I-P-1.01-W-12 (DP & Pressure Transmitter)
I-P-1.01-W-12 (DP & Pressure Transmitter)
Instrumentation Department
Issue No:02 Rev No:01 Effective Date: 01.07.2016 I-P-1.01-W-12
CALIBRATION OF DP & PRESSURE TRANSMITTER / HYDRAULIC PRESSURE
TRANSDUCER
1.2 Keep open both high side and low side tapping’s incase of pressure or draught transmitter
to the atmosphere and check for zero. If not, adjust it by `zero alignment' in DTM menu.
1.3 Connect the Pressure calibrator/vacuum pump to the either side of the tapping’s (high/low
tapping) of the transmitter.
1.4 Apply the pressure corresponding to the maximum range of transmitter. Read the reference
Value in process value field, If it doesn't match, adjust it by high balance point in DTM \
menu.
2.3 Apply the pressure corresponding to the maximum range of t transducer. Read the
reference Value in process value field, If it doesn't match, adjust it by high balance point in
menu.
This doc. is valid only until it is viewed in General drive of DCBL local area network.The unsigned print out of the same shall be
treated “Invalid doc.” For print out of the same contact MR.
DALMIA CEMENT (B) LIMITED, KADAPA
Instrumentation Department
Issue No:02 Rev No:01 Effective Date: 01.07.2016 I-P-1.01-W-12
Instrumentation Department
Issue No:02 Rev No:01 Effective Date: 01.07.2016 I-P-1.01-W-12
Instrumentation Department
Issue No:02 Rev No:01 Effective Date: 01.07.2016 I-P-1.01-W-12
400.0 400.0
MAIN RABH DP TRANSMITTER RANGE 0- 250mmwg
Applied Pr in mmwg. Calculated value in mmwg
0.0 0.0
125.0 125.0
250.0 250.0
Instrumentation Department
Issue No:02 Rev No:01 Effective Date: 01.07.2016 I-P-1.01-W-12
50 50
100 100
200 200
LIFTING PRESSURE
Applied Pr in Bar Calculated value in Bar
0.0 0.0
50 50
100 100
200 200