FIRE ZONE R (CONDENSATE STORAGE AREA) 1. FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS,
SEE P&IDS FOR LEGEND SHEET.

2. HOSE CONNECTIONS FOR EMERGENCY BACKUP BY FIRE TRUCK SHALL BE


LOCATED AT LEAST 15 M FROM TANK DIKE WALL.

3. ORIENTATION OF HOSE CONNECTIONS SHALL FACE TO ROAD SIDE


CONSIDERING EASY ACCESS.

4. DRAIN VALVE SHALL BE PROVIDE AT EACH LOW POINT.

5. THE TIE-IN FLANGE BETWEEN CONTRACTOR AND VENDOR SHALL BE LOCATED


2.3M ABOVE THE TANK BOTTOM.

6. DELETED.

7. DELETED.

HOLDS :
1. RELEASED

3"
079-TK1002/A-11E 079-TK1002/A-11F
2" SEE DETAIL "A"
NOTE (TYP)
SEE DETAIL "A" 079-TK1002/A-11A
NOTE (TYP)

079-TK1002/A-11D 079-TK1002/A-11B 079-TK1002/A-11D 079-TK1001/A-11A

2"

079-TK1002/A-11C

079-TK1002/A-11C 3"
079-TK-1002 079-TK1002/A-11B

079-TK-1001

068-FF-1630-4"-1CG1F-NI NOTE 4 (TYP)


3022 D-068-1225-035
FOAM SOLUTION
FROM 068-UV-0404
068-FF-1632-3"-1CG1F-NI

3" ASME 150#


RF FLANGE
BV
3"
NOTE 2, 3 (TYP)
68MV3015
HOSE CONNECTION
2 1/2" BS 336 MALE

68MV3016
BV
3"
AS BUILT

T.KURODA H.ASANO H.ASANO


C1 AS BUILT
BV 01 JUL 16 01 JUL 16 01 JUL 16
S.KANNO H.NAITO H.ASANO
C0 FOR CONSTRUCTION 13 FEB 15 13 FEB 15 13 FEB 15
S.KANNO H.NAITO H.ASANO
068-FF-1631-3"-1CG1F-NI NOTE 4 (TYP) B FOR EPC
3023 D-068-1225-035 24 OCT 14 24 OCT 14 24 OCT 14
FOAM SOLUTION S.KANNO H.NAITO H.ASANO
A FOR REVIEW 27 AUG 14 27 AUG 14 27 AUG 14
FROM 068-UV-0405
068-FF-1633-3"-1CG1F-NI

3" ASME 150# NOTE 5


RF FLANGE 3" ASME 150#
BV RF FLANGE
3" DIKE WALL
NOTE 2, 3 (TYP)
68MV3017
HOSE CONNECTION
2 1/2" BS 336 MALE

68MV3018
BV 079-TK-1001/1002
3"

DETAIL "A"
TYPICAL INSTALLATION DETAIL FOR FOAM LINE

PIPING & INSTRUMENTATION DIAGRAM


D-068-1225-036

FIRE PROTECTION SYSTEM


LOW EXPANSION FOAM SYSTEM
IN CONDENSATE STORAGE AREA (3/3)

Project Code: 04 0-5151-20-3000 NONE

D-068-1225-036 C1

D R A
IN2-JUL- T6
1
2 0 1
UIL