Analysis of Transient Stability with SSSC and UPFC with Multi-Band PSS in Two
Area Multi-Machine System

Abubakar Siddique1, Yonghai XU1, Waseem Aslam1, Muhammad Rasheed2, Maham Fatima2
1
School of Electrical & Electronics Engineering, North China Electric Power University, 102206, Beijing, China
2Department of Electrical Engineering, University of Engineering and Technology (UET), Pakistan

e-mail: engr.abs@yahoo.com

Abstract—Power system stability plays a vital role in the prevented further development of highly interconnected
growth of large interconnected power systems. Today‘s power networks. The growth of large interconnected power
system continues to expand in an exponential way due to an systems demands faster response to maintain stability. For
extensively automated need of both domestic and industrial economic reasons and to have high reliability,
needs. The ever-growing demand of power system network has interconnections are unavoidable and therefore the power
resulted in rotor angle oscillations and voltage instability. In system oscillations are also inevitable. However, these
this paper, Static synchronous series compensator (SSSC) and oscillations decay with respect to time. Small changes in
Unified power flow controller (UPFC) are employed to analyze load in power system network initiate power system
the transient stability of the power network with multi-band oscillations and during large disturbances, it becomes worse
power system stabilizer (MB-PSS). The two area four machine [6], [7].
power network has been considered to illustrate the Since 1960s numerous theoretical studies and field tests
performance of UPFC and SSSC in coordination with MB-PSS. have been conducted by power engineers regarding the
To investigate the achievements of the designed system stability issues. According to the nature of power system
simulation has been carried out in MATLAB/Simulink oscillations, controllers are developed to increase the
software. The simulation results show that UPFC with MB-
damping torque. The damping of power oscillations is
PSS controller gives a better improvement in transient stability
possible by using power system stabilizers and FACTS
compared with SSSC coordinated with MB-PSS.
devices. Power system stabilizers are incorporated in
Keywords-component; FACTS; MB-PSS; generator excitation systems and are used to damp the
MATLAB/Simulink; SSSC; Transient Stability; UPFC generator electro-mechanical oscillations by taking
generator speed and electrical power as inputs.
Therefore it is also necessary to develop computationally
I. INTRODUCTION intelligent controllers based FACTS devices for faster and
Today's power system network is highly interconnected accurate control action [8-10]. The target of this paper is to
in which synchronous generators rotate at the same speed analyze stability enhancements in power system network by
and also the power flow in transmission lines should be free FACTS devices SSSC and UPFC.
from oscillations during normal conditions [1]. When a In this paper, Static synchronous series compensator
small interruption appears in the power network, it leads to (SSSC) and Unified power flow controller (UPFC) are
low-frequency electromechanical oscillations. Due to these employed to analyze the transient stability of the power
oscillations, the power system variables like line frequency, system with and without multi-band power system stabilizer
Bus voltages, Line currents and generator speeds also (MB-PSS). The rest arrangement of the remaining paper is
becomes oscillatory. For enhancement in the reliability of succeeded as follows: section 2 describes a schematic of
the power system and to increase the generation capacity, SSSC, UPFC, and MB-PSS. Section 3 presents the
the synchronous generators are interconnected, which MATLAB/Simulation model of SSSC and UPFC. Results
resulted in a power system oscillations of around 1-2 Hz [2], and discussion are described in section 4. Lastly, a
[3]. conclusion has been described.
The generator rotor is provided with damper windings to
damp the amplitude of oscillations. For enhancing the II. MODELING
response of the generators and to maintain synchronism, fast
excitation systems were then introduced, but it led to the A. SSSC
reduction in damping of oscillations. Therefore excitation SSSC is voltage source converter (VSC), it is linked in
systems with Power System Stabilizers (PSS) were widely series with the power line. By this connection SSSC control
used to damp these oscillations [4], [5]. transfer of power correctly in a line. In [7] the SSSC control
During the 1960s, the power stations were highly parameters, angle and degree of the voltage of the series
interconnected for economic reasons and to improve the converters are shown as independent variables and their
reliability of power supply. But these interconnections values are determined by the conventional load flow
resulted in low-frequency oscillations (0.1 - 1 Hz) in which iterative procedure. Therefore SSSC controls a wide range
the generators of one area swing against the generators of of power through a transmission line. The basic construction
neighboring areas. These low-frequency oscillations of an SSSC is denoted in Fig. 1.

978-1-5386-8311-8/18/$31.00 ©2018 IEEE 226


Figure 1. Schematic of an SSSC

MB-controller shown in Fig. 3, composed of three types


B. UPFC of filters namely, low-pass filter, intermediate-pass filter,
The schematic configuration of the UPFC is given in Fig. 2. and high-pass filter, which remove the local
UPFC linked to a transmission line with voltage source converters electromechanically disturbance, generated between
(VSC) names as shunt converters and series converters. They are
networks and global electromechanically oscillations
interconnected by dint of a common dc link storage element.
Commonly, the shunt VSC is treated as STATCOM and series one generated in the synchronized system. MB is designed to
as SSSC. The transformers associated at the output of converters to mitigate all form electromechanical oscillation generated in
give the isolation, customize voltage/current levels and also to a power network.
avoid dc link storage element being shorted due to the operation D. Multi-Machine Two-Area Power Network
of different switches. The real power can transmit in both
directions through DC link which provides connections to these In this paper two area multimachine system is
converters. Reactive absorb or generate through these converters considered for analysis of transient stability, shown in Fig. 4
independently at its owned AC output terminal. The current & Fig. 5, for both SSSC and UPFC. The considered test
flowing through the line and voltage source converter can system consists of two areas which are linked with one
exchange reactive and active power in the electrical network. another with the help of a weak tie line. This line elongated
up to 220 km, each generator is rated as 900MVA/20KV.

Figure 2. Schematic of UPFC

C. Multi-band Power System Stabilizer Figure 4. Two area multi-machine system with SSSC

Figure 5. Two area multi-machine system with UPFC

III. MATLAB SIMULATION MODEL


Power system subsists of two symmetrical areas which
are connected through a weak tie line of 230KV and
elongated up to 220 km. Each area has two coupled
Figure 3. Control system block diagram of MB- Controller generating units. Its behavior is very close to real-time

227
systems in actual operation. The load is represented in the each generator generates its out power about 700 MW.
system has constant impedances and split between the two Simulation design of power system with SSSC and UPFC
areas in such patterns that area 1 is supplying power to area are depicted in Fig.6 & Fig. 7 respectively.
2. Generator G2 considered the slack machine is such that

Figure 6. MATLAB simulation diagram with SSSC.

Figure 7. MATLAB simulation diagram

228
Figure 8. Performance SSSC and MB controller during 3 phase fault conditions.

Figure 9. Performance UPFC and MB controller during 3 phase fault conditions

229
From simulation results shown in fig. 8 and fig. 9, a his constructive technical consultations and ideas, which
comparison is made among the SSSC with MBPSS and always inspired and encouraged me during my research.
UPFC with MBPSS for transient stability analysis. It can be Also, I would like to express my earnest appreciation to my
seen that the torque angle stabilizes at t = 5 s, with SSSC in co-authors for their contribution in this work.
co-ordinate with MB controller whereas UPFC stabilizes the
torque angle at t = 3 s. The angular speed is stabilized at t = REFERENCES
3 s in the case of the UPFC incorporated with MB controller. [1] Prabha Kundur, “Definition and Classification of Power System
Terminal voltages stabilize at t = 4 s with SSSC, whereas Stability” IEEE TRANSACTIONS ON POWER SYSTEMS © 2004
the UPFC coordinated with MB controller maintains it at t = IEEE.
2 s. From above fig. 8 and 9, it can be concluded that MB- [2] P.M.Anderson, A.A. Fouad, “Power System Control and stability”,
The Iowa state University Press, AMES, IOWA, U.S.A.
PSS coordinated with UPFC is more effective as compared
[3] Narain G. Hingorani, Laszlo Gyugyi, “Understanding FACTS :
to the SSSC coordinated with MB-PSS for the improvement concepts and technology of flexible AC transmission systems”
in stability. It can also be seen that angle deviation and the
[4] Sandeep Kaur, “Transient stability using facts controller” IJLTET,
post-fault settling time is less in UPFC coordinated with Volume 7,1 may 2016.
MB-PSS. [5] Gaber Shabib, “COORDINATED DESIGN OF A MB-PSS AND
STATCOM CONTROLLER TO ENHANCE POWER SYSTEM
IV. CONCLUSION STABILITY” International Journal of Electrical Engineering and
In this paper, the dynamic behavior of the design power Technology (IJEET), Volume 3, Issue 2, July September (2012).
system is compared with the SSSC in the coordination of [6] Divya Prakash, “Enhancing Stability of Multi-Machine IEEE 9 Bus
Power System Network Using PSS” International Journal of
MB-PSS and UPFC incorporated with MB-PSS. The Advanced Research in Electrical, Electronics and Instrumentation
comparison performance is evaluated under the three-phase Engineering, Vol. 4, Issue 5, May 2015.
fault condition. Simulation has been carried out in [7] Ishwar Lal Yadav, “Stability Enhancement for Transmission Lines
MATLAB/Simulink software. It is declared from the using Static Synchronous Series Compensator” International Journal
simulation outcomes that there is an appreciable of Engineering Research & Technology (IJERT) Vol. 4 Issue 02,
enhancement in the system performance by employing of February-2015.
UPFC in coordination with MB-PSS for which settling time [8] C.R. Makkar and, L. Dewan,"Simultaneous coordination of Power
System Stabilizer and UPFC for improving dynamic stability of
and angle deviation is less as compared to SSSC multimachine system", 6th India International Conference on Power
incorporated with MB-PSS. Hence these MATLAB Electronics (IICPE) IEEE, 01 June 2015.
simulation outcomes validate that UPFC incorporated with [9] Abubakar Siddique, Yonghai Xu, Waseem Aslaml, Fadi M. Albatsh.
MB-PSS gives accurate results with a reduced size of “Application of series FACT devices SSSC and TCSC with POD
oscillations and with less settling time in initial condition controller in electrical power system network”, 2018 13th IEEE
when a fault occurred, as compared to SSSC in coordinated Conference on Industrial Electronics and Applications (ICIEA), 2018.
with MB-PSS. [10] Garima Aggarwal, “MATLAB/SIMULINK MODEL OF MULTI-
MACHINE (3-Machine, 9-Bus) WSCC SYSTEM INCORPORATED
ACKNOWLEDGMENT WITH HYBRID POWER FLOW CONTROLLER” 2015 Fifth
International Conference on Advanced Computing & Communication
I would like to thank my respectable teacher Prof. Technologies.
Yonghai XU, for his time and guidance. I am thankful for