Professional Documents
Culture Documents
To complete the requirements of the course refrigeration and air conditioning system lab.
Objectives:
To calculate the cooling load needed to remove the amount of heat energy from a room by the
Refrigeration and air conditioning equipment to maintain the room at indoor design temperature
when worst case outdoor design temperature is being experienced.
Terminology:
Before we go further in cooling load calculations, we need to define and understand some
important terminology.
Sensible Heat Gain: is the energy added to the space by conduction, convection and/or radiation.
Latent Heat Gain: is the energy added to the space when moisture is added to the space by means
of vapor emitted by the occupants, generated by a process or through air infiltration from outside
or adjacent areas.
Space Cooling Load: is the rate at which energy must be removed from a space to maintain a
constant space air temperature.
1. External Loads
2. Internal loads
Both external and internal loads consist of sensible as well as latent heat
components
Buildings in general may be either externally loaded or internally loaded.
In externally loaded buildings the cooling load on the building is mainly due to the heat transfer
between the surroundings and internal conditioned space.
In internally loaded buildings the cooling load is mainly due to internal heat generating sources
such as occupants or appliances or processes. For example: A theater.
Knowledge of whether the building is externally loaded or internally loaded is essential for
effective system design.
COOLING LOAD CALCULATION FOR A TYPICAL ROOM:
Cooling load for the room was being carried out using the CLTD method.
Room dimensions:
The room consist of two doors, one window and one attach bathroom.
Height = 10 feet
Width = 10 feet
Equipments:
2 Fans
4 energy saver bulbs
1 printer
2 Laptop computers
1. : External Cooling Loads:
Wall # 1:
Q= UACLTD
∆T = To – Ti
To = 37, Ti = 25
∆T = 12
R= 0.53, U= 1.89
A = 9.29 m2
Q = UA∆T
U = 1.89
Area = 19.68 m2
Q = UA∆T
U= 1.89
A = 7.78 m2
ROOF:
Q = UACLTD
= 0.40
U = 2.47
At R = 0.40 Roof no.1 ( from ASHRAE 1997 )
CLTDc = (25.5-25)+(33-28.4)
= 5.1
Q = (2.47)(22.29)(25.1)
= 1382 watt
DOOR # 1:
Q = UA∆T
R = 0.842
U = 1.19
A = 1.95 m2
Q = (1.19)(1.95)(12)
= 27.85 watt
DOOR # 2:
Q =UA∆T
R = 0.842, U = 1.19
A = 1.51 m2
Q = (1.19)(1.51)(12)
= 21.56 watt
WINDOW:
Q = UA∆T
R = 0.249 , U = 4.02
A = 1.11 m2
Q = (4.02)(1.11)(12)
= 53.55 watt
OCCUPANCY:
No. of occupants = 3
Qsensible = qs x n x CLF
Qlatent = qL x n
n = no. of people
LIGHTS:
Q = W x BF x CLF
BF = Ballast factor
BF = 1.25 for fluorescent lighting
Q = (4)(25)(1)(1)
= 100 watt
FANS:
Q = PEF CLF
EF = fan efficiency
Q= (2)(75)(0.75)(1)
= 112.5 watt
Laptop:
Q = 2 x 32.5 = 65 watt
VENTILATION:
Qs = 0.0204 cmm x ∆T
Qs = (0.0204)(0.424)(3)(41-25)
QL = 50 (0.424)(3)(0.014- 0.01)
Qinternal + Qventilation
= 4661.45 / 3516.7
= 1.325 TR