You are on page 1of 2

SG2500HV-MV-20 Characteristic Curve

SH2500HV-MV-20 Characteristic Curves


Version Date Author Approved by
V10 Sep.19.2017;Mar.9.2018 Li X Zheng W

1.Introduction

This document describes the Characteristics Curves for the SG2500HV-MV-20 including inverter temperature
dependent derating behavior, DC voltage dependent derating behavior, and altitude dependent derating.

This document is intended to be used by the specific addressees. No part of this document may be reproduced or
distributed in any form or by any means without the prior written permission of Sungrow Power Supply Co., Ltd.

2.SG2500HV-MV-20 Characteristics Curves

2.1. Temperature Derating Curve

1.2
SG2500HV-MV-20
1.1
1.0
With
With Standard Transformer Optional
0.8 Transformer
P/Pn

0.6

0.4

0.2

-40-35 -20 0 20 40 45 50 60

Ambient Temperature [℃]

Fig.-1 Temperature Dependant Power Derating

2.2. DC Voltage Derating Curve

1.2
1.1 SG2500HV-MV-20

1.0 Inverter shuts down when


operating point is out of the
permissable range for 5 mins
0.8
P/Pn

0.6

0.4

0.2

800 1300 1500


DC Voltage [V]

Fig.-2 DC Voltage Dependent Output Power Derating Curve

1
SG2500HV-MV-20 Characteristic Curve

2.3. Altitude Derating Curve

MV Turnkey Station

Version HV Standard Altitude Customizable Altitude Range


12KV: 1000~4000m
SG2500HV-MV-20 10~35kV 1000m 24KV: 1000~2500m
36KV: 1000~2000m

1.2
SG2500HV-MV-20

1.0
0.9
0.8
0.7
P/Pn

0.6 Beyond 1000m till 4000m


Transformer needs to be
25℃ customized as listed in
40℃ the table above
0.4
45℃

0.2

0 1000 2000 3000 4000 5000


Altitude [m]

Fig.-3 SG2500HV-MV-20 Altitude Dependent Output Power Derating Curve

2.4. Grid Voltage Derating Curve

1.2
1.1Pn SG2500HV-MV-20

1.0

0.8
P/Pn

0.6

0.4

0.2

0 495 550 605


Vgrid [V]

Fig.-4 Grid Voltage Derating Curve