Professional Documents
Culture Documents
net/publication/266888989
CITATION READS
1 2,236
3 authors:
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
The derating parameters of power transformers operating under nonsinusoidal condition View project
All content following this page was uploaded by Marilena Stanculescu on 21 November 2014.
Abstract. This paper presents a case study concerning The complete technical data, according to the latest
energy efficiency functionality in an electrical technical bulletin, accomplished in 2008, are presented
substation, consisting of two power transformers. The in Table 1 and Table 2.
whole analysis is done in order to accurately express
both active and reactive power losses within the Table 1. Technical data for Transformer 1
substation for a certain load. Thus, a complete power
Transformer power Sn kVA 1600
quality measurement (wave forms, harmonics,
Terminal Primary voltage U1n kV 20
unbalances, flicker etc.) was accomplished with a class
A analyzer (Fluke 435). By analyzing and processing Terminal Secondary voltage U2n kV 0.4
the measured data, we propose a solution for Primary nominal current I1n A 46.2
minimizing the energy loss. The proposed solution is a Secondary nominal current I2n A 2309
substation functioning in time-harmonic regime with Type of Connection Dyn05
only one power transformer. No load losses P0 W 1600
Copper losses Pk W 12000
Keywords: power substation, energy quality, energy loss. No load current i0 % 0.36
Short-circuit voltage uk % 6.33
1. INTRODUCTION
Table 2. Technical data for Transformer 2
The power balance boundary is represented by the power
Transformer power Sn kVA 1600
substation consisting of two oil transformers having
Terminal Primary voltage U1n kV 20
1600 kVA. The transformers are powered at primary
windings with 20 kV. All the equipments in the plant are Terminal Secondary voltage U2n kV 0.4
powered on the secondary windings at 0.4 kV. Primary nominal current I1n A 46.2
Secondary nominal current I2n A 2309
Type of Connection Dyn05
No load losses P0 W 1580
Copper losses Pk W 12000
No load current i0 % 0.36
Short-circuit voltage uk % 6.36
11
Scientific Bulletin of the Electrical Engineering Faculty – Year 11 No. 2 (16) ISSN 1843-6188
12
Because the loads of the two transformers have similar One can notice that the total harmonic distortion (THD)
characteristics, the power quality parameters for the level for the voltage weave form of each phase is very
second transformer are not exposed. small (fewer than 10%) [6].
Figure 8. Voltage waveform of the three power lines. Figure 11. Current waveforms
One can notice a sinusoidal variation of the voltage We notice a balance loading, on each of the three phases,
between the 3 phases and the neutral point of the the current being around 950 A. One can also notice the
transformer’s secondary, which belongs to the admitted relatively high level of harmonic distortion of current for
in terms of the rms values. all the three phase.
Figure 9. Vector diagram and unbalance level for the Figure 12. Vector diagram and unbalance level for the
voltage system current system.
The vector diagram of the voltage system underlines the The vector diagram of the current system shows a
appearance of the positive phase sequence. We can also see normal distribution of the currents. The relative to
the voltages between each phase and the neutral point. The fundamental negative current sequence is 0.4% while
relative to fundamental negative voltage sequence is only zero sequence current is 0.7%. The parameters are under
0.2 %, while zero sequence voltage is 0.3 %. These the acceptable limit (10%), thus the current system can
parameters are under the acceptable limit (2 %) thus the also be accepted as a balanced one [6, 7]
voltage system can be considered as a balanced one [6].
Figure 10. Harmonic histogram of the voltage waveform Figure 13. Harmonic histogram of the current waveform
13
Scientific Bulletin of the Electrical Engineering Faculty – Year 11 No. 2 (16) ISSN 1843-6188
∑I
1
i
2
14
5. RESULTS - OPTIMIZED BALANCE TABLE
Component’s name kW kWh/24h %
0 1 2 3 4
In this section we quantitatively present the active and
INPUT ENERGY
reactive power and energy losses for two different
Active electrical energy 65.67
615.59 14774.16 situations: when the station is working with two
1 Trafo 1 0
Active electrical energy 34.33 transformers (real case), and when the station has only
321.805 7723.320 one transformer (optimum case).
2 Trafo 2 0
TOTAL INPUT ACTIVE 100.0 The transformer circuit model [5] was used in order to
ENERGY 937.395 22497.48 00 evaluate the power and energy losses for primary and
ACTIVE ENERGY LOSSES secondary winding of each transformer.
1 Iron Losses Trafo 1 1.6 38.400 0.171
2 Iron losses Trafo 2 1.58 37.920 0.169 5.1 Active energy real balance
Joule losses primary
0.982 23.568 0.105
3 Trafo 1 Table 3. Active energy real balance for the power
Joule losses secondary substation 2×1600 kVA 20/0.4 kV
0.973 23.352 0.104
4 Trafo 1
Joule losses Primary
0.26 6.240 0.028
5 Trafo 2
Joule losses Secondary 5.2 Reactive energy real balance
0.254 6.096 0.027
6 Trafo 2
7 INCONGRUITIES 0.42 10.08 0.045 Table 4. Reactive energy real balance for the power
TOTAL ACTIVE LOSSES 6.069 145.656 0.647 substation 2×1600 kVA 20/0.4 kV
TOTAL USEFUL 99.35 Component’s name kW kWh/24h %
931.326 22351.82 0 1 2 3 4
ACTIVE ENERGY 3
INPUT REACTIVE
ENERGIES
Reactive electrical
223.11 5354.712 71.256
1 energy Trafo 1
Reactive electrical
90 2160.000 28.744
2 energy Trafo 2
TOTAL INPUT
RECTIVE ENERGY 313.11 7514.712 100.00
REACTIVE LOSSES
Magnetizing losses
5.54 132.960 1.769
1 Trafo 1
Magnetizing loss
5.54 132.960 1.769
2 Trafo 2
Inductance losses
8.237 197.688 2.631
3 Primary Trafo 1
Inductance losses
8.153 195.672 2.604
4 Secondary Trafo 1
Induction losses
2.182 52.368 0.697
5 Primary Trafo 2
Figure 16. Reactive power loss for 1600 kVA Trafo 1 Induction losses
2.144 51.456 0.685
6 Secondary Trafo 2
7 INCONGRUITIES 0.42 10.08 0.134
TOTAL REACTIVE
32.216 773.184 10.289
ENERGY LOSSES
TOTAL USEFUL
280.897 6741.528 89.711
REACTIVE ENERGY
15
Scientific Bulletin of the Electrical Engineering Faculty – Year 11 No. 2 (16) ISSN 1843-6188
Acknowledgment
Table 5. Active energy optimum balance for the power [1] Arri, E. Locci, N. Mocci, F., Measurement of
substation 1 x 1600 kVA 20/0.4 kV transformer power losses and efficiency in real
Nr. Component’s name kW kWh/24h % working conditions, International Conference on
0 1 2 3 4 Precision Electromagnetic Measurements CPEM.
INPUT ENERGIES 1990, pp. 164 – 165, Ottawa, June1990.
Active electrical energy
[2] Golovanov N, et. al, Power Plants and industrial
931.265 22350.360 100.000 audit elements, N’ERGO Publishing House, 2008
1 from Trafo
2 0 0.000 0.000 (in romanian).
931.265 22350.360 100.000
[3] Olivares J. C., et al, Reducing Losses in Distribution
TOTAL ACTIVE ENERGY
Transformers, IEE Transactions on Power
ENERGY LOSSES
Delivery, vol. 18, no. 3, July 2003, pp. 821-825.
1 Iron losses in Trafo 1.6 38.400 0.172 [4] Lin, D., Fuchs, E. F., Real-time monitoring of iron-
Joule losses primary 2.23792 53.710 0.240 core and copper losses of three-phase transformers
2 Trafo under (non)sinusoidal operation, IEEE
Joule losses secondary Transactions on Power Delivery, vol. 21, issue 3,
2.22309 53.354 0.239
3 Trafo July 2006, pp. 1333-1341.
4 INCONGRUITIES 0.42 10.08 0.045 [5] Fitzgerald, A. E., Kingsley C. Jr., Umans S., Electric
TOTAL ENERGY LOSSES 6.48101 155.544 0.696 Machinery, McGraw-Hill Science, 6th Edition,
924.784 22194.816 99.304
2002.
TOTAL USEFUL ENERGY
[6] Bollen, M.H.J., Understanding Power Quality
Problems, IEEE Press Series on Power
6. CONCLUSIONS
Engineering, 2000.
[7] Pierce, L.W., Transformer design and application
Analyzing both measured and computed data for the real
considerations for nonsinusoidal load currents,
balance, we can conclude the following:
IEEE Transactions on Industry Applications, vol.
- the power substation necessary to assure the energy
32, issue 3, May-June 1996, pp. 633-645.
consumption for the whole factory, consisting of two
[8] Fuchs, E.F., Lin, D., Martynaitis, J., Measurement of
transformers of 1600 kVA with almost identical
three-phase transformer derating and reactive
characteristics, that are functioning with a high
power demand under nonlinear loading conditions,
efficiency (the transformer’s loading is in the optimum
IEEE Transactions on Power Delivery, vol. 21,
functioning area).
issue 2, April 2006, pp. 665-672.
- the total active energy for the whole station (for the 2
transformers) during 24h is approx. 22 MWh, having an
average power factor of approx. 0.95.
- the energy losses of the two transformers are normal
for the exploitation practice or for those presented in
literature characteristic to the specified power class of
these transformers (between 1000-2000 kVA) [4, 5].
16