Professional Documents
Culture Documents
Protection PDF
Protection PDF
Generator Protections
Basic Information & Recommendations
Part-I
Kamin Dave
Senior Application Engineer
DOBLE ENGINEERING COMPANY
Generator Protections
¾ Stator Protections
¾ Rotor Protections
¾ Exciter Protections
¾ Backup Protections
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections
¾ Stator Protections:-
1. Generator differential Protection (87G)
2. Generator Split Phase differential Prot(50D)
3. Over Voltage Protection (59)
4. Over all Generator-Transformer differential
Protection (87GT)
5. 0 – 95% Stator E/F & 100% Stator E/F
Protection (59N/27TN)
6. Protection against Stator winding over
Heating & over loading (51O/L)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections
¾ Rotor Protections:-
1. 1st & 2nd Rotor E/F Protection (64F1/64F2)
2. Stator Unbalanced current Protection (NPS-46)
3. Loss of Excitation Protection (LOF-40G)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Protections
Stator Over heat 51 O/L Yes Yes Yes Only for alarm
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection schemes are recommended for
Generator Prot based on Size:-
Generator- 87GT - Yes Yes
Transformer
combined
differential
Stator E/F 0-95% 51N & 27N & Yes Yes Yes
& 100% 59GN
Rotor E/F-1st & 2nd 64F1 & 64F2 - Yes Yes Stage-1 for alarm
& Stage-2
for Trip
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection schemes are recommended for
Generator Prot based on Size:-
Field failure 40 - Yes Yes
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection schemes are recommended for
Generator Prot based on Size:-
ROTOR AND BEARING PROTECTION:
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection schemes are recommended for
Generator Prot based on Size:-
REQUIRED ALARMS:
ABNORMAL AIR COOLED HYDROGEN REMARKS
CONDITION COOLED
Bearing Oil pressure Yes Yes
low
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Tripping Criteria:
¾ Class-A Tripping:
Turbine Trip + GCB Trip + Field Breaker
Trip
¾ Class-B Tripping:
Turbine & Boiler Trip
¾ Class-C Tripping:
GCB Trip only or GCB & FB Trip
¾ GCB = Generator Circuit Breaker
¾ FB = Field Breaker
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Tripping Criteria
Knowledge Is Power SM
Apparatus Maintenance and Power Management
ACA - PROT - 2 / 45 for Energy Delivery
Tripping Criteria
Knowledge Is Power SM
Apparatus Maintenance and Power Management
ACA - PROT - 3 / 45 for Energy Delivery
Technical Specification: Generator
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Generator
¾ Zero Sequence Reactance (X0) : 13%
¾ Time (Td”) short circuit : 0.032s
¾ Time (Td’) short circuit : 0.75s
¾ Short Circuit Ratio (SCR) : 0.52
¾ Capacitance between Stator Winding & Ground : 0.385 microF
¾ Surge Capacitance betn Step-up Tr & GCB : 0.25 microF/Phase
¾ Capacitance bewn TR winding & Ground : 0.2 microF/Phase
NB:
¾ Sub-transient reactance Xd” is used for Breaker rating calculations.
¾ Transient reactance Xd’ is used for O/C & E/F relay co-ordination &
motor starting studies.
¾ Higher SCR, lower the reactance, higher the machine size & higher the
cost. Lower the SCR, higher the reactance, low the machine size & lower
the cost
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Generator
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: PMG-Pilot
Exciter
¾ Low excitation power-400 HZ permanent magnet
generator is provided as pilot exciter with
brushless exciters.
¾ The PMG ELP 50/42-30/16 is rated : 65 KVA,
220 V, 3 Ph, 91 A and 158 A for field forcing.
¾ Frame has laminated core with 3ph wdg. Rotor has
mounted poles. Permanent magnets are screwed
to poles.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Brushless
Exciter for 500MW-BE70/90-30/6-20
¾ Rating: 3840 kW, 6300 A, 600 V
¾ 10 seconds output: 7050 kW
Current & voltage: 8600 A, 820 V.
¾ Nominal current : 4030 Amp.
¾ Response ratio: >2
¾ 60 diodes per wheel (20 per arm)
¾ Current per diode: 67 A, and
with 6 out of 20 diodes failed: 96 A
¾ Armature dia: 70 cm; Length 90 cm
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Generator Capability Curve
450 0.4 0.7
400 MAX 0.85
RATED
LAG 300 0.9
200 0.95
100
MVAR
100 200 300 400 500 1.0
0
MW 588
100
LEAD 0.95
200
250 Knowledge Is Power SM
0.85 P.F
A. C. ARON Apparatus Maintenance and Power Management
99 07 31 for Energy Delivery
Technical Specification: 500MW
Generator Efficiency
99
η % 98.5
98
97.5
97
0 25% 50% 75% 100%
LOAD IN MW : % FULL LOAD
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Technical Specification: Generator
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Unbalanced Load – Time Curve
10
6
2
I2 t = 10 sec
1
I2
PU
0.1
0.08
t in Seconds
0.03
0.3 1 10 100 1000
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Current Limit: 3-Phase
Balanced Load
10 20 40 60 100 200
t in Seconds
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Current Limit: 3-Phase
Balanced Load
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
PERMISSIBLE LOADING
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Generator Data for Relay Setup
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: PT Input “Line to Line
Voltage”
VL-L = 21000V
VNOMINAL = 110VL-L
VAB
VBC Relay
VCA
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: PT Input “Line to Line
Voltage”
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: PT Input “Line to
Ground Volatge-3 wire”
VL-L = 21000V
VNOMINAL = 110VL-L
VAB
VBC
Relay
VCA
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: PT Input “Line to
Ground Voltage”
VL-L = 21000V
VL-N = 21000V/1.7325
VNOMINAL = 63.5VL-N
VAN
VBN
Relay
VCN
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Basic Connection: PT Input “Line to
Ground Voltage”
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection
(51O/L)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection (51O/L)
¾ Causes:
Over Loading of Generator
Stator Over Current
Short-circuited laminations
Failure of core bolt insulation
Failure of Ventilation
Coolant circuit failure
¾ Setting Criteria: Based on Generator O/L
Curve (Say: 115% for 30s)
¾ RTD or PT100 is required to sense over
temp.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overheating Protection (51O/L)
3 R 51O/L 51O/L-Timer-1
75-200%
Annunciation ckt.
DC Circuit
G
Power Circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Overvoltage Protection
(59)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Voltage Protection (59)
¾Causes:
Transient Over Voltages
• Surge Voltages mainly originate in
Transmission System because of
Lightning Strokes
Power Frequency Over Voltages
• Defective operation of AVR
• Sudden Load thrown off
¾Protection is normally offered by other
relays like over fluxing relay
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Voltage Protection (59)
¾ Setting Criteria: Based on Generator Open
circuit voltage characteristic Curve.
¾ Normally, Inverse Characteristic element is
used for Stage-1 for Alarm/Trip (Say: 105%
to 110% of Un for 45s to 50s)
¾ Definite Time element is used for Stage-2
for Tripping (115% to 125% for 500ms to
3000ms). Stage-2 must e set below the
maximum stator voltage possible, taking in to
account magnetic core saturation.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Over Voltage Protection (59)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer Over Fluxing
Protection (24)
¾Causes:
Generator Regulator Problem
• AVR or Voltage Regulator Fails
• Operating Error during off line manual
regulator operation
• Loss of VT supply of AVR
System Problem
• Unit Load Rejection: Full Load or –
Partial Load
• Power System Islanding during Major
disturbances in Grid
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer Over Fluxing
Protection (24)
¾Fundamental Voltage & Flux relation:
EAVE = N*Flux*Frequency
ERMS = 1.11*N*Flux*Frequency
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer Over Fluxing
Protection (24)
¾ Flux = (VN / FN)---Æ (Volts/Hz)
Flux increases when System voltage rises
at Rated Frequency
Flux increases when System Frequency
fall at Rated Voltage
¾ Saturation of Magnetic Core of the GT due to
exceeded the V/Hz ratios
¾ Serious Over heating will occur in bolts &
support structure of machine which destroys
their own insulation as well as coil insulation
if the phenomenon persist for longer duration
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer Over Fluxing
Protection (24)
¾Specific Over Fluxing Protection is not
Mandatory & It is generally offered as
an optional by other Protection like
Over Voltage. Protection should be in
circuit whenever field CB is closed
¾IEEE C50.13 Generator should
continuous withstand 105% of rated
excitation at full load
¾Normally Inverse & DMT type relays
are used for application
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer Over Fluxing
Protection (24)
¾Setting Criteria: Based on Generator
V/Hz with stand capability Curve (Say:
1.05 V/Hz or 1.1 V/Hz of Un/Fn)
¾Normally, Inverse Characteristic
element is used for Stage-1 (1.05 to
1.1 V/Hz for Alarm/Trip for 45-50s)
¾Definite Time element is used for
Stage-2 for Tripping (1.15 to 1.25
V/Hz for 2s - 6s)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator-Transformer Over Fluxing
Protection (24)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency
Protection (81)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81)
¾ Causes:
Demand of Active Power suddenly Increases in
Power Grid
Islanded system, inadequate input quantity and
quality of fuel (i.e. Problem occur in Steam valve
in Steam Turbine or Fuel Pump in Diesel
Engine/Gas Engine etc.)
Islanded system, Two or more Machines are
running in parallel on more than 70% load &
outage of machine due to machine fault, increases
load on another machine to create under freq. on
running machine
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under Frequency Protection (81)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Over Frequency Protection (81)
¾ Causes:
Full or Partial Load Rejection (Load
thrown off)
Overshedding of Load during a major
system disturbance
¾ Condition is not a serious problem since
control system or operator action can be
used to quickly restore generator speed but,
if it is not then Machine may pull out of step
condition & it is required to trip on over freq.
protection
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Over Frequency Protection (81)
0.5s – 5s
2/81-Timer
81G-2
T
DC Circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Under/Over Frequency Protection
(81)
+VE -VE
86F
TM-1 2/81-1 86F-2
R
86F-3
Annunciation ckt.
86F-1
Trip ckt.
DC Circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection
(32R)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
MVAR MW
MVAR
-MW MW
MVAR
-MW MW
¾ Causes:
Two or more machines are running in
parallel & Prime-mover of one of the
machine fails. Turbine has Problems;
exhaust hood temperature on steam
turbines
Sometimes the condition appear during
synchronization of machine, if incoming
machine frequency is lesser than bus
frequency
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
¾ Effect:
Steam Turbine:-
• Steam turbine tends to overheat, when steam
supply is cut off and the turbine still rotates as
the generator runs as motor. Steam turbine, act
as a pump and the steam is trapped. The
turbulence losses in the trapped steam may
then built up a high temperature in low-
pressure stage. Hence, the turbine blades are
overheated due to windage or air friction.
However, the heat caused by turbulence of the
trapped steam can de-temper turbine runner.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
¾ Effect:
Hydro Turbine:-
• In case of hydro turbine, the flow of water
starts reducing or complete cut off and hence
bubbles are formed causing cavitations in the
turbine resulting to damage turbine runner.
Diesel Engine:-
• In case of diesel driven set, loss of motive
power is likely to be cause by some
mechanical failure, such as bearing over
heating leading to closure of fuel valves, and
continued running is likely to cause several
damages in engine.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R): Allowable
limit
Prime Mover Allowable limit of %P of
Reverse Power
Diesel (Two cycle-2 25% of rated power
stroke) stroke)
Diesel (Four cycle-4 15% of rated power
¾ Sequential Tripping:
Used on Steam Turbine Generator to Prevent
Overspeed
This trip mode only used for boiler/reactor or
turbine mechanical problems
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
¾ Sequential Tripping:
Step 1:
• Abnormal Turbine/Boiler/Reactor condition is
detected
Step 2:
• Turbine Valves closed; Generator allowed to
briefly “Motor” (i.e. Importing Active Power
from Grid)
Step 3:
• A Reverse Power relay in Series with Turbine
Valves position switches confirms all Valves
have closed
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
¾ Sequential Tripping:
Step 4:
• Generator is required to Isolate from Power
System
G D Y
MW
GCB
MVARs
Consider
• Export High MVARs
• Import Low MW
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
Sequential Tripping Logic:
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R)
¾ Setting Criteria: As the overheating of the
turbine blade does not occur
instantaneously while the generator starts
motoring, so it is not required to trip
instantaneously.
Set Point 1:
• -P<0.5% for Steam Turbine Generator
• Operating Time 10s
Set Point 2:
• -P<0.5% for Steam Turbine Generator
• Operating Time 2s
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Low Forward Power
Protection (37L)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Low Forward Power Protection (37L)
MVAR MW
G D Y
MVAR
-MW MW
-MVAR
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential
Protection (87G)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Protection Against Internal Faults in Machine
¾ Operating Criteria: Differential protection
relay operate when the current at two ends
of feeder differ or mismatch by more than
threshold value of relay (Idiff>Idiffset)
3
3
GCB
E F1
I1 I1 I2
R
I2 Idiff = I1+I2
NGR
G2 D Y
GCB
E
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Protection Against Internal Faults
I1 L
NGR CT1 CT2
G1 Y D
O
3
3
A
GCB
F1
D
E
I1 I1 R
Idiff = I1
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Stable for External Faults
I1 I2
NGR CT1 CT2
G1 D Y
3
3
GCB
I2 F2
E
I2
I1
R
I1 Idiff = I1+I2 = 0
NGR
G2 D Y
GCB
E
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Mainly Two Types of Differential
Schemes;
High Impedance Differential Protection
Schemes
Low Impedance Differential Protection
Schemes
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G): High Impedance Scheme
3 3 3
3 3 3
G
Pickup Setting:
5%-25% of IFLC
R Y B
Metrosil &
Stabilizing Resistor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G): High Impedance Scheme
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Low Impedance Differential Scheme;
Complex & Higher cost Scheme compared to High
impedance scheme
Settings are more complex & %Slope Characteristics
settings are differ from manufacturer’s to manufacturer’s
The scheme is also called as a percentage differential
scheme
For External faults-----Æ High restraint current
For internal faults-----Æ Low restraint current
High sensitivity during internal faults
Chance of mal-operation of relay during high through fault
current
7UT62/MICOMP632/DUOBIAS/SPAD346 etc. relays are
used as low impedance differential relays
Much suitable for Transformer
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection
(87G)
¾ Low Impedance Differential Scheme;
Normally, Single Slope Characteristic is sufficient
if the Protection is applied for Generator/Motor
because both the CTs are on same voltage level,
so we can minimize %CT error during an external
fault
Dual Slope Characteristic is required if the
Protection is applied for Transformer
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection (87G):
Low Impedance Differential Protection in MICOM P345 Relay
IBias = I1 + I2
First slope is always starts from origin & 2nd slope is depends on
Base Point2 setting. Turn point for 2nd slope is set in following way;
For example; Base point2 = 2.5A then 2nd slope starts after 5A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator Phase Differential Protection (87G):
Low Impedance Differential Protection in REG316 Relay
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Type of Generator Permissible NPS current
(I2) Percentage of stator
winding
Salient Pole
With connected amortisseur windings 10
Without connected amortisseur 5
windings
Cylindrical Rotor
Indirectly Cooled 10
Directly Cooled to 960MVA 8
961 to 1200 MVA 6
1201 to 1500 MVA 5
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Type of Generator Permissible I22t
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Tmin is
the Generator Withstand Curve
Definite
Time
Relay Characteristic Inverse
to be set below
Generator Cont.
Withstand capacity
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
500MVA/21KV GT
F1
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Xd” = 7.2%
XG2 = 8%
XT = 9.5%
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection
(40)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
Basic Diagram
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
Basic Diagram of Brushless Excitation
Auto
BALANCING Manual
R Y B M GEN VOLT INSTMT.
SET POINT
DV M SET POINT
VT MEASURING
CIRCUIT GEN VOLT
COMPENSATE CONTROLLER CONTROLER
CT
FOLLOW UP
CONTROL
G GATE GATE
CONTROL CONTROL
DE-EXCITN AUTO-
MANUAL
CONTROL SELECTOR
EXC
THYR.
PMG
FB
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
Basic Diagram of 210MW Static Exciter
RECTIFIER TRANSFORMER
2500 KVA 15.75 KV/575V DYN 5
TY1
AVR ~
=
TY2
AUTO
FCB CEX 3000 MANU
TY3
1200V 3000A ~
=
COIL 220V DC
TY4
NO LOAD 917A, 95 V
FULL LOAD 2500A, 300 V
5 KVA 415 / 35V
220 V BATTERY
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
End
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
How Excitation Fails???
If it Open!!!
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
How Excitation Fails???
If it Fails!!!
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
How Excitation Fails???
If it Fails!!!
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G):
How Excitation Fails???
If it Shorts or Open!!!
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾ Causes:
Field Open Circuit (Field current is zero)
Field Short Circuit (Field current is too high)
AVR Control Failure
Accidental Tripping of field breaker
¾ Momentary; It will Import Reactive & Real
Power (Motoring Action)
¾ After Motoring Action; Importing Reactive
Power & Exporting Real Power
¾ Synchronous Generator Becomes Induction
Generator
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G)
MVAR MVAR
G D Y
MW
-MW MW
-MVAR
Machine Act an Induction Generator
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss of Excitation Protection (40G)
MVAR MVAR
G D Y
MW
-MW MW
-MVAR
Machine Act an Induction Motor
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾ Slip Induced Eddy Currents Heat Rotor
Surface
¾ System Voltage Collapse due to Reactive
Power demand Increasing in Power System
¾ Reactive power is drawn from grid
proportional to short circuit ratio. Power
factor is low, end zone heating increases.
¾ Partial loss of excitation may cause pole
slipping-highly detrimental to the machine.
¾ During failure of field, field suppression
shall be cut off from circuit and active
load decreased to 60% rated within 30 sec
and to 40% in next 1.5 minutes.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Rotor Limit
Over Excited
Stator Limit
PF=0.85
Under Excited
X Rotor Limit
Over Excited
Stator Limit
PF=0.85
Under Excited
-R R
-X Z = (KV2/MVA)*(CTR/PTR)
Xd
Rotor Limit
Generator Capability Curve: R-X Plot
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Xd
Rotor Limit
Generator Capability Curve: R-X Plot
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾ ZPU = (MVABase*ZOhms)/(KVBase2)
¾ ZOhms = ((KVBase2)*(ZPU)/(MVABase)
¾ Xd’Ohms = (21)2*(0.241)/(588)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾ Xd’Ohms = 0.18075*(CTR/PTR)
¾ Xd’Ohms = 0.18075*(4000/190.90)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾ ZPU = (MVABase*ZOhms)/(KVBase2)
¾ ZOhms = ((KVBase2)*(ZPU)/(MVABase)
¾ Xd Ohms = (21)2*(2.31)/(588)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾ Xd Ohms = 1.7325*(CTR/PTR)
¾ Xd Ohms = 1.7325*(4000/190.90)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾Offset Setting;
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Machine Operating
Limit in Leading PF
¾ OFFSET Setting:
¾ ZPU = (MVABase*ZOhms)/(KVBase2)
¾ ZOhms = ((KVBase2)*(ZPU)/(MVABase)
¾ Xd’Ohms = (21)2*(0.241)/(588)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾ OFFSET Setting:
¾ Xd’Ohms = 0.18075*(CTR/PTR)
¾ Xd’Ohms = 0.18075*(4000/190.90)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾ ZONE 1 Setting:
¾ ZPU = (MVABase*ZOhms)/(KVBase2)
¾ ZOhms = ((KVBase2)*(ZPU)/(MVABase)
¾ Xd Ohms = (21)2*(1)/(588)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾ ZONE 1 Setting:
¾ Xd Ohms = 1.7325*(CTR/PTR)
¾ Xd Ohms = 1.7325*(4000/190.90)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾ ZONE 2 Setting:
¾ ZPU = (MVABase*ZOhms)/(KVBase2)
¾ ZOhms = ((KVBase2)*(ZPU)/(MVABase)
¾ Xd Ohms = (21)2*(2.31)/(588)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾ ZONE 2 Setting:
¾ Xd Ohms = 1.7325*(CTR/PTR)
¾ Xd Ohms = 1.7325*(4000/190.90)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
¾Offset Setting;
¾ (Xd’Ohms )/2= 1.893 Ohms-Æ Secondary side
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Loss Of Excitation Protection (40)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
IF
VLN = 21000/1.7325
IF PTR = 21000/240V
100 Ohms, 10s
CTR = 20/1A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
IF VLN = 21000/1.7325
a
PTR = 21000/240V
100 Ohms, 10s
CTR = 20/1A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
VLN = 21000/1.7325
PTR = 21000/240V
100 Ohms, 10s
CTR = 20/1A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
VLN = 21000/1.7325
PTR = 21000/240V
100 Ohms, 10s
CTR = 20/1A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
PTR = 21000/240V
NGR Value = 100 Ohms
59GN Relay Range = 5.4V to 20V
IF-Max = (12121.21)
-------------------------
100
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
PTR = 21000/240V
NGR Value = 100 Ohms
59GN Relay Range = 5.4V to 20V
Fault at 90% location of Stator Winding from Phase
Terminal
Ground Fault Amps at fault location = (Maximum Ground Fault current * %A)/100
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
PTR = 21000/240V
NGR Value = 100 Ohms
59GN Relay Range = 5.4V to 20V
Fault at 90% Location of Stator Winding from Phase
terminal
Ground Fault Volts = (Ground fault Amps*PT secondary volts*NGR Resistance)
---------------------------------------------
(PT Primary Volts)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
59GN Relay Setting = 5.4V & TMS = 0.3
Relay Setting % Location “A” Fault Voltage Operating of
from Neutral Magnitude on Relay
relay terminals
5.4V 5% 6.92V
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Appendix:
59GN Relay Setting = 5.4V & TMS = 0.3
Relay Setting % Location “A” Fault Voltage Operating of
from Neutral Magnitude on Relay
relay terminals
5.4V 1% 1.38V Not Operate
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (50G):
Resistor Ground
Appendix:
PTR = 21000/240V
NGR Value = 100 Ohms
50G Relay Range = 0.1A to 0.4A
CTR = 20/1A
Maximum Ground Fault Amps = (Line to Neutral Voltage)
-----------------------
(NGR Resistance)
IF-Max = (12121.21)
-------------------------
100
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (50G):
Resistor Ground
Appendix:
50G Relay Setting = 0.1A
Relay Setting % Location “A” Fault Current on Fault Current on
from Neutral Primary side secondary side
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (50G):
Resistor Ground
Appendix:
50G Relay Setting = 0.1A
Relay Setting % Location “A” Fault Current on Fault Current on
from Neutral Primary side secondary side
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)
V
Grounding Transformer
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)
IF
VLN = 21000/1.7325
KVPri = 21kV
KVSec = 0.240kV
KVA = 70KVA
R = 0.913 Ohms
Full Load current in Primary wdg = 3.33A
Ground Fault Impedance = 3640.004 Ohms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)
IF
a
VLN = 21000/1.7325
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)
IF
a
VLN = 21000/1.7325
Ratio = 21000/240
= 87.5
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)
¾Setting Criteria: Typical Recommended
setting for IDMTL 59GN relay is 5.4V &
TMS is 0.3
¾Typical Recommended setting for
Definite Time 59GN relay is 5V & 2s for
Stage-I and 15V & 1s is for Stage-II.
¾Neutral Grounding Resistor value should
not be more than Rn = 106/2*3.14*C to
avoid harmful transient over voltage
because of the Ferro-resonance
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
100% Stator Ground Fault
Protection (27TN)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)
3rd Harmonic
Current circulate
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN):
3RD Harmonic Under Voltage Method
3rd Harmonic
Under voltage relay 3rd harmonic
voltage drop
Because capacitance
Is shorted
IF
IF
3rd Harmonic
Voltage at Neutral End reduced
3rd Harmonic
Voltage at Neutral End reduced
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN): 3rd
Harmonic Under Voltage Method
3rd Harmonic Present
At normal Load
Condition on both end
Numerical Relay
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)
Control circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59TN)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59TN):
3RD Harmonic Over Voltage Method
IF
IF
3rd Harmonic
Over voltage relay
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59TN)
Control circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection
(59TN+27TN)
¾ 3rd Harmonic Ratio Method;
In this method; 3rd Harmonic voltage will
be measured at both sides, at the neutral
(V3N) & at the terminal (V3T) of generator
Normally, Ratio will be constant for
balance load condition
Ratio will be modified when ground fault
occurs
Ground fault will not detected at null point
(Midpoint of winding)
Overlapping scheme (59TN+27TN+59GN)
is reqd. to detect ground fault at null point
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: 3rd
Harmonic Ratio Method
Method:1
V3N V3T
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: 3rd
Harmonic Ratio Method
Method:2
V3N V3T
Control circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Sub-Harmonic Injection Method;
Sub-Harmonic voltage is injected through
an injection transformer between the
grounding element of the generator &
ground
Usually sub-harmonic frequency is 1/4th of
Fundamental frequency. i.e. 12.5 Hz for
50Hz & 15 Hz for 60Hz relay
This scheme provides ground fault
protection with generator energized or
standstill
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Fn = 50Hz
Xco = 1
- ---------
2*3.14*Fn*C
IC = (Vn / Xco)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Finj = 12.5Hz
XCo = 1/(2*pi*F*C)
12.5Hz
XL = 2*pi*F*L
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Sub-Harmonic Injection Method;
During Ground Fault condition; 12.5Hz
current flows through Ground ckt. The
fault resistance appears in parallel with
shunt capacitances to ground. Thus, the
impedance that limits the sub-harmonic
current & this also make the current
change
Capacitive Reactance Increases
Inductive Reactance Decreases
Relay Operates if 12.5Hz Ground fault
current is more than threshold value
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
Equivalent Circuit
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Sub-Harmonic Injection Method;
Iinj = (Einj)/ (Zinj + Rn + ZC Total)
Where;
Einj = Injection Voltage
Zinj = Injection TR Leakage Impedance
Zinj = (Rinj + j*Xinj)
Rn = Grounding resistor
ZC = Capacitive impedance of total ckt.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Appendix;
Iinj = (Einj)/ (Zinj + Rn + ZC Total)
Where;
Einj = 56V
Zinj = (36 + j*125)
Finj = 12.5 Hz
Rn = 1212 Ohms
CTotal = 2.035 microF
ZC = (106) / (2*pi*12.5*2.05)= -j*6214 Ohms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Appendix;
Zinj = (36 + j*125)
Where;
Rinj = 36 Ohms
Xinj = 125 Ohms
Now;
Xinj = (2*pi*50*L)
125 = (2*3.14*50*L)
L = 0.331H
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Appendix;
Xinj at Low frequency = (2*pi*12.5*L)
= (2*3.14*12.5*0.331)
= 25.98 Ohms
Now;
Zinj = (36 + j*25.98) Ohms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Appendix;
¾ Relay setting is 20mA
¾ Iinj during Normal load condition is;
Iinj = (Einj)/ (Zinj + Rn + ZC Total)
= (56) / (36+j*25.98)+1212-(j*6214)
= 0.0088A @ 78.67o
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Appendix;
¾ Iinj during Fault condition is;
Iinj = (Einj)/ (Zinj + Rn + Z’C Total)
Where;
Z’C = (ZC * RF) / (ZC + RF)
RF = Fault resistance
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Method
¾ Appendix;
¾ Iinj during Fault condition is;
Iinj = (Einj)/ (Zinj + Rn + Z’C Total)
= 0.0258A @ 6.67o
Relay will issue trip command
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Transformer & Grounding Resistor
Method:1
Grounding
Resistor
Injection
Transformer
IF
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Injection Transformer & Grounding Transformer
Method:2
Grounding
Transformer
Separate Injection
Transformer
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection through Grounding Resistor
Method:3
Sub-Harmonic
Voltage Injection
Through Grounding
Transformer
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in 7UM62 Relay
25VAC
Relay Measures;
Rm = (V@20Hz)
---------
(I@20Hz)
IF
Operates;
If Rm < Rset
IF
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in MICOMP345 Relay
Band pass
Filter range
Is 15 to 25Hz
Or
Low Pass
Filter (Cut of
Freq. 45Hz
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection: Sub-Harmonic
Voltage injection Method in MICOMP345 Relay
NGR
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): DC
Injection Method
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): DC
Injection Method
Slip Rings Negative Potential Biasing
IF
IF
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F):
Potentiometer Method
FCB
R1
64R
R2
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): Low
Frequency Injection Method
LC-filter is the low-pass
Filter to removed high
Frequency Rotor current
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): Low
Frequency Injection Method
Low Frequency voltage output is the
Square wave output
Capacitive coupling blocks normal DC
Field voltage, preventing discharge of
Large current
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): AC
Voltage Injection Method in 7UM62
Fundamental Frequency Injection
Rm = UE
----------
IEE
Relay Operates;
If Rm < Rset
36V/45V
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Rotor Ground Fault Protection (64F): AC
Voltage Injection Method in 7UM62
Generating square wave voltage
Rm = Ug
-------
Ig
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator: Front & Side view
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Generator: Front view
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
DOBLE ENGINEERING PVT. LTD
305-SAKAR, OLD PADRA ROAD,
VADODARA.
PH: (+91)(265) 655 77 15 & Fax: (+91)(265) 235 62 85
Cell: (+91) 94267 47545 / 98980 55956
E-MAIL: kdave@doble.com
infokamindave@yahoo.com
Website: www.doble.com
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery