Professional Documents
Culture Documents
ELEVATOR
123/INDSBY-ELC/1014
A B C D E F G H
1 1
# SDP ELEVATOR BY OTHER
3
BC10mm2
F1-3 3
From MCB 1phasa
LVMDP ….. A
R/S/T/N/G AC engine Room
MCB 1phasa
6A
Spare
5 5
Box SDP
3P & 1P # SDP by
R/S/T/L0/N/PE
Other
R S T Lo N PE
7 7
By Electrical Contractor
By Elevator Contractor
8 ARD 8
3phasa
9 9
Mechanical
Brake
U Traction
V
W
machine
10 2 10
1
CONTROL PE 0
DRAWING CHECKED APPROVED
101 Safety Gear REV. DATE
BY BY BY
CABINET 102
PROJECT :
ELEVATOR PA Mataram City
PB
(CCE) PG
VCC
PREPARED BY :
11 GND 11
SHIELD
DRAWING TITLE :
12
123/INDSBY-ELC/1014 1 12
1 1
2 2
3
FLU 3
SLU 1
4 4
Hoistway cable
nDLS
HOP COP Car top Box (CTB)
5 LT.2 5
Stop contac
indicator LAMP
ARRIVAL BELL
Intercom
Calling Floor
Can Bus
6 6
7 7
PARKING
CAR
1DLS
9
FIRE
9
POWER PIT
DRAWING TITLE :
Pit box
Blok Diagram Wiring hoistway & car
DRAWING NO. : REV.
12 123/INDSBY-ELC/1014 2 12
1 1
R S T
SDP by Other
380vac
N G DC : LOCK LIFT CONTACTOR
KC : RUNNING CONTACTOR
2
L0 2
PG : PULSE GENERATOR
N0
R S T F1 : MCB 3P
INV. : INVERTER
ARD 3~
U V W
3 3
R S T
ELCB BR
BRAKING
RESISTOR
4 4
Magnetig
T B1 B2 Brake
R L1 R U
U
L1
T1
MOTOR
5
S L2 S
L2 V
V 3
5
T2
T L3 T L3 W PHASA
T3 W
A1 A2
MC PE
PE
6 6
PG
CM A+
A B FWD
Y11
s1
A-
To tranformator Y12 B+
REV s2
Y15 B-
380vac/600va SPD.1 s5
Y16 Z+
7
(sheet 4) SPD.2
Y14
s6
Z- Enc
Ins.spd s7 SD
7
Y17
RST s4 IP
Y13
bb s3 IG
batry ARD FE
s8
B3
8
fault MB 8
MC A0
ready M5 IG to board
M6 B0
mico
zero M3 IG
N24 M4 Z0 control
IG
M3
- -
ARM
9 FWD Y16 - - 1 1 1 1 9
REV Y15 - - 1 1 1 1
INV.
SPD.3 Y22 - - 1 0 0 1
SPD.2 Y23 - - 0 0 1 0
10 2 10
SPD.1 Y24 - - 0 1 1 1 1
0
DRAWING CHECKED APPROVED
RST Y11 - - - - - - REV. DATE
BY BY BY
M3 PREPARED BY :
11
ARM
- - 11
INV.
IN1 X4 - - DRAWING TITLE :
WIRING POWER, INVERTER & UPS
ERROR
INV.
IN2 X2 - - RUNNING
DRAWING NO. : REV.
ZERO
12
IN3 X3 - - SPEED 123/INDSBY-ELC/1014 3 12
1 1
SW4 SW5
3
(COP) (COP)
3
Stop kontak
230 VAC
230 VAC
fan
4 Lamp. 4
Panel
PIT Top Car
N0 Lamp Lamp
I/O terminal panel
Nc
7 7
POWER P24vdc
TRAFOMATOR
SUPPLY
STEP DOWN To board control & wiring safety
SWITCHING
600VA
24VDC
N24vdc
PS
220vac
8 F3/6A 8
F2/6A
BC BC
L2
BK
L1
380vac AC (+) +
T1 T2
F1/6A 110vdc
110vac BR M
D1
BC
B
BC
13 L3
9 9
14
AC (-) T3 BK-
0vac 0vdc
TRF
DRAWING TITLE :
12
123/INDSBY-ELC/1014 4 12
1 1
E.S 1 Tmp.MTR
SAFETY HOISTWAY SAFETY MACHINE ROOM
3
104 105 106 3
4 4
13
MC1 14
Y03 M3P1
N24vdc
CS
MC1
9
5
X21
5 5
S106A
X17 M3P1
1DS 2DS nDS 111
X16
6 CDLS 110 6
Wiring contactor
BC1
7 A1 9 A1
Nc 7
220vac 5 A2
BC
MC1
9 A1
5 A2
MC
8 8
9 9
1 1
CABINET
P24vdc N24vdc CAR
2 2
COM 1 HOISTWAY
Door Close Limit DCLS1
X14
Running Feedback KC1
X15
Car Door
3 X16 110 3
10
(BC) M3P 2 10
1
0
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
Mataram City
PREPARED BY :
11 11
DRAWING TITLE :
I/O CONTROL M3P
DRAWING NO. : REV.
12
123/INDSBY-ELC/1014 6 12
1 1
CABINET
N24vdc
CAR
2 P24vdc 2
HOISTWAY
COM3
Slow Up 1 SLU1
X43
Door Open Limit 2 DOLS2
X44
3 3
Door Close Limit 2 DCLS2
X45
X46
X47
4 Inverter Running 4
X50 M5
7 Call Up 7UP
X51
8 Call Down 8DN
X52
8 Call Car 8C
5 X53 5
COM4
1 Call Up 1UP
X54
2 Call Up 2UP
6 X55 6
3 Call Up 3UP
X56
4 Call Up 4UP
X57
5 Call Up 5UP
X60
7 6 Call Up 6UP 7
X61
2 Call Down 2DN
X62
8 (BC)M3P 8
9 9
10 2 10
1
0
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
Mataram City
PREPARED BY :
11 11
DRAWING TITLE :
I/O CONTROL M3P
DRAWING NO. : REV.
12
123/INDSBY-ELC/1014 7 12
1 1
CABINET
N24vdc
2 CAR 2
P24vdc
HOISTWAY
COM0
7 Call Car 7C
X13
6 Call Car 6C
3
X12 3
5 Call Car 5C
X11
4 Call Car 4C
X10
3 Call Car 3C
4
X7 4
2 Call Car 2C
X6
1 Call Car 1C
X5
7 Call Down 7DN
X4
5 6 Call Down 6DN 5
X3
5 Call Down 5DN
X2
4 Call Down 4DN
X1
6 3 Call Down 3DN 6
X0
VP+ IP
7
- INV.
7
A AO
B BO
8 8
Data VCC H
CAN bus interface for Car Call
CAN GND L
(BC)M3P
10 2 10
1
0
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
Mataram City
PREPARED BY :
11 11
DRAWING TITLE :
I/O CONTROL M3P
DRAWING NO. : REV.
12
123/INDSBY-ELC/1014 8 12
1 1
GND N24vdc
2
+24V P24vdc
2
GND HOISTWAY
3
N24vdc COM5
3
Y0
Y1 BC1
13 14
4 - RL 4
Y2 KC1
13 14
- RL
S106
5
Y3 MC1
13 14 5
- RL
Y4 LIGHT RELAY
13 14
Y5 DC2 RL
6 6
Y6 DO2
Y7 DC1
Y10 DO1
7 7
EMC aux
COM6 CM s8
Run Up Dir. UPS/ARD
Y11 FWD
8
Run Down Dir. 8
Y12 REV
bb
Y13 s3
INV.
JOG SPEED
Y14 S5
Creep Speed
9 Y15 S6 9
Low Speed
Y16 s7
RST
Y17 s4
10
M3P
2 10
1
0
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
12 123/INDSBY-ELC/1014 9 12
1 1
P24vdc CAR
N24vdc
2 2
HOISTWAY
COM7
1 Call Up Light L.1UP
Y20
3 3
2 Call Up Light L.2UP
Y21
3 Call Up Light L.3UP
Y22
4 Call Up Light L.4UP
Y23
4
2 Call Down Light L.2DN 4
Y24
3 Call Down Light L.3DN
Y25
4 Call Down Light L.4DN
Y26
5 Call Down Light L.5DN
5 Y27 5
COM8
4 Call Car Light L.5C
Y33
5 Call Car Light L.5C
7
Y34 7
Buzzer BZ
Y35
Inspection Light L.ins
Y36
8 8
M3P
9 9
10 2 10
1
0
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
Mataram City
PREPARED BY :
11 11
DRAWING TITLE :
I/O CONTROL M3P
DRAWING NO. : REV.
12
123/INDSBY-ELC/1014 10 12
1 1
P24vdc N24vdc
2 2
HOISTWAY
CAR
COM9
Up Direction Light
Y37
DN Direction Light
3 Y40 L.UP
3
A
Y41 L.DN
B A
Y42 B
C
4
Y43 C
4
D D
Y44 E
E
Y45 F
F G
Y46
5 G 5
Y47
Y50
Y51
6 Arrival Gong AG 6
Y52
OverLoad Light L.OL
Y53
COM10
5 Call Up Light L.5UP
7
Y54 7
6 Call Up Light L.6UP
Y55
7 Call Up Light L.7UP
Y56
6 Call Down Light L.6DN
Y57
8 7 Call Down Light L.7DN 8
Y60
8 Call Down Light L.8DN
Y61
6 Call Car Light L.6C
Y62
7 Call Car Light L.7C
9
Y63 9
10
M3P 2 10
1
0
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
Mataram City
PREPARED BY :
11 11
DRAWING TITLE :
I/O CONTROL M3P
DRAWING NO. : REV.
12 123/INDSBY-ELC/1014 11 12
1 1
2 2
N24vdc
from maintenance
box top car
3 INS1 3
Auto/ins di top car panel
311
4 4
INS2
Auto/ins in COP
311
5 5
INS3
Auto/ins di control cabinet
com
com
6 6
DINS1
UINS1
DINS2
UINS2
DINS3
UINS3
7 7
310
Auto/ins
8 8
INS DN
INS UP
X06
X33
XO7
9 9
CONTROL
TO MICO
12 123/INDSBY-ELC/1014 12 12
1 1
3 COM DINS1 3
TB10
Lamp
TB7
4
TB6 TB8 TA1 TA2 4
SSW5
E.S 2
5 220 VAC 5
6 L11/TB3 6
L220 vac
ground
56 M PG
PE
Nvac
Nd /TB4
55
7 7
OPEN 8
COM2 9 30 CL.L
10 31 COM1
11 34
8 8
CLOSE 12 33 OP.L
9 9
10 2 10
E.S 2 : Emergency Stop on Top Car
1
0
SSW5 : Emergency Exit (Optional) REV. DATE
DRAWING CHECKED APPROVED
BY BY BY
INS1 : SWITCH INS./AUTO TOP CAR PROJECT :
Mataram City
UINS1/DINS1 : Switch Up/Down Ins.Top Car
PREPARED BY :
11 11
12 123/INDSBY-ELC/1014 13 12
1 1
TERMINAL A
NO NAME MARK
1 220 vac (L0)
2 2 0 vac (N0) 2
3 0 vac (N0)
4 0 vac (N0)
5 Light Car
6 Fan Car
7 L11 (power door & Safety ray)
3 8 N11 (power door & Safrty ray) 3
9 E.S Car
10 E.S Car
11 E.S Car
12
4 TERMINAL B 4
NO NAME MARK
1 P-24vdc
2 P-24vdc
3 N-24vdc
5 4 N-24vdc 5
5 Auto mode
6 Inspection mode
7 Up Inspection Button (UIB)
8 Dn Inspection Button (DIB)
6 9 6
10
11 Car Door Lock Switch
12 Car Door Lock Switch
TERMINAL D
7 7
NO NAME MARK
1 N-24vdc
2 Door Open Limit
3 Door Close Limit
4 Open Door ( DO )
8
5 Close Door ( DC ) 8
6 Com (DO/DC)
7 P-12vdc (phone)
8 N-12vdc (phone)
9 L (phone)
10 R (phone)
9 9
11 Buzzer Car
12 Arrival Bell
TERMINAL C
NO NAME MARK
10 1 N-24vdc 2 10
2 N-24vdc 1
0
3 Door Close Limit REV. DATE
DRAWING CHECKED APPROVED
BY BY BY
4 Open Door ( DO ) PROJECT :
5 Close Door ( DC ) Mataram City
6 Safety ray
PREPARED BY :
11 7 Over load Switch 11
8 OLS buzzer
DRAWING TITLE :
9 att
TERMINAL I/O Top Car Box
10 Door Close Button (DCB) cop
11 Door Open Button (DOB) cop DRAWING NO. : REV.
12 12 N-24vdc 123/INDSBY-ELC/1014 14 12
1 1
2
No. Fungsi Keterangan
2
3 HDLS 106
4 HDLS 111
3 5 SLD X26 3
6 N24vdc N24
7 LSD X22
8 N24vdc N24
9 LSU X23
4 10 N24vdc N24 4
11 SLU X27
12 N24vdc N24
13 FIRE X20
14 N24vdc N24
5 15 PARKING X21 5
16 N24vdc N24
19
6 6
20 grounding
21
22
23
24
7 7
1 - 24VDC N24
KABEL
2 + 24VDC P24
3 DATA H
DATA
4 DATA L
4Core
9 9
10 2 10
1
0
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
Mataram City
PREPARED BY :
11 11
DRAWING TITLE :
HOISTWAY CABLE
DRAWING NO. : REV.
12 123/INDSBY-ELC/1014 15 12
1 1
2 2
N24vdc
X42
X24
X35
X36
X34
X27
X43
X37
X21
X17
N0
N24
N24
L1
FLU
3 N24/100 3
UPL
X37/N24
SLU 1
X43/N24
4 4
5
2DLS 5
6 6
1DLS
7 7
SLD 1
X42/N24
10 2 10
DNL 1
0
X36/N24 DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
FLD PROJECT :
100/100A Mataram City
E.S PIT PREPARED BY :
11 100A/101 11
12 123/INDSBY-ELC/1014 16 12
1 1
proximity
1600 MM
3 3
SLU
car
SLU 1
±10 CM (NC)
4 4
Upper floor
SLU 2
(NC)
5 5
Cam switch
±3000mm
6
SLU 2 6
(NC)
7 7
SLD 1
(NC)
1600 MM
8 8
SLD
Lower floor
±10 CM
car DOWN LIMIT 150 MM DN LIMIT (NC)
9 9
10 Speed 2 10
lift 0.25m/s 0.5m/s 1.0m/s 1.6m/s 1.75m/s 2.0m/s 2.5m/s 1
Force 0
slow DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
SLU 1 400mm 800mm 1600mm 1600mm 1600mm 1600mm 1600mm
PROJECT :
SLU 2 2600mm 2800mm 4000mm 5000mm Mataram City
SLD 1 400mm 800mm 1600mm 1600mm 1600mm 1600mm 1600mm
PREPARED BY :
11 SLD 2 2600mm 2800mm 4000mm 5000mm 11
DRAWING TITLE :
WIRING SAFETY LIMIT HOISTWAY
DRAWING NO. : REV.
12 123/INDSBY-ELC/1014 17 12
1 1
R
L
L
EB1
CALLING
+
3 3
EB2
-
+
-
4 4
5 5
L
-
NKT12(1-1)B1
~
DC
VAC
220
SUPPLY
~
6 6
RKP
220/12
NBT12(1-1)A NBT12(1-1)B
R
8 8
INT
EB1
CALLING
+
EB2
-
9 9
-
+
10 2 10
CAR SUB-PHONE (M/B) 1
0
DRAWING CHECKED APPROVED
R
REV. DATE
-
BY BY BY
NBT12(1-1)B1 PROJECT :
Mataram City
~
DC
VAC
220
SUPPLY PREPARED BY :
~
11 11
12 123/INDSBY-ELC/1014 18 12
1 1
Alarm Alarm
Content Error Reason Content Error Reason
display display
Security Cicuit Opened Security circuit has on-off action The floor record is different from the deceleration Deceleration switch damaged
2
Emergency exit,gipper,pit,car top,emergency Deceleration switch install
2
switch and the switch is off when the lift is not at the
stop,final safety up or down have on-off station wrongly
E1 E20
action Wrong operation of door zone
switch
Counting bias
3 3
Door Lock contact Opened Car or landing door lock is off when door When test the connection of feedback point of
closed. mechanical brake. It will occur this error if the feed
Door closed overtime back point of mechanical brake is be connected
E2 Car or landing door input is off when the lift E21
4 running 4
Controller monitors lift emergency stop
function faulty
Can’t find the leveling point after Door area switch damaged The floor record is different from the deceleration Deceleration switch is damaged
E3 deceleration for 10 second Flag not enough depth E22 switch and the switch is on when the lift is at station Counting bias
5 5
Can’t find deceleration point Changing switch faulty The error occurs by pushbutton block and blocked Landing call pshbutton is
Changing magnet position wrong over 30 second blocked
E4 Pulse mistake of inveter divide frequency E23
6 card,or have disturb 6
Time or floor protect parameter wrong
Up limit switch opened Lift crashed up limit switch The micro controller will record error if the close Door limit switches damaged
door limit position switch is not off after the door The close door limit switch is not
lock has been over 3 second. When landing call and in place
7 E5 E24 car call occur E24 erro at the same time and open The door operator parameter 7
door reversed; if without 2# door operator,the input setting is wrong
point of close door limit position for 2# door
operator must be in place
Down limit switch opened Lift crashed down limit switch When it has the function of open door in advance.it Wire connection loose or wrong,
8 E6 E25 will show E25 while it can’t detect the input point of safe module damaged 8
safe door zone
Function of Deceleration switch Force change switch faulty.speed changing No function
E7 E26
switch in wrong position
Contact not release Controller menu<A4> NO/NC wrong set No safety touch input when pre-opening Wiring start or wrong connected
9
E8 Main or brake contactor and assistant point E27 Door area signal faulty 9
12
Mataram City 12
123/INDSBY-ELC/1014
A B C D E F G H
A B C D E F G H
1 1
The lift run over time “TIME 2”, Time/floor protect or “TIME2” floor The safety exit opened in Russia mode, lift can’t run. Safety exit damaged or wiring
or the signal of leveling doesn’t protection with short time Need inspection reset after safe exit closed mistake
2 change Time/speed stop,time set too long Forget to reset 2
Inveter error or lift stopped Frequency has failure warning,please rever to Motor over heating, door keep opened Motor over heating
immediately the frequency erro specifications Check switch and wiring
E12 E32
Frequency is damaged or with wrong
4
parameter
4
Door contact not release Door machine power is off or manual No function
connection in wrong way
E13 E33
Open/closedoor control relay in error,check
PM709 or door machine control signal
5 With counting the error of the Counting erro,be disturbed lift not stop at When using door advance open function, safety 5
floorwhere the lift is with leveling position,sometimes E2,E4,E9 also module door area single not release
counting pulse is over shortstop may reasons this warnings
speedchanging distance Door area sensors have disturbed
E14 E34
Car skidding
6
When E14 happened, it may also have 6
12
Mataram City 12
123/INDSBY-ELC/1014
A B C D E F G H
A B C D E F G H
1 1
11 11
Mataram City
12 12
123/INDSBY-ELC/1014
A B C D E F G H