You are on page 1of 12

Hardware Installation Guide

BACnet B-ASC VAV / VVT Controllers:


ECB-VAVS-O, ECB-VAVS, ECB-VAV, ECB-VVTS, ECB-VAV-N

BACnet B-ASC 10-Point Programmable Controller:


ECB-103

1. Product Description
This document describes the hardware installation procedures for the
Single Duct Variable Air Volume / Variable Volume Temperature
Controllers (ECB-VAVS-O, ECB-VAVS, ECB-VAV, ECB-VVTS, and
ECB-VAV-N), and the 10-Point Controller (ECB-103).
The Distech Controls Variable Air Volume / Variable Volume
Temperature product line is designed to control and monitor various
types of HVAC equipment such as baseboards, single and multi-stage
duct heaters, fans, valves, lights, etc. When connected to a Wireless
Receiver, this product line can be used with a variety of wireless
battery-less sensors and switches.
®
Each controller uses the BACnet MS/TP LAN communication protocol
®
and are BTL -Listed as BACnet Application Specific Controllers (B-
ASC). Figure 1-1: ECB-VAV
This document describes the hardware installation procedures for the
following controllers: ECB-VAVS-O, ECB-VAVS, ECB-VAV,
ECB-VVTS, ECB-VAV-N, and ECB-103.
For more information on the specific layout and
functionality of each controller, please refer to their
individual datasheets.

Figure 1-2: ECB-VAVS

Figure 1-3: ECB-VAV-N

www.distech-controls.com 1/12
2. General Installation Requirements 4. Mounting Instructions
For proper installation and subsequent operation of the controller, pay The following mounting instructions pertain to controllers that
special attention to the following recommendations: have a built-in actuator (ECB-VAVS-O, ECB-VAVS, ECB-VAV,
or ECB-VVTS). If mounting a controller without a built-in
 It is recommended that the controller(s) be kept at room actuator (ECB-VAV-N or ECB-103), simply mount the
temperature for at least 24 hours before installation to allow any controller using the integrated mounting bracket(s) and
condensation that may have accumulated due to low temperature screw(s) that are provided with the controller.
during shipping/storage to evaporate. Each controller is specially designed for easy installation either directly
 Upon unpacking the product, inspect the contents of the carton for on an air duct or in a panel by using the integrated mounting collar and
shipping damages. Do not install damaged controllers. the screw that is provided with the controller. This mounting
 Avoid areas where corroding, deteriorating or explosive vapors, arrangement opposes the torque applied to the damper shaft. Mount
fumes or gases may be present. the controller as follows:
 Allow for proper clearance around the controller’s enclosure and 1. Orient the controller into position on to the damper shaft so that
wiring terminals to provide easy access for hardware configuration wiring connections are easily accessible. The controller must be
and maintenance, and to ventilate heat generated by the controller. fitted onto the shaft such that the base of the controller is parallel to
When installed in an enclosure, select one that provides sufficient the VAV box (perpendicular to the damper shaft). If the damper
surface area to dissipate the heat generated by the controller and shaft has an external bushing that prevents the controller from
by any other devices installed in the enclosure. A metal enclosure is being mounted flush to the side of the VAV box, use a spacer of
preferred. If necessary, provide active cooling for the enclosure. the same thickness to compensate and to ensure the controller is
 The controller’s datasheet specifies the power consumption at a right-angle to the shaft to prevent binding.
(amount of heat generated), the operating temperature range, and Condensation from the damper shaft will damage the
other environmental conditions the controller is designed to operate controller’s electronics. When the VAV box air supply is below
under. 10°C (50°F), ensure that any condensation from the damper
 Do not drop the controller or subject it to physical shock. shaft or from the VAV box does not enter the controller’s
electronics. Under these conditions, mount the controller
 If the controller is used and/or installed in a manner not specified by
vertically above the damper shaft so that any condensation
Distech Controls, the functionality and the protection provided by
from the damper shaft will fall away from the controller.
the controller may be impaired.
Further countermeasures may be required in some
Any type of modification to any Distech Controls product installations.
will void the product’s warranty.
2. Using a power screwdriver, attach the controller to the VAV box
Before installation of the Wireless Receiver, verify that with the screw provided with the controller through the controller’s
local communication regulations allow the installation of mounting bracket slider. Otherwise, mark the screw’s position on
wireless devices that operate at a frequency of 315 MHz the VAV box with a punch and then drill a hole into the VAV box.
or 868.3MHz. Refer to the Open-to-Wireless™ Solution Then attach the controller to the VAV box with the screw provided
Guide for more information. with the controller.
Take reasonable precautions to prevent electrostatic Avoid over tightening the mounting screw so as to not strip
discharges to the controller when installing, servicing or the threads. Make sure the screws do not interfere with
operating the controller. Discharge accumulated static damper blade movement.
electricity by touching one’s hand to a securely grounded 3. Find the damper position by the marking typically found on the end
object before working with the controller. of the damper shaft.

3. General Wiring Recommendations

Turn off power before any kind of servicing.


Figure 4-1: Typical Damper Shaft End Marking
4. Determine the direction required to close the damper: Clockwise
 All wiring must comply with electrical wiring diagrams as well as (CW) or Counterclockwise (CCW). Turn the damper shaft with a
national and local electrical codes. pair of pliers to fully close the damper for 90° boxes or fully open
the damper for 45° or 60° boxes
 To connect the wiring to a controller, use the terminal connectors.
5. Press and hold down the Actuator Clutch For Manual Adjustment
Use a small flat screwdriver to tighten the terminal connector
button (see Figure 5-3), and turn the controller’s shaft coupler until
screws once the wires have been inserted.
it touches the mechanical end-stop to either the fully closed
 Comply with all BACnet network and power supply guidelines position (90° boxes) or the fully open position (45° and 60° boxes).
outlined in the Network Guide. 6. For 90° VAV boxes: If the damper closes CCW, turn the coupler to
 Power type cables (i.e. for power, 2- and 3-wire voltage and current the CCW mechanical stop limit. If the damper closes CW, turn the
inputs and outputs, as well as triac outputs) should be kept apart coupler to the CW mechanical stop limit. The open mechanical stop
from other types of wiring to avoid any ambient noise transmission is factory preset for 90° boxes.
to other wires. For 45° and 60° VAV boxes: The mechanical stops must be set for
 The board connectors accept wires or flat cables ranging from 22 to both the fully closed and fully open damper positions. By installing
14AWG (0.644 to 1.630mm diameter) per pole. However, power the controller at the fully open position, the controller provides the
cables must be between 18 and 14AWG (1.024 to 1.630mm open mechanical stop for 45° and 60° boxes. The closed damper
diameter). seal provides the fully closed stop.
 Do not connect the universal inputs, analog/digital outputs or 7. Tighten the U-Bolt clamp on to the damper shaft using an 8 mm
common terminals to earth or chassis ground (unless stated (5/16 in.) wrench or socket. Tighten the bolts between 11 and 15
otherwise). N·m (100 and 130 lb·in).
 Keep all wires away from high speed data transmission cables (for 8. Test for free damper shaft movement: Press and hold down the
example, Ethernet, etc.). Actuator Clutch For Manual Adjustment button and manually turn
 Keep input and output wiring in conduits, trays or close to the the actuator coupling to be certain that the actuator can rotate from
building frame if possible. full closed to full open positions without binding.

2/12
9. Connect the VAV box’s flow sensor tubing to the controller’s 190 [7.48 ]

Pressure Sensor Inputs. Create a condensation trap in the


pneumatic tubing by forming it into a vertical loop.
10. Finalize the installation by rotating the damper to the full open

54 [2.13 ]
position.
CAUTION: Risk of Property Damage. Ensure that the
damper is at the full open position before starting the air
handler. Failure to rotate the damper to its full-open position
may result in damage to the Variable Air Volume (VAV) box
or ductwork when the air handler is started.

61.5 [2.42]
10 11
[0.40] [0.43]

5 [0.2]
High pressure
Bracket
mouting kit
Low pressure

26.5 [1.04]
3 mm
0.12 in
min. 40 mm (1.5")

Units Legend: mm [in]

Figure 5-2: VAV-N & ECB-103 series dimensions


Figure 4-2: Mounting a controller on a damper shaft
Damper Shaft
Clamping Mechanism
5. Controller Dimensions & Components
Opening for Connectors
Damper Shaft

Mechanical Stops

Integrated
Actuator Clutch for Mounting
Manual Adjustment Brackets

PRESSURE
HIGH LOW

Pressure Sensor Inputs (when equipped)

Figure 5-3: VAVS-O, VAVS, VAV & VVTS series components

Connectors

Integrated
Mounting
Bracket
Integrated
Mounting
Brackets

Pressure Sensor Inputs (when equipped)


Figure 5-1: VAVS-O, VAVS, VAV & VVTS series dimensions
PRESSURE

HIGH LOW

Figure 5-4: VAV-N & ECB-103 series components

3/12
6. Configuration Jumper Location and Use an external fuse on the 24VAC side (secondary side) of the
transformer, as shown in Figure 6-1, to protect all controllers against
Identification power line spikes.
Controllers have the following onsite configurable jumpers. Maintain consistent polarity when connecting controllers and devices to
the transformer. One terminal on the secondary side of the transformer
must be connected to the building’s ground. All 24V COM terminals of
Subnet
BACnet MS/TP Network
EOL Termination
Port all controllers and peripherals throughout the BACnet MS/TP network
EOL Off EOL On
must be connected to the grounded transformer terminal as shown in
(Disabled)* (Enabled) Figure 7-1. This ensures that the 24V COM terminals of all devices
connected to any BACnet MS/TP bus in the building are at the same
potential.
A mechanical ground is unacceptable: Do not use a pipe,
conduit, or duct work for a ground. The power supply

Typical locations: Quantity may vary according to controller model


must have a dedicated ground wire that comes from the
main electrical supply panel.
Failure to maintain consistent polarity throughout the
Digital Outputs (DO)
entire BACnet MS/TP network will result in a short circuit
Power Source Jumpers for and/or damage to the controller!
Triac Internal DO3 & DO4
Wireless Power*
Triac External The COM terminals of the controller are internally wired to
Powered
Port the 24V COM terminal of the power supply. Connecting a
peripheral or another controller to the same transformer
Jumpers for without maintaining polarity between these devices will
DO1 & DO2
cause a short circuit.
Fuse: 4 A Max.
Controller 1 Fast Acting
24V AC
24V COM 24 VAC AC
* Factory-default positions

Figure 6-1: ECB-VAV Series and ECB-103 Controller Jumper Transformer


Controller 2 Electrical System Ground
Locations
24V AC - At Transformer Only
24V COM

7. Power Wiring
Figure 7-1: Power wiring
Voltage: 24VAC; ± 15%, Class 2
This is a Class 2 Product. Use a Class 2 transformer only
(rated at 100VA or less at 24VAC) to power the controller(s). 8. Input Wiring
The Network Guide provides extensive information and requirements Each controller has physical connections for inputs (marked as UIx)
for powering a VAV that uses a BACnet network for communications. It that are configured in EC-gfxProgram. Each input can be configured
can be downloaded at the www.distech-controls.com website. for digital, resistive, current, or voltage signals. Input types must be
It is recommended to wire only one controller per 24VAC transformer. configured properly in software to ensure proper input readings.
If only one 24VAC transformer is available, determine the maximum Before connecting sensor to the controller, refer to the
number of VAVs that can be supplied on a single power cable supplied installation guide of the equipment manufacturer.
by a 100 VA transformer, according to the cable’s wire gauge and the
total cable length from the following table.
Table 7-1: Maximum Number of VAV Devices on a Power Run  For a wire length less than 75’ (23m), either a shielded
or unshielded 18AWG wire may be used.
AWG Power Run Total
Cable Length
Maximum
Number of
Maximum
Number of
Maximum
Number of
 For a wire up to 200’ (61m) long, a shielded 18AWG
Devices @ 7 Devices @ 10 Devices@ 15 wire is recommended.
VA per device1 VA per device2 VA per device3  The shield of the wire should be grounded on the
144 75M (250 feet) 4 2 1 controller side and the shield length should be kept as
14 60M (200 feet) 5 3 2 short as possible.
14 45M (150 feet) 5 4 3
14 30M (100 feet) 5 5 4
Wiring Digital Inputs
16 60M (200 feet) 3 2 1
This input configuration is used to monitor digital dry contacts, as well
16 45M (150 feet) 5 3 2 as pulsed contacts.
16 30M (100 feet) 5 4 3
UIx
18 45M (150 feet) 3 2 1 Digital Dry Contact To Digital
NO-NC Input
COM
18 30M (100 feet) 5 3 2

1. Typical VAV with 1 Allure EC-Smart-Vue and actuator activated.
No external loads. Figure 8-1: Digital dry contact (NO & NC)
2. Typical VAV with 1 Allure EC-Smart-Vue, 2 triac loads (1.6 VA
each), 1 analog output (20 mA), and actuator activated.
3. Typical VAV with 1 Allure EC-Smart-Vue, 4 triac loads (1.6 VA Wiring Resistive Inputs
each), 2 analog outputs (20 mA each), and actuator activated. This input configuration is used to monitor Resistance Temperature
4. Device terminals are not capable of accepting two 14 AWG wires Detectors (RTD), thermistors such as 1000Ω RTDs to 10kΩ type II and
(when daisy-chaining devices). Use a wire nut with a pig tail to III thermistors, as well as 10kΩ and 100kΩ potentiometers.
make such a connection.
Any installation condition that is outside of the parameters of Table 7-1
should be avoided.
4/12
RTD/
UIx To Analog- 9. Allure EC-Smart-Vue Wiring
To-Digital
Thermistor
COM Converter
The Allure EC-Smart-Vue is a Communicating room temperature
sensor with backlit display and graphical menus and has VAV
Figure 8-2: Resistive input – RTD /Thermistor input balancing capabilities. Connect the Allure EC-Smart-Vue to the
Potentiometer UIx
controller with a standard Category 5e Ethernet patch cable fitted with
To Analog-
10kΩ RJ-45 connectors. The Network Guide provides extensive information
To-Digital
Converter
COM and requirements for the connection of Allure EC-Smart-Vues. It
contains information about network topology and length, cable type,
Figure 8-3: Resistive input – 10kΩ Potentiometer input setting the Subnet ID, etc. It can be downloaded at the www.distech-
controls.com website. See also the Hardware Installation Guide
supplied with the Allure EC-Smart-Vue.
Wiring Current Inputs If you make your own patch cable, use Category 5e cable crimped with
Current inputs have a range of 0 to 20mA. Depending on the RJ-45 connectors either as T568A or T568B.
transducer power requirements, any one of the following input
configurations can be used. Use the following configuration for a 2-
 Do not crimp one connector as T568A and crimp the other
connector as T568B on the same cable.
wire, 0 to 20mA transducer powered by the controller’s internal 15VDC
power supply.  Protect the controller’s connector from being pulled on
when a cable to the Allure EC-Smart-Vue is connected.
+15VDC Create a strain-relief by looping the cable and attaching it
Transducer +
0-20mA UIx To Controller’s to a solid object with a nylon tie so that a tug on the cable

Analog-To-Digital
Converter
will not pull out the connector on the controller.
249Ω / ¼W COM
Table 9-1: T568A and T568B Terminations for an RJ-45
Connector
Figure 8-4: Current input – 2-wire transducer powered by the
controller Pin T568A (at both cable ends) T568B (at both cable ends)
Pair Color Pair Color
Use the following configuration for a 2-wire, 0 to 20mA transducer 1 3 2
powered by an external 24 AC/DC power supply. white/green stripe white/orange stripe
249Ω ¼W 2 3 2
green solid orange solid
UIx 3 2 3
0-20mA - To Analog-
Transducer + To-Digital white/orange stripe white/green stripe
COM Converter
24VDC
4 1 1
blue solid blue solid
Figure 8-5: Current input – 2-wire transducer, externally powered 5 1 1
white/blue stripe white/blue stripe
Use the following configuration for a 3-wire, 0 to 20mA transducer 6 2 3
powered by an external 24 AC/DC power supply. orange solid green solid
249Ω ¼W 7 4 4
white/brown stripe white/brown stripe
+
UIx 8 4 4
0-20mA
Transducer
Common
COM
To Analog- brown solid brown solid
24VAC To-Digital
AC Converter The final result of a crimped RJ-45 connector is shown graphically
below.
Figure 8-6: Current input – 3-wire transducer, externally powered T568A T568B

Use the following configuration for a transducer powered by its own


power source. Key:
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

249Ω ¼W

UIx To Analog-
0-20mA +
Transducer - To-Digital Stripe Solid
COM Converter

Pair 3 Pair 1 Pair 2 Pair 4 Pair 2 Pair 1 Pair 3 Pair 4


Figure 8-7: Current input – Transducer with its own power source
Figure 9-1: T568A and T568B Crimp Wire Sequence for an RJ-45
Wiring Voltage Inputs Connector
Voltage inputs have a range of 0 to 10VDC or 0 to 5VDC. Connect the
voltage input according to the following figure if a 3-wire 0 to 10V or 0
to 5V transducer is being used.
UIx
+
0-10V
Common To Analog-
Transducer COM
24VAC To-Digital
AC Converter

Figure 8-8: Voltage input – 3-wire transducer


Connect the voltage input according to the following figure if the
transducer is powered by its own power source. Figure 9-2: Pins on RJ-45 Jack Face
UIx To Analog-
Patch cables fitted with connectors supplied by Distech Controls are
0-10V +
Transducer - To-Digital wired as T568B.
COM Converter

Figure 8-9: Voltage input – Transducer with its own power source

5/12
Actuator
10. Output Wiring
DOx ~
Each controller has physical connections for either digital (triac) and/or JUMPER Cx-x
DOx ~
universal outputs, depending on the type and model. The power SETTINGS
source type for digital outputs is hardware configurable and must be Figure 10-4: Digital output with internal power supply – Floating
configured by changing the jumper settings on the printed circuit board actuator
(for jumper location, see Section 6). The universal outputs are software
configurable. Wiring Universal Outputs (UOx)
Before connecting an output device (actuator, relay, etc.) Universal outputs can be configured to provide either a discrete signal
to the controller, refer to the installation guide of the of 0 or 12VDC or a linear signal ranging from 0 to 10VDC. The discrete
equipment manufacturer. signal can be used to generate a pulse wave modulation (PWM) signal
or a simple two-state signal. These outputs are protected by an auto-
reset fuse.
 For a wire length less than 75’ (23m) long, either a
shielded or unshielded 18AWG wire may be used.
 For a wire up to 200’ (61m) long, a shielded 18AWG Wiring Discrete Outputs
wire is recommended. If a 12VDC relay is being controlled, connect it to a universal output
 The shield of the wire should be grounded on the according to the following figure.
controller side and the shield length should be kept as
From UOx
short as possible. Digital
A1

Output A2
COM
12VDC Relay
Wiring Digital Outputs (DOx)
The digital outputs are all made of triacs and can be configured as Figure 10-5: Discrete 0 or 12VDC universal output – Relay
either powered outputs or non-powered outputs and output wiring must Wiring Voltage Outputs
be done accordingly.
Connect the 0 to 10VDC output according to the following figure.
 The non-powered output type does not have any voltage on the
From Digital- UOx
output terminals when the output is active. Power must be supplied To-Analog
0-10V
externally. Output
COM
Common

 The powered output type has 24VAC on the output terminals when
the output is active. Power is therefore supplied internally by the
controller. Figure 10-6: Voltage 0 to 10VDC universal output
It should be noted that all controllers are shipped with all digital outputs If an analog actuator is being controlled, connect the 0 to 10VDC
configured as powered outputs. Maximum output current for all digital output, along with an external 24VAC power source, to the analog
outputs (whether powered or non-powered) is 0.5A continuous or 1A actuator according to the following figure.
@ 15% duty cycle for a 10-minute period.
Actuator
From Digital- UOx
DO1 and DO2 share the same C1-2 common terminal and are To-Analog
0-10V
controlled by a single jumper and must therefore be set identically. Output
COM
~ or +
24VAC
Similarly, DO3 and DO4 (VAV, VVT and ECB-103 product lines only) or -
share the same C3-4 common terminal and are controlled by a single
jumper and must therefore be set identically. The jumpers are used to Figure 10-7: Voltage 0 to 10VDC universal output – Analog actuator
specify whether an internal or external power source is being used.
If a 24VAC relay is being controlled using an external or internal power To measure the state of a triac output, an external load
supply, connect the digital output according to the following figures. must be connected.

External power supplies must be grounded as shown in


Figure 10-1 and Figure 10-3. 11. Communications Wiring
DOx A1 The Network Guide provides extensive information and requirements
JUMPER
SETTINGS Cx-x A2 to implement a BACnet MS/TP network. It contains information about
AC
24VAC Relay
network and sub network length, cable type, device addressing, etc. It
can be downloaded at the www.distech-controls.com website. For
Figure 10-1: Digital output with external power supply – Relay optimal performance, use Distech Controls 24 AWG (0.65 mm)
stranded, twisted pair shielded cable or refer to the Network Guide for
DOx A1
JUMPER
cable specification. The BACnet MS/TP communication wire is polarity
SETTINGS Cx-x A2 sensitive and the only acceptable topology is to daisy-chain the cable
24VAC Relay from one controller to the next.
Figure 10-2: Digital output with internal power supply – Relay
As shown in Figure 11-1 below:
If a floating actuator is being controlled using an external or internal  The first and last daisy-chained BACnet MS/TP
power supply, connect the digital output according to the following device must have its EOL resistors enabled / installed.
figures.
All other devices must have their EOL resistor
Actuator disabled (default factory setting). For jumper location,
DOx ~ see Section 6
24VAC

JUMPER
Cx-x
~
 When the BACnet MS/TP data bus is connected to a
DOx
SETTINGS following device, twist data bus shields together.
Figure 10-3: Digital output with external power supply – Floating
 Isolate all shields with electrical tape so there is no
exposed metal that can touch ground or other
actuator
conductors.
 The shield of the data bus must be connected to the
electrical system ground at only one point – usually at
one end of the bus as shown below.

6/12
 Connect no more than 50 devices to a BACnet MS/TP 13. Setting the Allure EC-Smart-Vue Subnet ID
data bus.
First and last daisy-chained
- device: ECB Series controllers can be commissioned with an Allure
- EOL Jumpers are ON
All other Devices:
: EC-Smart-Vue by connecting it to the controller as shown in Figure
- EOL Jumpers are OFF
21-1. The default Subnet ID for an Allure EC-Smart-Vue is 1. To
Typical BACnet Device Typical BACnet Device Typical EC-BOSAX Device commission an ECB Series controller, the Allure EC-Smart-Vue’s
EOL ON EOL OFF
EOL ON: For the EC-BOSAX
as the first or last daisy Subnet ID must be set to 1. If the Allure EC-Smart-Vue’s Subnet ID
chained device:
has been set to another value (for example, the display flashes error
NET+

NET+
- OPTIONALLY set the EOL
NET-

NET-
jumper internally
- AND add a 120 Ohm EOL
- + S code 1 with the Bell icon when the Allure EC-Smart-Vue is connected
resistor as shown here
The shield of the
to a controller for commissioning), change the Subnet ID to 1 as
Data Bus Shields: Twist
together and isolate
data bus must be
connected to the
follows:
with electrical tape 12
0Ω electrical system
ground at only one
point – usually at
1. Connect an Allure EC-Smart-Vue to the controller with a Cat 5e
Data Bus Shield:
: Isolate with
Data Bus: Shielded Twisted Pair Cable Up to 50 Devices Total
Data Bus Shield: Connect
one end of the bus
as shown.
patch cable. Wait for the Bell icon and the number 1 to flash on the
electrical tape to the ‘S’ terminal
display.
Figure 11-1: Communications wiring 2. Press and hold the Menu button for 5 seconds to enter the
If inserting multiple wires in the terminals, ensure to properly twist password menu. 10000 is shown on the display.
wires together prior to inserting them in the terminal connectors. 3. Use the down button to set the number to 9995 (this is the
default password).
For more information and detailed explanations on network topology
4. Use the Menu button to select SUBNET ID. The current
and wire length restrictions, refer to the Network Guide, which can be
downloaded at the www.distech-controls.com website. controller’s Subnet ID is shown.
5. Use the up and down buttons to set the controller’s Subnet
ID. Tip: Hold down either the up or down button to fast-advance the
display value.
12. Device Addressing
6. Press the Menu button once to apply the value.
The Network Guide provides extensive information and requirements 7. Press and hold the Menu button for 5 seconds to exit the
to implement a BACnet MS/TP network. It contains information about configuration menu.
network planning and MAC Address numbering schemes. It can be The Allure EC-Smart-Vue can now be used to go from one ECB series
downloaded from the www.distech-controls.com website. controller to the next for commissioning purposes.
The MAC Address must be set according to your network planning
document by setting the DIP switch located under the cover or when
this DIP switch is set to 0 (all off), the MAC address can be set by 14. Commissioning ECB-Series Controllers
connecting an Allure EC-Smart-Vue to the controller as shown in
Figure 21-1. An example of how to set the device’s MAC Address DIP When using an Allure EC-Smart-Vue for commissioning ECB Series
switch is shown below. controllers (the DIP switch located on the faceplate is set to 0 (all off)
and before code is downloaded to the controller from EC-gfxProgram),
S1

connect an Allure EC-Smart-Vue to the controller with its Subnet ID set


to 1. During commissioning, the Allure EC-Smart-Vue is used to set the
ON
1

®
controller’s BACnet MAC Address and to perform application
2

selection if needed. Applications are pre-loaded programs that enable


The MAC Address
weighting for each
S1

the ECB-VAV to control a typical VAV box.


3

switch

Set the connected controller’s MAC Address as follows:


4
5

1. Connect an Allure EC-Smart-Vue to the controller with a Cat 5e


patch cable. Wait for the display to show the room temperature.
6

MAC Address DIP


Switch (S1) 2. Press and hold the Menu button for 5 seconds to enter the
7

located under the password menu. 10000 is shown on the display.


Must be set to the
cover
8

OFF (0) position 3. Use the down button to set the number to 9995 (this is the
default password).
Figure 12-1: Typical Device MAC Address DIP Switch Set to 82 4. Use the Menu button to select GEN CFG.
5. Press the down button once to enter the GEN CFG submenu.
The address is the sum of the numbers set to ON. For example, if the The MAC ADDRESS menu is shown with the current controller’s
second (2), fifth (16), and seventh (64) DIP switches are set to ON, the BACnet MAC Address.
device MAC address is 82 (2 + 16 + 64). Only addresses from 1 to 127
6. Use the up and down buttons to set the controller’s MAC
are recommended to be used.
Address. Only addresses from 1 to 127 are recommended to be
The controller must be power cycled after the MAC address DIP switch used.
has been changed. The device instance (DevID) is automatically 7. Press the Menu button once to apply the value.
configured when setting the MAC Address to prevent network address 8. Press and hold the Menu button for 5 seconds to exit the
conflict. The following formula is used to determine the device configuration menu.
instance:
Once the BACnet MS/TP network is operational, the controller can be
DevID = 364 * 1000 + MAC programmed with EC-gfxProgram. For each Allure EC-Smart-Vue, set
For example: its Subnet ID number to the block number of its associated
CommSensor block in EC-gfxProgram. This is done in the Allure
MAC: 37
EC-Smart-Vue’s GEN CFG menu under SUBNET ID.
DevID = 364 * 1000 + 37 = 364037
The Device Instance can be changed once the controller has been
commissioned through the network management software interface.

7/12
15. Setting the BAUD Rate (optional) 17. Terminal Block Cover
By default, the BAUD rate for the controller is set to automatically In certain jurisdictions, terminal block covers are required to meet local
detect the current communication BAUD rate of the connected BACnet safety regulations. Terminal block covers are available for all
MS/TP network (AUTO). This is the preferred setting for a controller. controllers and are used to conceal the controllers’ wire terminals.
However, at least one controller on the BACnet MS/TP network data Terminal block covers are optional and are sold as peripherals.
bus must have its BAUD rate set. The preference is to set the building The terminal block cover can be clipped on to the controller as shown
controller’s BAUD rate (if present). Otherwise, set the BAUD rate on below.
one controller that will set the BAUD rate for all other controllers (to act
as the master for setting the BAUD rate).
When the Baud rate is set to AUTO, the controller cannot
initiate any communication until it has detected the baud
rate of the BACnet MS/TP network. If all controllers on
the BACnet MS/TP network are set to AUTO, then all
controllers will not communicate.
Set the connected controller’s BAUD rate as follows:
1. Connect an Allure EC-Smart-Vue to the controller with a Cat 5e
patch cable. Wait for the display to show the room temperature.
2. Press and hold the Menu button for 5 seconds to enter the
password menu. 10000 is shown on the display. Figure 17-1: Terminal block cover installation
3. Use the down button to set the number to 9995 (this is the 18. Maintenance
default password).
4. Use the Menu button to select GEN CFG.
5. Press the down button once to enter the GEN CFG submenu. Turn off power before any kind of servicing.
The MAC ADDRESS menu is shown.
6. Use the Menu button to select BAUD RATE. The current
controller’s BAUD rate is shown. Each controller requires minimal maintenance, but it is important to
7. Use the up and down buttons to set the controller’s Baud take note of the following:
rate. AUTO detects and uses the Baud rate currently being used by
the BACnet MS/TP network.
 If it is necessary to clean the outside of the controller, use a dry
cloth.
8. Press the Menu button once to apply the value.
 Retighten terminal connector screws annually to ensure the wires
9. Press and hold the Menu button for 5 seconds to exit the remain securely attached.
configuration menu.

19. Disposal
16. Wireless Installation
The Waste Electrical and Electronic Equipment (WEEE) Directive sets
When connected to a Wireless Receiver, controllers can receive input out regulations for the recycling and disposal of products. The
signals from a wide selection of wireless devices. Compatible wireless WEEE2002/96/EG Directive applies to standalone products, for
devices include temperature sensors, duct sensors, window/door example, products that can function entirely on their own and are not a
contacts and light switches. These devices are easy to install, and can part of another system or piece of equipment.
be mounted on a wide range of building materials.
For this reason Distech Controls products are exempt from the WEEE
The Wireless Receiver is available in 315MHz or 868.3MHz Directive. Nevertheless, Distech Controls products are marked with the
frequencies.
Connecting the Wireless Receiver
The Wireless Receiver is connected to the controller using a telephone WEEE symbol , indicating that devices are not to be thrown
cable with 4P4C modular connectors at both ends. The Wireless away in municipal waste.
Receiver’s telephone socket is located inside the device. To locate it, Products must be disposed of at the end of their useful life according to
open the Wireless Receiver by separating its front and back plates. local regulations and the WEEE Directive.

Figure 16-1: Location of the Wireless Receiver’s telephone socket


Connecting to the Controller’s Wireless Port
Each controller has a wireless port in which one end of the Wireless
Receiver’s telephone cable plugs in. Uncover the controller to locate
the wireless port on the PCB board (marked as Wireless Module).

8/12
20. FCC Statement
Changes or modifications not expressly approved by
Distech Controls could void the user's authority to operate
the equipment.

This equipment has been tested and found to comply with


the limits for a Class B digital device, pursuant to Part 15
of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a
residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions,
may cause harmful interference to radio communications.
However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the
interference by one or more of the following measures:
 Reorient or relocate the receiving antenna.
 Increase the separation between the equipment and
receiver.
 Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
 Consult the dealer or an experienced radio/TV
technician for help.

9/12
21. Typical Variable Air Volume Application Wiring Diagram

Back of Allure
EC-Smart-Vue
MAC Address DIP Switch Do not pull on connector
(S1) beneath cover
EOL Enabled
at the last
sensor at the
end of the Bus

S1
ON
ON

EOL
2
From Previous Device

3
OFF

4
BACnet MS/TP Network
5
6
7
8 To Next Device

Data Bus Shields: Twist together


and Isolate with electrical tape
Wireless Port
(beneath cover)

ECB-VAVS
Heating Floating
Actuator

Allure
PRESSURE
HIGH LOW

24VAC
Fuse EC-Smart-Vue
L
120 / 220 VAC
N
GND
Electrical System Ground

Figure 21-1: Typical Power and Network Connections with an Allure EC-Smart-Sensor Input and Floating Actuator Output

Data Bus Shields: Twist together


MAC Address DIP Switch Do not pull on connector and Isolate with electrical tape
(S1) beneath cover
From EC-Sensor
Previous Connectors EC-Sensor
Device
S1

NET+
ON
1

BACnet MS/TP Network


NET-
2
3

SHIELD
4
5

To Next Device
6
7
8

COMMON
Wireless Port TEMP
(beneath cover) SETPOINT
FANSPEED
LED

ECB-VAVS
Heating Floating
Actuator
PRESSURE
HIGH LOW

24VAC
Fuse
L
120 / 220 VAC
N
GND
Electrical System Ground

Figure 21-2: Typical Power and Network Connections with an EC-Sensor Input and Floating Actuator Output

10/12
22. Troubleshooting guide
Controller is powered but does not turn on
Fuse has blown Disconnect the power.Check the fuse integrity. Reconnect the power.
Power supply polarity Verify that consistent polarity is maintained between all controllers and the transformer. Ensure that the 24VCOM terminal of
each controller is connected to the same terminal on the secondary side of the transformer. See Figure 6-1.
Controller cannot communicate on an BACnet MS/TP network
Absent or incorrect supply voltage 1. Check power supply voltage between 24VAC ±15% and 24VCOM pins and ensure that it is within acceptable limits.
2. Check for tripped fuse or circuit breaker.
Overloaded power transformer Verify that the transformer used is powerful enough to supply all controllers.
Network not wired properly Double check that the wire connections are correct.
Absent or incorrect network termination Check the network termination(s).
Max Master parameter Configure the maximum number of master device on the MS/TP network in all devices to the controller’s highest MAC
address used on the MS/TP trunk.
Controller communicates well over a short network, but does not communicate on large network
Network length Check that the total wire length does not exceed the specifications of the Network Guide.
Wire type Check that the wire type agrees with the specification of the Network Guide.
Network wiring problem Double check that the wire connections are correct.
Absent or incorrect network termination Check the network termination(s). Incorrect or broken termination(s) will make the communication integrity dependent upon a
controller’s position on the network.
Number of controllers on network segment The number of controllers on a channel should never exceed 50. Use a router or a repeater in accordance to the Network
exceeded Guide.
Max Master parameter Configure the maximum number of master device on the MS/TP network in all devices to the controller’s highest MAC
address used on the MS/TP trunk.
There is another controller with the same MAC Each controller on a BACnet MS/TP data bus must have a unique MAC Address. Use an Allure EC-Smart-Vue to check the
Address on the BACnet MS/TP data bus MAC Address of each controller.
There is another controller with the same Device Each controller on a BACnet intranetwork (the entire BACnet BAS network) must have a unique Device ID. Use an Allure
ID on the BACnet intranetwork EC-Smart-Vue to check the Device ID of each controller.
Hardware input is not reading the correct value
Input wiring problem Check that the wiring is correct according to this manual and according to the peripheral device’s manufacturer.
Open circuit or short circuit Using a voltmeter, check the voltage on the input terminal. Short circuit (0V) and open circuit (5V).
Configuration problem Using the controller configuration wizard, check the configuration of the input. Refer to the controller’s user guide for more
information.
Over-voltage or over-current at an input An over-voltage or over-current at one input can affect the reading of other inputs. Respect the allowed voltage / current
range limits of all inputs. Consult the appropriate datasheet for the input range limits of this controller.
Hardware output is not operating correctly
Fuse has blown (Auto reset fuse) Disconnect the power and outputs terminals. Then wait a few seconds to allow the auto-reset fuse to cool down. Check the
power supply and the output wiring. Reconnect the power.
Output wiring problem Check that the wiring is correct according to this manual and according to the peripheral device’s manufacturer.
Configuration problem Using the controller configuration wizard, check the configuration of the output. Refer to the controller’s user guide for more
information.
0 to 10V output, 24VAC powered actuator is not Check the polarity of the 24VAC power supply connected to the actuator while connected to the controller. Reverse the
moving. 24VAC wire if necessary. Check the jumper settings for the external power supply as shown in Figure 9-3.
Wireless devices not working correctly
Device not associated to controller Using the device configuration wizard, check the configuration of the input. Refer to the device’s user guide for more
information.
Power discharge 1. Recharge device with light (if solar-powered) or replace battery (if battery-powered),
2. Ensure sufficient light intensity (200lx for 4 hours/day).
Device too far from the Wireless Receiver Reposition the device to be within the range of the Wireless Receiver. For information on typical transmission ranges, refer
to the Open-to-Wireless Solution Guide.
Configuration problem Using the device configuration plug-in or wizard, check the configuration of the input. Refer to the Wireless Battery-less
Sensors and Switches Solutions Guide for more information.
Flow sensor is not giving proper readings
Tubing connection problem 1. Ensure the tubing is installed properly and that the tubing is not bent.
2. Verify that the high and low pressure sensors are not inversed.
Controller is not calibrated properly Recalibrate the controller. Refer to the controller’s user guide for more information.
Damper is not opening or closing properly
Mechanical stops not in proper position The two mechanical stops must be positioned to stop the damper motion when it is completely closed and completely
opened. The mechanical stops can be moved by increments of 5°.
Controller in Override Set the Override to OFF in the wizard.
Rx/Tx LEDs
RX LED not blinking Data is not being received from the BACnet MS/TP data bus.
TX LED not blinking Data is not being transmitted onto the BACnet MS/TP data bus.

11/12
Status LED– Normal Operation
One fast blink Initialization: The device is starting up.

Fast blink continuous: Firmware upgrade in progress. Controller operation is temporarily unavailable. The new firmware is being
loaded into memory. This takes a few seconds. Do not interrupt power to the device during this time.
(150ms On, 150ms Off, continuous)
The Status LED is always OFF The controller is operating normally.

Status LED blink patterns – Repeats every 2 seconds (highest priority shown first)
Long Long Long blink The device has not received a BACnet token, and therefore cannot communicate on the network: Verify
that the controller’s MAC Address is unique on the BACnet MS/TP Data Bus – see Section 12. Make sure
(800ms On, 300ms Off, 800ms On, 300ms Off, 800ms On) the controller’s BAUD rate is the same as the BACnet MS/TP Data Bus’ BAUD rate (see Section 15). Verify
that the Max Master is set high enough to include this controller’s MAC Address (See the Network Guide).
Short Short Long blink Poor-quality power; The device has browned-out: The voltage at the 24VAC and 24VCOM terminals has
gone below the device’s acceptable limit during power up.
(150ms On, 300ms Off, 150ms On, 300ms Off, 800 ms On)
Short Long blink Invalid MAC address: The device’s MAC address is set to zero (0) or is set to an address higher than the
Max Master. See the Network Guide.
(150ms On, 300ms Off)
Long Short Short Short Short Long Short: Backup and Restore. The controller is being backed-up or restored.

(800ms On, 300ms Off, 150ms On, 300ms Off, 150ms On, 300ms Off, 150ms
On, 300ms Off, 150ms On, 300ms Off, 800ms On, 300ms Off, 150ms On)

For issues with the Allure EC-Smart-Vue, refer to the Allure EC-Smart-Vue Hardware Installation Guide.

Product Warranty & Total Quality Commitment


All Distech Controls product lines are built to meet rigorous quality standards and carry a two-year warranty. Distech
Controls is an ISO 9001 registered company.

Hardware Installation Guide: ECB-VAVS-O, ECB-VAVS, ECB-VAV, ECB-VVTS, ECB-VAV-N, ECB-103

©, Distech Controls Inc., 2010. All rights reserved.

While all efforts have been made to verify the accuracy of information in this manual, Distech Controls is not responsible for damages or claims arising from the use of
this manual. Persons using this manual are assumed to be trained HVAC specialist / installers and are responsible for using the correct wiring procedures and
maintaining safe working conditions with fail-safe environments. Distech Controls reserves the right to change, delete or add to the information in this manual at any
time without notice.

Distech Controls, the Distech Controls logo, Open-to-Wireless, Innovative Solutions for Greener Buildings, ECO-Vue, and Allure are trademarks of Distech Controls Inc.
BACnet is a registered trademark of ASHRAE. NiagaraAX Framework is a registered trademark of Tridium, Inc. EnOcean is a registered trademark of EnOcean GmbH.

12/12
*05DI-HIBVAVT-16*
05DI-HIBVAVT-16

You might also like