TEST REPORT
REPORT NO : 2019CB0252 PAGE : 1 OF 3
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS
International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or
forms (including but not limited to advertising purposes) without written approval from the Managing Director, SIRIM QAS International
Sdn. Bhd. Please refer the last page for Conditions Relating to the Use of Test Report.

THIS TEST REPORT IS ISSUED IN SECURED PDF SOFTCOPY

Applicant : TECHNO FRAME SOLUTIONS SDN. BHD.


Lot 197, Jalan Industri 3/7,
Rawang Integrated Industrial Park,
48000 Rawang, Selangor Darul Ehsan.
Manufacturer : TECHNO FRAME SOLUTIONS SDN. BHD.
Lot 197, Jalan Industri 3/7,
Rawang Integrated Industrial Park,
48000 Rawang, Selangor Darul Ehsan.
Product : M6 EYE ANCHOR
Reference Standard / : Company’s Specification :
Method of Test - Pull Out Test
Description of sample / : Six (6) samples of M6 Eye Anchor were received for testing.
Description of Test Brand : Techno Frame
Specimen
Date Received of : 05 December 2018
Complete Application
Job No. : J20181432338
Description of Test : The test results for the submitted test samples are described from Page 2
Results / Overall Test to Page 3 of this test report.
Result
Issued Date : 12 February 2019

Approved Signatories;

...................................................... ......................................................
(MOHAMAD RAZIQI BIN SHA'DUN) (RAJA NOR SIHA BINTI RAJA ABDUL HANAN)
Testing Executive Head
Civil & Construction Section
Testing Services Department
REPORT NO : 2019CB0252 PAGE : 2 OF 3
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS
International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or forms
(including but not limited to advertising purposes) without written approval from the Managing Director, SIRIM QAS International Sdn. Bhd.
Please refer the last page for Conditions Relating to the Use of Test Report.

STANDARD REFERENCE : COMPANY’S SPECIFICATION


TEST RESULTS : TEST 9
COMPONENTS : 1) M6 EYE ANCHOR
2) 150 x 150 x 150 CONCRETE CUBE 25 N/mm2

SAMPLE REFERENCE RESULTS REMARKS

M6 Eye Anchor was fractured


Sample 1 The maximum load is 5.88 kN
after test.

M6 Eye Anchor was fractured


Sample 2 The maximum load is 6.48 kN
after test.

M6 Eye Anchor was fractured


Sample 3 The maximum load is 5.62 kN
after test.

M6 Eye Anchor was fractured


Sample 4 The maximum load is 5.97 kN
after test.

M6 Eye Anchor was fractured


Sample 5 The maximum load is 5.80 kN
after test.

M6 Eye Anchor was fractured


Sample 6 The maximum load is 6.41 kN
after test.
REPORT NO : 2019CB0252 PAGE : 3 OF 3
This Test Report refers only to samples submitted by the applicant to SIRIM QAS International Sdn. Bhd. and tested by SIRIM QAS
International Sdn. Bhd. This Test Report shall not be reproduced, except in full and shall not be used for any purpose by any means or forms
(including but not limited to advertising purposes) without written approval from the Managing Director, SIRIM QAS International Sdn. Bhd.
Please refer the last page for Conditions Relating to the Use of Test Report.

Photo : Shows samples after test