TEST REPORT
RENDERED TO
Franklin International
2020 Bruck Street
Columbus OH, 43207
PRODUCT EVALUATED:
Finger Joint Stud/HRA Adhesive
60 Minute - Full Scale Vertical, Fire Endurance Test, Loaded Wall Assembly
EVALUATION PROPERTY:
Tested to ASTM E119-15 “Standard Test Methods for Fire Tests of Building
Construction and Materials” modified by ASTM D7470-08 (2015)
This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client.
Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any
party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this
report. Only the Client is authorized to copy or distribute this report and then only in its entirety. Any use of the Intertek name or
one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by
Intertek. The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply
that the material, product, or service is or has ever been under an Intertek certification program. Page 1 of 14
Franklin International June 29, 2016
Project No. 102532954MID-005 Page 2 of 14
Table of Contents
1 Introduction
The Middleton, Wisconsin fire testing laboratory of Intertek Testing Services NA
(Intertek)/Warnock Hersey conducted a Vertical Fire Test for Franklin International. The test
sample(s) were received at the laboratory in June 2016 in good condition. This report gives the
results of the evaluation of a fire resistance property of a finger jointed stud wall. The test
results described in this report are limited to the submitted items.
The test was conducted in accordance with ASTM E119, 2015 edition modified by ASTM
D7470-08 (2015) for a loaded wall design. ASTM E119 conditions of acceptance for
temperature and passage of flame or hot gases are to be recorded and reported but are not
acceptance criteria for the end-jointed lumber adhesive qualification and the ASTM E119 hose
stream test is not required per ASTM D7470. Acceptance criteria for ASTM D7470 per section
9.1 is as follows, the wall assembly shall sustain the applied load for a minimum of 60 min,
rounded to the nearest minute.
The test was conducted at neutral pressure in accordance with ATM E119.
Sheathing (1) Layer of 5/8” Type X Drywall each side with all joints and
fastener heads covered with compound and joints taped.
Insulation 3 ½” x 16” 2.5 pcf density. (Roxul AFB)
Fasteners Wood to Wood Maze 16d (3-1/2 inch) common nails.
Drywall to wood 2-1/4 in Type W drywall screws 12” O.C.
Franklin International June 29, 2016
Project No. 102532954MID-005 Page 4 of 14
After positioning the assembly frame over the furnace opening, the burners were ignited and a
timer started. Temperatures within the furnace were monitored using thermocouples and the
data recorded. The burners were controlled to keep the furnace temperatures within the
allowable limits specified in the test standards. These temperature data are included in this
report.
Periodic observations were made of the exposed and unexposed surfaces of the test assembly
during the fire endurance test. These observations are included in this report.
Pressure taps were installed through the furnace wall adjacent to the test assembly at two
heights (top and 40” above the sill) to measure furnace pressure. The neutral pressure plane
within the furnace was maintained at the top of the wall as specified in the test standards. This
pressure data is included in this report.
The superimposed load applied to this wall was 21,663 lbf, equal to 1,895 lb/per stud. The
calculation for this can be found in Figure 7.
The following test equipment was used to collect and monitor test conditions.
4.3. Hose-Stream
A hose stream was not conducted per ASTM D7470.
5 Conclusion
The loaded wall assembly comprised of Franklin Advantage EP-950A emulsion w/ Hardener
200 MDI (EPI) in conjunction with Gilman Building Products Southern Pine No. 2 Finger Jointed
Studs, (1) layer of 5/8” thick type X drywall on each side and 3 ½” thick 2.5 pcf density (Roxul
AFB) Insulation, as described herein, complied with ASTM E119 (2015) modified by ASTM
D7470 for a “60 Minutes” rating with a superimposed 17,058 lb load (1,895 lbs per stud). Refer
to Southern Pine Inspection Bureau Report titled Gilman Franklin FJ May 2016 for finger joint
strength qualification results.
This report does not automatically imply product certification. Products must bear the Warnock
Hersey registered certification mark to demonstrate compliance.
APPENDIX A
Test Data, Photographs and Diagram
Franklin International June 29, 2016
Project No. 102532954MID-005 Page 8 of 14
lbs
Dead load: Sample wall 872
Refractory/beam 2209
Knee wall 1272
Wing walls 252
Wall load: 2x4 FJ #2 SYP @ 16oc 17058
Total target load: 21663
Franklin International June 29, 2016
Project No. 102532954MID-005 Page 13 of 14
PHOTOGRAPHS
BEFORE TEST
Franklin International June 29, 2016
Project No. 102532954MID-005 Page 14 of 14
REVISION SUMMARY
DATE SUMMARY
June 29, 2016 Original Issue Date