

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾ ZONE 1 Setting:

¾ Xd Ohms = 1.7325*(CTR/PTR)

¾ Xd Ohms = 1.7325*(4000/190.90)

¾ Xd Ohms = 7.857 Ohms-Æ Secondary side

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾ ZONE 2 Setting:

¾ ZPU = (MVABase*ZOhms)/(KVBase2)

¾ ZOhms = ((KVBase2)*(ZPU)/(MVABase)

¾ Xd Ohms = (21)2*(2.31)/(588)

¾ Xd Ohms = 1.7325 Ohms

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾ ZONE 2 Setting:

¾ Xd Ohms = 1.7325*(CTR/PTR)

¾ Xd Ohms = 1.7325*(4000/190.90)

¾ Xd Ohms = 36.3 Ohms-Æ Secondary side

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

¾Offset Setting;
¾ (Xd’Ohms )/2= 1.893 Ohms-Æ Secondary side

¾Circle Diameter Setting;


¾ZONE 1
¾ Xd Ohms = 7.857 Ohms-Æ Secondary side
¾ZONE 2
¾ Xd Ohms = 36.3 Ohms-Æ Secondary side

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)

Setting Criteria: 2 for Dual Characteristics


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40):
MICOM P345 Relay

Setting Criteria: 2 for Dual Characteristics


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
0-95% Stator Ground Fault
Protection (59GN)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN)

¾ It provides a protection for stator ground


faults on generator which are high
impedance grounded (NGT through NGR or
NGR etc.)
¾ Protection function normally applicable for
unit connected generators
¾ Ground current can be limited up to about 3A
to 25A on primary side

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground

IF
VLN = 21000/1.7325
IF PTR = 21000/240V
100 Ohms, 10s
CTR = 20/1A

Maximum Ground Fault Amps = (Line to Neutral Voltage)


-----------------------
(NGR Resistance)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground

IF VLN = 21000/1.7325
a
PTR = 21000/240V
100 Ohms, 10s
CTR = 20/1A

Ground Fault Amps at fault location = (Maximum Ground Fault


current * %A)/100

Where; %A = (100 – Fault at location of stator winding)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground

VLN = 21000/1.7325
PTR = 21000/240V
100 Ohms, 10s
CTR = 20/1A

Maximum Ground Fault Volts = (Line to Neutral Voltage*PT secondary volts)


-------------------------------------
(PT Primary Volts)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground

VLN = 21000/1.7325
PTR = 21000/240V
100 Ohms, 10s
CTR = 20/1A

Ground Fault Volts = (Ground fault Amps*PT secondary volts*NGR Resistance)


---------------------------------------------
(PT Primary Volts)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
PTR = 21000/240V
NGR Value = 100 Ohms
59GN Relay Range = 5.4V to 20V

Maximum Ground Fault Amps = (Line to Neutral Voltage)


-----------------------
(NGR Resistance)

IF-Max = (12121.21)
-------------------------
100

IF-Max = 121.21 Amps

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
PTR = 21000/240V
NGR Value = 100 Ohms
59GN Relay Range = 5.4V to 20V
Fault at 90% location of Stator Winding from Phase
Terminal

%A = (100 – 90) = 10%

Ground Fault Amps at fault location = (Maximum Ground Fault current * %A)/100

IF at location “A” = (121.21*10)/100

IF at location “A” = 12.12 Amps

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
PTR = 21000/240V
NGR Value = 100 Ohms
59GN Relay Range = 5.4V to 20V
Fault at 90% Location of Stator Winding from Phase
terminal
Ground Fault Volts = (Ground fault Amps*PT secondary volts*NGR Resistance)
---------------------------------------------
(PT Primary Volts)

Ground Fault Volts = (12.12*138.52*100)


---------------------------
12121.21

Ground Fault Volts = 13.85 Volts

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
59GN Relay Setting = 5.4V & TMS = 0.3
Relay Setting % Location “A” Fault Voltage Operating of
from Neutral Magnitude on Relay
relay terminals
5.4V 5% 6.92V

5.4V 25% 34.63V

5.4V 50% 69.264V

5.4V 75% 103.89V

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
59GN Relay Setting = 5.4V & TMS = 0.3
Relay Setting % Location “A” Fault Voltage Operating of
from Neutral Magnitude on Relay
relay terminals
5.4V 1% 1.38V Not Operate

5.4V 2% 2.77V Not Operate

5.4V 3% 4.15V Not Operate

5.4V 4% 5.54V Not Operate

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (50G):
Resistor Ground
Appendix:
PTR = 21000/240V
NGR Value = 100 Ohms
50G Relay Range = 0.1A to 0.4A
CTR = 20/1A
Maximum Ground Fault Amps = (Line to Neutral Voltage)
-----------------------
(NGR Resistance)

IF-Max = (12121.21)
-------------------------
100

IF-Max = 121.21 Amps

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (50G):
Resistor Ground
Appendix:
50G Relay Setting = 0.1A
Relay Setting % Location “A” Fault Current on Fault Current on
from Neutral Primary side secondary side

0.1A 5% 6.06A 0.3A

0.1A 25% 34.63A 1.51A

0.1A 50% 69.264A 3.03A

0.1A 75% 103.89A 4.54A

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (50G):
Resistor Ground
Appendix:
50G Relay Setting = 0.1A
Relay Setting % Location “A” Fault Current on Fault Current on
from Neutral Primary side secondary side

0.1A 1% 1.21A 0.06A

0.1A 2% 2.42A 0.121A

0.1A 3% 3.63A 0.181A

0.1A 4% 4.84A 0.242A

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)

V
Grounding Transformer

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)

IF

VLN = 21000/1.7325
KVPri = 21kV
KVSec = 0.240kV
KVA = 70KVA
R = 0.913 Ohms
Full Load current in Primary wdg = 3.33A
Ground Fault Impedance = 3640.004 Ohms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)

IF
a
VLN = 21000/1.7325

Assume; Fault is just 10% from Neutral

Ground Fault Volts = (Ground fault Amps*NGTX Impedance)


= (0.333 * 3640.306)
= 1212.12 Volts in Primary

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)

IF
a
VLN = 21000/1.7325

Ratio = 21000/240
= 87.5

Assume; Fault is just 10% from Neutral


Ground Fault Volts = (1212.12) / (87.5) = 13.85V in Secondary

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)
¾Setting Criteria: Typical Recommended
setting for IDMTL 59GN relay is 5.4V &
TMS is 0.3
¾Typical Recommended setting for
Definite Time 59GN relay is 5V & 2s for
Stage-I and 15V & 1s is for Stage-II.
¾Neutral Grounding Resistor value should
not be more than Rn = 106/2*3.14*C to
avoid harmful transient over voltage
because of the Ferro-resonance
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
100% Stator Ground Fault
Protection (27TN)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)

¾Two Measuring Methods to Detect


100% SEF Protection Scheme;
ƒ (3rd ) Third Harmonic Voltage
Method
• 3rd Harmonic Under Voltage
Method
• 3rd Harmonic Over Voltage Method
• 3rd Harmonic Ratio Method
ƒ Sub-harmonic Injection Method
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)

¾ 3rd Harmonic Voltage Method;


ƒ 1% to 3% 3rd Harmonic (Zero sequence)
Line to Neutral Voltage developed by
Generator during Normal condition
because of the capacitance betn Stator
winding & Ground
ƒ 3rd Harmonic Voltage generated by
machine are present in the two ends of
Stator Winding, but the magnitude is
different depends on design & loading
ƒ Fault very close to neutral; 3rd Harmonic
voltage reduced to zero (3V0 = 0V)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)

3rd Harmonic
Current circulate

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)

¾ 3rd Harmonic Under Voltage Method;


ƒ 27H Under voltage relay detect 3rd
harmonic voltage (150Hz for 50Hz &
180Hz for 60Hz).
ƒ Fault is close to neutral; 3rd Harmonic
voltage of machine drop down at neutral
end & initiate tripping

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN):
3RD Harmonic Under Voltage Method
3rd Harmonic
Under voltage relay 3rd harmonic
voltage drop
Because capacitance
Is shorted

IF
IF
3rd Harmonic
Voltage at Neutral End reduced

3rd Harmonic
Voltage at Neutral End reduced

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN): 3rd
Harmonic Under Voltage Method
3rd Harmonic Present
At normal Load
Condition on both end

3rd Harmonic drop to


Zero at neutral end
if fault is close
To neutral

3rd Harmonic drop to


Zero at terminal end
if fault is close
To terminal
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN +59GN)

Numerical Relay

3rd harmonic filter


Extract only 3rd
Harmonic voltage
59GN Element
27TN Element

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)

Control circuit

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59TN)

¾ 3rd Harmonic Over Voltage Method;


ƒ 59TN Over voltage relay detect 3rd
harmonic voltage (150Hz for 50Hz &
180Hz for 60Hz).
ƒ Fault is close to neutral; 3rd Harmonic
voltage of machine Increases at Terminal
end & initiate tripping

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59TN):
3RD Harmonic Over Voltage Method

IF

IF

3rd Harmonic
Over voltage relay

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59TN)

Control circuit

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection
(59TN+27TN)
¾ 3rd Harmonic Ratio Method;
ƒ In this method; 3rd Harmonic voltage will
be measured at both sides, at the neutral
(V3N) & at the terminal (V3T) of generator
ƒ Normally, Ratio will be constant for
balance load condition
ƒ Ratio will be modified when ground fault
occurs
ƒ Ground fault will not detected at null point
(Midpoint of winding)
ƒ Overlapping scheme (59TN+27TN+59GN)
is reqd. to detect ground fault at null point
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: 3rd
Harmonic Ratio Method
Method:1

V3N V3T

Operate: V3T/V3N > Set value

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: 3rd
Harmonic Ratio Method
Method:2

V3N V3T

Operate: V3N/(V3N + V3T) < Set value


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: 3rd
Harmonic Ratio Method

Control circuit

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)

¾ Limitation for Directly Connected Machines;


ƒ Third Harmonic can Circulate between two
Machines
ƒ 3rd Harmonic Voltage varies on Generator
(G1) based on Loading of G2 & G3
ƒ Difficult to apply 3rd Harmonic under
voltage Protection

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Sub-Harmonic Injection Method;
ƒ Sub-Harmonic voltage is injected through
an injection transformer between the
grounding element of the generator &
ground
ƒ Usually sub-harmonic frequency is 1/4th of
Fundamental frequency. i.e. 12.5 Hz for
50Hz & 15 Hz for 60Hz relay
ƒ This scheme provides ground fault
protection with generator energized or
standstill
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method

Fn = 50Hz

Xco = 1
- ---------
2*3.14*Fn*C

IC = (Vn / Xco)

Frequency highÆ Xco value less-Æ High “Ic” current flows

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method

Finj = 12.5Hz

XCo = 1/(2*pi*F*C)
12.5Hz
XL = 2*pi*F*L

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Sub-Harmonic Injection Method;
ƒ During Ground Fault condition; 12.5Hz
current flows through Ground ckt. The
fault resistance appears in parallel with
shunt capacitances to ground. Thus, the
impedance that limits the sub-harmonic
current & this also make the current
change
ƒ Capacitive Reactance Increases
ƒ Inductive Reactance Decreases
ƒ Relay Operates if 12.5Hz Ground fault
current is more than threshold value
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method

Equivalent Circuit

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Sub-Harmonic Injection Method;
ƒ Iinj = (Einj)/ (Zinj + Rn + ZC Total)
Where;
Einj = Injection Voltage
Zinj = Injection TR Leakage Impedance
Zinj = (Rinj + j*Xinj)
Rn = Grounding resistor
ZC = Capacitive impedance of total ckt.

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Appendix;
ƒ Iinj = (Einj)/ (Zinj + Rn + ZC Total)
Where;
Einj = 56V
Zinj = (36 + j*125)
Finj = 12.5 Hz
Rn = 1212 Ohms
CTotal = 2.035 microF
ZC = (106) / (2*pi*12.5*2.05)= -j*6214 Ohms

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Appendix;
Zinj = (36 + j*125)
Where;
Rinj = 36 Ohms
Xinj = 125 Ohms

Now;
Xinj = (2*pi*50*L)
125 = (2*3.14*50*L)
L = 0.331H
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Appendix;
Xinj at Low frequency = (2*pi*12.5*L)
= (2*3.14*12.5*0.331)
= 25.98 Ohms

Now;
Zinj = (36 + j*25.98) Ohms

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Appendix;
¾ Relay setting is 20mA
¾ Iinj during Normal load condition is;
ƒ Iinj = (Einj)/ (Zinj + Rn + ZC Total)
= (56) / (36+j*25.98)+1212-(j*6214)
= 0.0088A @ 78.67o

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Appendix;
¾ Iinj during Fault condition is;
ƒ Iinj = (Einj)/ (Zinj + Rn + Z’C Total)

Where;
Z’C = (ZC * RF) / (ZC + RF)
RF = Fault resistance

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Appendix;
¾ Iinj during Fault condition is;
ƒ Iinj = (Einj)/ (Zinj + Rn + Z’C Total)
= 0.0258A @ 6.67o
ƒ Relay will issue trip command

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Transformer & Grounding Resistor
Method:1

Grounding
Resistor
Injection
Transformer

IF

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Transformer & Grounding Transformer
Method:2

Grounding
Transformer

Separate Injection
Transformer

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection through Grounding Resistor
Method:3

Sub-Harmonic
Voltage Injection
Through Grounding
Transformer

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in 7UM62 Relay

25VAC

Relay Measures;

Rm = (V@20Hz)
---------
(I@20Hz)
IF
Operates;
If Rm < Rset

IF

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in MICOMP345 Relay

Band pass
Filter range
Is 15 to 25Hz
Or
Low Pass
Filter (Cut of
Freq. 45Hz

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in MICOMP345 Relay

Transfer Function of Low Pass Fourier Filter


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in MICOMP345 Relay

Operating time of relay


Is faster than Low pass filter

Filter Response of Band Pass Filter


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in MICOMP345 Relay

NGR

100% SEF scheme with Primary Earthing resistor arrangement


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Earth Fault Protection
(64R)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)

First Ground Fault will not:


•Affect the operation of generator
•Produce any damaging effects

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)

First Ground Fault will:


• No current Flow
• Establish Ground reference making a
Second ground fault more likely
• Increase stress to ground at other points in
Field winding
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)

Second Ground Fault will:


• Flow of Large Current
• Unsymmetrical Flux distribution
• Air gap flux badly distorted

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)

Second Ground Fault will:


• Short out part of field winding causing unit
vibration can damage to bearing
• Cause Rotor Heating from Unbalance current
• Cause arc damage at point of fault

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)

¾DC Voltage Injection Method


¾Potentiometer Method
¾AC Voltage Injection Method

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): DC
Injection Method

Brush is used to ground


Rotor Shaft

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): DC
Injection Method
Slip Rings Negative Potential Biasing

IF

IF

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F):
Potentiometer Method

•Scheme adopted in Older


Machine

•Earth fault on Field Wdg


Produce voltage across
Relay

•Maximum voltage produce


If fault occurs at end of
Wdg
•Overvoltage relay operates
•Blind spot would exist at the centre of field when voltage across the
Wdg & fault would not be detected resistor exceeds 64F’s
•Tapping on Potentiometer could be varied Threshold limit
By using “Push button” to detect fault on
Mid point
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F):
Potentiometer Method
FCB

FCB

R1

64R
R2

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): Low
Frequency Injection Method
LC-filter is the low-pass
Filter to removed high
Frequency Rotor current

IF Low Frequency injection


Source to inject low freq.
Voltage (20Hz/12.5Hz)

Measuring circuit: Relay operates when actual voltage exceeds


Threshold value (U>)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): Low
Frequency Injection Method
Low Frequency voltage output is the
Square wave output
Capacitive coupling blocks normal DC
Field voltage, preventing discharge of
Large current

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): AC
Voltage Injection Method in 7UM62
Fundamental Frequency Injection

Rm = UE
----------
IEE

Relay Operates;
If Rm < Rset

36V/45V

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): AC
Voltage Injection Method in 7UM62
Generating square wave voltage

Rm = Ug
-------
Ig

Low Frequency AC Voltage Measurement

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator: Front & Side view

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator: Front view

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
DOBLE ENGINEERING PVT. LTD
305-SAKAR, OLD PADRA ROAD,
VADODARA.
PH: (+91)(265) 655 77 15 & Fax: (+91)(265) 235 62 85
Cell: (+91) 94267 47545 / 98980 55956
E-MAIL: kdave@doble.com
infokamindave@yahoo.com
Website: www.doble.com

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery

You might also like