You are on page 1of 1

1.

FOR EQUIPMENT AND INSTRUMENT SYMBOLS REFER


TO DWG. NO. RA-635150 & RA-617120.

2. ALL INSTRUMENTS TAGS SHALL BE PREFIXED BY


963-C410.

3. GAUGE HATCH TO BE PROVIDED BY THE VENDOR.

TOTALIZER
FQI 4. BIRD SCREEN AND GOOSENECK VENT BY TANK
0034 VENDOR AS PER SAUDI ARAMCO SPECIFICATION
AND TO BE CORROSION RESISTANT MATERIAL.

5. TANK VENDOR TO PROVIDE HANDRAILS, PLATFORM


FI AND LADDERS FOR ACCESS TO INSTRUMENT
0034 ACCORDING TO SAUDI ARAMCK SPECIFICATION.

6. FOR FIRE WATER TANK NOZZLE DETAILS REFER


TO FIRE WATER STORAGE TANK DATA SHEET
FT
RE-622582.
0034
UG AG 7. LOCATE AT GRADE.

12"-POT-0505-16FE0U 12"-POT-0506-20FE0U 8. FOR FIRE WATER STORAGE TANK LEVEL ALARM


RA-635814-001
SETTING REFER TO FIRE WATER STORAGE TANK
LO
DATA SHEET RE-622582.
NOTE-15
PIT
1" 1" 9. DRAIN TO NEAREST HEADER.

10. LOW POINT DRAIN.


SCADA

12"-POT-0506-20FE0U
(NOTE-14) H 11. PROVIDED ACCESS, LADDER OR PLATFORM.

LI
12. TEST LINE.
0031
L
LL 13. FOR SPECIFICATION FOR CONTROL SYSTEM
FW PUMP CONTROLLER REFER TO RE-617063.
LI
0031 14. LOW LEVEL IN STORAGE TANK TO ACTIVATE
N13 RAD AUDIBLE AND VIRTUAL ALARM FIRE PUMP
LIT CONTROL PANEL.
NOTE-7
F 0031
LG (NOTE-5) 15. CLAMP ON TYPE ULTRASONIC FLOW METER
0032 MW3 TWO PROBES SHALL BE CLAMPED ON THE
24" (NOTE-4) 4" PIPE 5D STRAIGHT LENGTH SHOULD BE
8" MW4
4" N6 N7 N8 MAINTAINED IN THE UPSTREAM OF FLOW
24"
8" NOTE-3,5 METER.

16. PILOT FLOAT OPERATED SELF ACTUATED


NOTE-6 VALVE.
12" 12" 12" 12" N01
14"-FW-0506-1CS1U 17. READABLE FROM GARDE.
LO LO NOTE-16 OVERFLOW
N3 18. TANK FILLING MECHANISM SHALL ACTIVATE
1" N11 AT MAXIMUM OF 102mm BELOW OVERFLOW
NOTE-11 LEVEL.
LCV
0034
19. FIRE WATER TANK WILL BE FEED WITH TWO
NOTE-16 INLET CONNECTIONS.
12"-POT-0508-20FE0U 12" 12" 12" 12" NOTE-6
RA-636402-001 12" 12"-FW-0518-1CS1U
963-D-7402
LO LO NOTE-16 N10 RA-635784-003
FIRE WATER STORAGE TANK
N9
N12 NOTE 6,8

LCV HHLL =10465mm


0035 HLL =10359mm LEGENDS:
NOTE-16 LLL LOW LIQUID LEVEL
LLL =1212mm
12"-FW-0516-1CS1U TEST LINE (NOTE 12) LLLL =1100mm LLLL LOW LOW LIQUID LEVEL
RA-635784-002 NLL NORMAL LIQUID LEVEL
LO N5 LG
NOTE-11&12 HLL HIGH LIQUID LEVEL

HHLL HIGH HIGH LIQUID LEVEL

MW2
MW1
24"
24"

12"-FW-0505-1CS1U FEED DRAWING REFERENCE NO.


PB4784-C410-ME-DR-34651_REV3
N2 L0
1"

N4 REFERENCE DRAWINGS
4"-FW-0523-1CS1U
DRAIN MASTER PLAN RA-614081
L0
FOUNDATION PFD FIRE WATER PUMP STATION RA-636789-001
D PFD FIRE WATER PUMP STATION RA-636789-001
PFD FIRE WATER ZONE A RA-635725-001
ANTI VORTEX
PLATE PFD FIRE WATER ZONE B RA-635755-001
(TYP.) PFD FIRE WATER ZONE C RA-635785-001
PFD FIRE WATER ZONE D2 RA-635815-001
PFD FIRE WATER TUXEDO RA-635815-002
NOTE 9

TO STORM WATER DRAIN

D
NTS

25-00053-0006-777

MK AS/UFA
04/21/20 04/21/20

ITEM NAME FIRE WATER STORAGE TANK


D 04/21/20 ISSUED FOR APPROVAL

TAG 963-D-7402 25-00053-0006


RA-635784-002

STORAGE 3
2272 M
CAPACITY PIPING & INSTRUMENT DIAGRAM PID
FIRE WATER STORAGE AND PUMPING
DIAMETER 18 M
SHIPBUILDING

HEIGHT 11 M RAS AL KHAIR

C410 963 A RA-635784 001 D


CAD