Professional Documents
Culture Documents
Abstract: It has been reported that a wind farm consisting of multiple identical or similar DFIGs may cause the small-signal
angular instability of power system. In this paper, the phenomenon is studied from the perspective of Bode diagram. Firstly, the
stability analysis method of Bode diagram derived from the Nyquist stability criterion and the self-oscillation theory are
introduced respectively, which have similar conclusions. Subsequently, closed-loop interconnected model of multi-machine
power system connected with multiple DFIGs is established. Impact of multiple identical grid-connected DFIGs on the
small-signal angular stability of power system is studied via Bode diagram. The analysis shows that with the number of DFIGs
increases, the phase curve of Bode diagram of the open-loop transfer function does not change, and the amplitude curve gradually
shifts upward. According to the stability margin defined in the Bode diagram method, the stability of the closed-loop system
decreases. Finally, the theoretical analysis is verified by two example power systems. The simulation results show that the
instability of power system connected with multiple identical DFIGs can lead to small-signal angular instability in the power
system.
Key Words: DFIG, small-signal angular stability, Bode diagram, Nyquist stability criterion, self-oscillation theory
1241
and G ( s ) H ( s ) is 1, the motion of the curve around the There is a correspondence between the Nyquist diagram
origin point (0, j 0) in the F ( s ) plane is equivalent to the and the Bode diagram, and the above relative stability index
can also be embodied in the Bode diagram, as shown in Fig.
motion around (1, j 0) in the G ( s ) H ( s ) plane. 3.
Let N represents the number of open-loop transfer
dB dB
function G ( jZ ) H ( jZ ) counterclockwise enclosing the
point (1, j 0) , and P represents the poles of open-loop 0
Zc
Z 0
K g 0dB Zc
Z
K g ! 0dB
transfer function G ( jZ ) H ( jZ ) which are located in the
right half of s plane. According to the Nyquist stability M M
criterion, the closed-loop system is stable when N equals to
P , otherwise the system is unstable. J !0 Z 180q Z
180q
Zg Zg J 0
In engineering control systems, the system must be
required to be stable, and be required with a certain stability
margin. System stability margin indicates the relative Fig. 3. Stability margins in Bode diagram
stability of the system.
Generally, the closer the curve of G ( s ) H ( s ) is to the The amplitude boundary frequency Zc is the frequency
point (1, j 0) , the more the oscillation is. Therefore, the at the intersection point of the amplitude curve of the Bode
stability margin of the system can be measured by the degree diagram and the real axis, and the phase angle margin
of closeness of the curve G ( s ) H ( s ) and the point (1, j 0) , J 180q M (Zc ) is the difference between the phase of the
which is often expressed by the phase angle margin J and intersection point and the axis 180q .
the amplitude margin K g , as shown in Fig. 2. The phase boundary frequency Z g is the frequency at the
intersection point of the phase curve of the Bode diagram
Im and the axis 180q , and the amplitude margin K g is the
amplitude value of the intersection point.
2.2 Derived from the Self-oscillation Theory
1
Kg In the negative feedback control system shown in Fig. 1,
Zg Re the input variable is X i ( s ) , the output variable is X o ( s ) ,
1 J 0 and the feedback variable is X f ( s ) . The net input signal
Zc
X d ( s ) is generated on the comparison of X i ( s ) and
X f ( s ) , and applied to the input terminal. The relationship
between them is:
X d (s) X i (s) X f (s)
Fig. 2. Stability margins in the Nynquist diagram X o (s) G ( s) X d ( s)
In Fig. 2, the curve G ( s ) H ( s ) intersects the unit circle X f (s) H (s) X o (s) G (s) H (s) X d (s)
centered on the origin at the point where the frequency is Zc , When the negative feedback control system generates
which is defined as the amplitude boundary frequency. self-oscillation, X i ( s ) 0 , there is still an output signal:
M (Zc ) is the phase angle at Zc of the open-loop transfer
X d (s) 0 X f (s) G ( s ) H ( s ) X d ( s )
function. The phase angle margin J 180q M (Zc ) is
defined as the additional phase angle required to make the Therefore, the condition that the negative feedback
system reach critical stability. Normally, the system is stable control system generates self-oscillation is:
if J ! 0 , and the system is unstable if J 0 . G ( s) H ( s) 1
The curve G ( s ) H ( s ) intersects the negative real axis at
Decompose it into amplitude and phase conditions:
the point where the frequency is Z g , which is defined as the
1 G ( s) H ( s) 1
phase boundary frequency. Kg is
G ( jZ g ) H ( jZ g ) G ( s ) H ( s ) (2n 1) u 180q
defined as the amplitude margin, which can be expressed in The amplitude condition can be written as
decibels (dB) as 20 lg G ( s ) H ( s ) 20 lg G ( s ) 20 lg H ( s ) 0 .
K g (dB) 20 lg K g 20 log G ( jZ g ) H ( jZ g ) . Normally, It can be found that the conditions of system instability
the system is stable if K g ! 0dB , the system is unstable if can also be derived by the self-oscillation theory. The
conclusion is the same as in Section 2.1. The stability
K g 0dB . margins in the previous section also apply.
1242
3 Impact of Multiple Identical Grid-connected 3.1 The Case of One DFIG
DFIGs on the Small-signal Angular Stability of When only one DFIG is connected to the multi-machine
Power System power system, assuming the open-loop transfer function of
Vw the DFIG is H ( s ) , the interconnection model shown in Fig.
P1 jQ1 5 can be simplified to Fig. 6.
DFIG1
Pw jQw
ª 'Pw º
Ă
T
PN jQN
DFIG N
H(s)
Fig. 4. Multi-machine power system connected with a wind farm Fig. 6. The interconnection system consists of a single DFIG
Fig. 4 shows the multi-machine power system connected The system shown in Fig. 6 is a positive feedback control
with a wind farm. Assuming there are N DFIGs in the wind system. Since the negative feedback control system is
farm, the output power of each DFIG is Pk jQk , the total studied in Section 2, the conclusions need to be corrected to
output power of the wind farm is Pw jQw , and the voltage be applied to the system shown in Fig. 6.
The closed-loop transfer function of the system shown in
of the bus connected with the wind farm is Vw . For the
Fig. 6 is:
multi-machine power system, the open-loop transfer
function is: G ( s)
)( s)
1 G ( s)H( s)
'Vw g P ( s )'Pw gQ ( s )'Qw
ª 'P º ª 'P º
The characteristic function of the system is:
¬ª g P ( s ) gQ ( s ) ¼º « w » G (s) « w »
¬ 'Qw ¼ ¬ 'Qw ¼ F (s) G ( s)H( s) 1
g P ( s )hP ( s ) gQ ( s )hQ ( s ) 1
where G ( s ) ª¬ g P ( s ) gQ ( s ) º¼ .
Analogy to the derivation in Section 2.1, it can be
The open loop transfer function of each DFIG is: concluded that the closer the curve G ( s )H ( s ) is to the point
'Pk hP ( s )'Vw (1, j 0) , the greater the oscillation is. Therefore, in this
'Qk hQ ( s )'Vw situation, the phase boundary frequency Z g should be
For the entire wind farm, it can have: corrected to the frequency of the intersection point of the
phase curve of the Bode diagram and the axis 0q , and the
ª 'Pw º ª 'Pk º amplitude margin K g is the amplitude of the intersection
« 'Q » ¦ « 'Q » ¦H k ( s )'Vw
¬ w¼ ¬ k¼ point.
It can also be analogized to the derivation in Section 2.2,
ª hP ( s ) º and the condition for the system to generate self-oscillation
where H k ( s ) « h (s) » .
¬ Q ¼ is:
H N (s)
1243
dB dB
dB
Zc K g 0dB Zc
0 Z 0 Z
K g ! 0dB
0 Z
N=3
M M N=2
20lg3 N=1
J !0 M 20lg2
0q Z 0q Z
Zg Zg J 0
0q Z
Zg
Fig. 7. Stability margins in Bode diagram
In this situation, the open loop transfer function of the Fig. 9 shows the configuration of multiple DFIGs
positive feedback control system as shown in Fig. 5 can be connected to an infinite bus. The infinite bus is equivalent to
written as: a synchronous machine with an extremely large inertia
constant. The output power of each DFIG is 0.5p.u.
¦ G ( s)H k (s) N G ( s)H ( s) DFIG 1
k
Ă
N ª¬ g P ( s )hP ( s ) gQ ( s )hQ ( s ) º¼
DFIG k
It can be seen from Eq. (13) that when the DFIGs with the
Ă
1244
shown in the third column of Table 1. The results of the 4.2 Multiple DFIGs Connected to the Two-area
study are consistent with the conclusions given in Section 3. Four-machine Power System
It should be pointed out that the phase curves are not
Fig. 11 shows the configuration of the two-area
exactly the same in the three cases, the amplitude curve is
four-machine power system connected with multiple
not the offset upwards and downwards exactly, and the
identical DFIGs. The wind farm is connected to the system
difference between the amplitude curves is not 20 lg N
at bus 6. The output power of each DFIG is 1p.u.
accurately. That is because the increase of the wind farm N identical DFIGs
-2 0
-4 0 G2 G4
-6 0
2 L6 L8 4
-8 0
-1 00
3 60
Fig. 11. Configuration of the two-area four-machine power system
connected with multiple DFIGs
2 70
Phase (deg)
1 80
90
When the number of DFIGs connected to power system is
0
1, 2, and 4, the three synchronous oscillation modes of the
-9 0
system are shown in Table 2.
-1 80
1 0-1 1 00 1 01 1 02 1 03 Table 2: Oscillation Modes and Amplitude Margin of Bode
Frequency (rad/s) Diagram with Different Number of DFIGs Connected in Fig. 11
(a) N=1 Number of Amplitude
0 Oscillation Modes
DFIGs Margin
-0.1712 + 5.5057i
Magnitude (dB)
-2 0
-4 0
1 -0.1467 + 5.7327i 18
-0.0383 + 3.0129i
-6 0
-0.1763 + 5.4016i
-8 0 2 -0.1467 + 5.7369i 13
-1 00
-0.0317 + 2.9995i
3 60 -0.1558 + 5.0583i
2 70 3 -0.1497 + 5.7436i -12
Phase (deg)
1 80 0.0140 + 2.8904i
90
0
It can be seen from the second column of Table 2 that
-9 0
when the identical DFIGs are connected successively, the
-1 80
1 0-1 1 00 1 01 1 02 1 03 damping of the inter-area oscillation mode gradually
Frequency (rad/s) reduced. When the number of DFIGs is increased to 4, the
(b) N=2 real part of the inter-area oscillation mode becomes positive,
and the system instability occurs. The Bode diagrams of
0
three cases are shown in Fig. 12. It can be seen from Fig. 12
Magnitude (dB)
-2 0
that when the number of DFIGs increases, the amplitude
-4 0 margin of the system gradually decreases, as listed in the
-6 0 third column of Table 2. The results of this example are also
-8 0
consistent with the conclusions given in Section 3.
20
-1 00 10
Magnitude (dB)
3 60
0
2 70
Phase (deg)
-1 0
1 80
-2 0
90
-3 0
0
-4 0
-9 0
4 50
-1 80
1 0-1 1 00 1 01 1 02 1 03
Phase (deg)
4 05
Frequency (rad/s)
3 60
(c) N=4 3 15
1245
20
5 Conclusions
10
Magnitude (dB)
4 05
defined in Bode diagram method, the stability of the
3 60
closed-loop system will decrease. Finally, the theoretical
3 15
analysis is verified by two example power systems. The
simulation results show that the instability of power system
2 70
2 2 .5 3 3 .5 connected with multiple identical DFIGs may lead to
Frequency (rad/s) dynamic instability in the power system.
(b) N=2 References
20 [1] J. G. Slootweg and W. L. Kling, The impact of large scale
10 wind power generation on power system oscillations, Elect.
Magnitude (dB)
0 Power Syst. Res., vol. 67, no. 1, pp. 9-20, Oct. 2003.
-1 0 [2] J. J. Sanchez-Gasca, N. W. Miller, and W. W. Price, A modal
-2 0 analysis of a two-area system with significant wind power
-3 0
penetration, in Proc. Power Systems Conf. Expo., 2004.
-4 0 [3] A. Mendonca and J. A. P. Lopes, Impact of large scale wind
-5 0
power integration on small signal stability, Future Power
4 50 Syst., pp. 1–5, 2005.
[4] D. Gautam, V. Vittal, and T. Harbour, Impact of Increased
Phase (deg)
4 05
Penetration of DFIG-Based Wind Turbine Generators on
3 60
Transient and Small Signal Stability of Power Systems, IEEE
Trans. Power Syst., vol. 24, no. 3, pp. 1426-1434, Aug. 2009.
3 15 [5] G. Tsourakis, B. M. Nomikos, and C. D. Vournas, Effect of
wind parks with doubly fed asynchronous generators on
2 70
2 2 .5 3 3 .5
small-signal stability, Electr. Power Syst. Res., vol. 79, no. 1,
pp. 190–200, Jan. 2009.
Frequency (rad/s)
[6] L. Fan, Z. Miao, and D. Osborn, Impact of doubly fed wind
(c) N=4 turbine generation on inter-area oscillation damping, in Proc.
IEEE Power Eng. Soc. Gen. Meeting, 2008, pp. 1–8.
Fig. 12. Bode diagram of the two-area four-machine power system [7] G. Tsourakis, B. M. Nomikos, and C. D. Vournas,
connected with multiple DFIGs Contribution of Doubly Fed Wind Generators to Oscillation
Damping, IEEE Trans. Energy Convers., vol. 24, no. 3, pp.
783-791, Sep. 2009.
1246