TECHNICAL MANUAL
Chilled Water Fan Coil Units
AWM, ACK, ACM, ACC, ADB Series
AWM-LW ACK-EW
ACK-CW ACM-DW/EW
ACC-CW ADB-BW
Table of Contents
Table of Contents
Nomenclature......................................................................................................................1
Application Information .....................................................................................................9
Installation Guide .........................................................................................................10
Sound Data........................................................................................................................15
NC Curve .....................................................................................................................22
Selection Process.............................................................................................................43
Engineering & Physical Data ...........................................................................................58
Outlines & Dimensions ....................................................................................................69
Wiring Diagrams .............................................................................................................101
Service & Maintenance .................................................................................................. 116
Troubleshooting ............................................................................................................. 117
Bulletin illustrations cover the general appearance of Acson International products at the time of publication.
We reserve the right to change design and construction specifications at any time without notice.
Nomenclature
Nomenclature
(Wall Mounted Fan Coil Unit)
A WM 10 L W – A C E D A - R
RoHS Compliance
Brand Product Specification Variation
A : Acson A : First Issue
Operating Mode
Size (Cooling/Heating) E : Cooling Only
07 : 8,300/11,000 btu/hr H : Heatpump
10 : 9,200/12,000 btu/hr
15 : 11,300/15,000 btu/hr
20 : 15,500/20,500 btu/hr Market Region
25 : 18,000/25,000 btu/hr C : Export with CE Mark
1
Nomenclature
Nomenclature
(Cassette Fan Coil Unit C series)
A CK 10 C W – A X AB - R
Brand
A : Acson
Product Type
CK : Ceiling Cassette
RoHS Compliance
Size (Cooling/Heating)
10 : 8,500/12,000 btu/hr
15 : 14,000/16,000 btu/hr Product Specification Variation
20 : 15,500/18,000 btu/hr
2
Nomenclature
Nomenclature
(Cassette Fan Coil Unit A series)
A CK 25 A W – A X AB - R
Brand
A : Acson
Product Type
CK : Ceiling Cassette
RoHS Compliance
Size (Cooling/Heating)
20 : 22,500 / 28,500 btu/hr Product Specification Variation
25 : 25,500 / 32,000 btu/hr
30 : 30,000 / 37,500 btu/hr
40 : 33,500 / 40,500 btu/hr Type of ref. connection
50 : 36,500 / 44,000 btu/hr X : Not applicable
Product Series
A : A series Electrical Characteristics
A : 50Hz / 1Ph / 220-240V
Model Piping
W : Chilled Water Fan Coil H : 4 pipes system
3
Nomenclature
Nomenclature
(Ceiling Cassette E series)
A CK 20 E W – A E C A A - R
RoHS Compliance
Brand Product Specification Variation
A : Acson A : First Issue
Product Series
E : E series Electrical Characteristics
A : 50Hz / 1Ph / 220-240V
Model
W : Chilled Water Fan Coil
4
Nomenclature
Nomenclature
(Ceiling Mounted D series)
M
A CM 25 D W – A X AB - R
Brand
A : Acson
Product Type
CM : Ceiling Mounted
RoHS Compliance
Size (Cooling/Heating)
20 : 17,000 / 22,000 btu/hr Product Specification Variation
25 : 20,800 / 25,900 btu/hr
30 : 24,600 / 28,000 btu/hr
40 : 31,200 / 42,300 btu/hr Type of ref. connection
50 : 45,000 / 51,500 btu/hr X : Not applicable
Product Series
D : D series Electrical Characteristics
A : 50Hz / 1Ph / 220-240V
Model
W : Chilled Water Fan Coil
5
Nomenclature
Nomenclature
(Ceiling Mounted E series)
A CM 15 E W – A X AB - R
Brand
A : Acson
Product Type
CM : Ceiling Mounted
RoHS Compliance
Product Series
E : E series Electrical Characteristics
A : 50Hz / 1Ph / 220-240V
Model
W : Chilled Water Fan Coil
6
Nomenclature
Nomenclature
(Ceiling Concealed)
A CC 010 C W – A X AC – R
Brand
A : Acson
RoHs Compliance
Product Type
CC : Ceiling Concealed
Size (Cooling/Heating)
010 : 9,900/11,500 btu/hr Product Specification Variation
015 : 11,600/15,000 btu/hr
020 : 18,000/23,000 btu/hr
025 : 22,500/29,000 btu/hr Type of ref. connection
028 : 26,000/33,000 btu/hr X : Not applicable
030 : 28,000/36,000 btu/hr F : For Flare
038 : 35,200/43,000 btu/hr
040 : 38,000/46,000 btu/hr
050 : 47,000/57,000 btu/hr Electrical Characteristics
060 : 54,000/67,000 btu/hr A : 50Hz / 1Ph / 220-240V
Product Series
C : C series
Model
W : Chilled Water Fan Coil
7
Nomenclature
Nomenclature
(Ducted Blower B series)
A DB 75 B W – A X AB - R
Brand
A : Acson
Product Type
DB : Ducted Blower
RoHS Compliance
Model
W : Chilled Water Fan Coil
8
Application Information
Application Information
Model: AWM Series
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode Heating Mode
Temperature Ts °C/°F Th °C/°F Temperature Ts °C/°F Th °C/°F
Minimum indoor Minimum indoor
19.0 / 66.2 14.0 / 57.2 15.0 / 59.0 -
temperature temperature
Maximum indoor Maximum indoor
32.0 / 89.6 23.0 / 73.4 27.0 / 80.6 -
temperature temperature
Ts: Dry bulb temperature. Th: Wet bulb temperature.
9
Application Information
Installation Guide
System Configuration
The standard controller board (W2/W3) comes with a VALVE jumper and a HEAT jumper. The system can be
configured as the jumper selection listed below:
HEAT Jumper VALVE Jumper
Heatpump Mode & Valve Application √ √
Heatpump Mode & Valveless Application √ X
Cooling Mode & Valve Application X √
Cooling Mode & Valveless Application X X
√ Jumper Remained X Jumper Removed
Caution
Disconnect the power supply to the unit before attempting to connect the wiring
BLACK
WHITE
BROWN
FM BLACK (LIVE)
RED (FAN CAP)
WHITE (NEUTRAL)
AS
N
CN_FAN CN_STP CN_FAN FB
VALVE
Heat Jumper
VALVE HEAT
L
CN_ID COIL
Valve Jumper
TH1
NOTATION
FM : FAN MOTOR
TH2
BLACK
BLUE
BLUE
10
Application Information
CN_DRY
SLIENT
CVLV
WTP
HVLV
LOW
MED
AS
HI
N2 LIVE
CN_TW
M1
M2
E
LV
M3
VA
M4
CN_PGRM
HE
H_SEN C_SEN ROOM CN_WIR CN_STP CN_DSP
AT
Valve Jumper Heat Jumper Fan Priority Jumper
CN_DRY
SLIENT
HVLV
CVLV
LOW
WTP
MED
AS
HI
LIVE
N2
L
CO_DRAFT TFULL A_FRZ W_OPEN UNOCP
HTR
N1
CN_TW
Model 1
M1
M2 Model 2
E
LV
M3 Model 3
VA
M4
CN_PGRM Model 4
SHED
HE
CN_STP CN_DSP
AT
The standard controller board (W2.0/W3.0) comes with a default setting for model selec-
tion. Please select the model accordingly by using jumper.
11
Application Information
FCU Boiler
FCU
Boiler
C) Others
The controller board comes with other option.
L
UNOCP A_FRZ W_OPEN TFULL
Unoccupied Mode
COMP
Anti Freeze Mode
TRANSFORMER
SHED
i) Unoccupied Mode
If the dry contact is closed, the Unoccupied mode is activated and vice versa. When Timer On is active,
system goes back to Occupied mode.
The dry contact connection points can be connected parallel with other fan coil unit (FCU) boards. If the
dry contact is closed, Unoccupied mode will be activated on all fan coil units that are connected parallel as
shown in figure below.
12
Application Information
Global Unoccupied, Global Window Open and Global Load Shedding operation could also be activated via the
network communication bus line by master controller with or without the above connection.
NOTE :
i) Auto Fan Mode is only applicable in Model 3 only. (Cooling only with Boiler)
ii) Fan mode is not available in valveless control.
iii) Wired handset has an indoor room sensor. Avoid locating the wired handset at isolated places where room
temperature reading will be inaccurate.
13
Application Information
Cable Size
ACK020/025/030/
Model Unit AWM07/10/15/20/25LW AWM301W
040/050AW
Power supply cable size* mm² 1.5 2.5 1.5
Number of wire 3 3 3
Recommended fuse* A 2 20 2
ACK020/025/030/ ACM020/025/
Model Unit ACM015/020EW
040/050AWH 030/040/050DW
Power supply cable size* mm² 1.5 1.5 2.5
Number of wire 3 3 3
Recommended fuse* A 2 2 2
Important: * These values are for information only. They should be checked and selected to comply local
or national codes and regulations. They are also subjected to the type of installation and size of
conductors.
14
Sound Data
Sound Data
Sound Pressure Level
1/1 Octave A-Weighted Sound Pressure (dBA), ref 20μPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 31 32 33 28 26 14 6 34 28
AWM07LW Med 25 29 28 24 19 9 5 29 22
Low 20 26 24 20 11 8 6 25 18
High 30 33 33 32 28 17 8 35 31
AWM10LW Med 26 29 30 27 21 11 7 30 25
Low 19 25 25 21 14 6 6 25 19
High 41 39 39 38 36 26 14 42 38
AWM15LW Med 38 36 37 34 32 22 10 39 33
Low 30 30 31 28 23 12 7 32 26
High 37 38 38 39 33 22 11 42 38
AWM20LW Med 33 35 35 35 29 17 8 38 34
Low 29 33 32 31 23 12 7 34 30
High 42 42 42 42 40 31 21 46 42
AWM25LW Med 37 38 39 38 34 24 13 42 37
Low 34 35 36 35 30 20 9 39 34
High 42 46 45 44 41 35 28 49 43
*AWM301W Med 40 45 44 43 38 33 27 47 42
Low 37 43 43 40 35 30 26 45 39
Microphone position: 1m in front and 0.8m/*1m below the vertical centre line of the unit.
1/1 Octave A-Weighted Sound Pressure (dBA), ref 20μPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 46 45 40 38 32 21 14 42 37
ACK020AW/
Med 44 43 37 33 28 18 12 39 32
AWH
Low 43 42 35 31 26 17 11 37 31
High 48 46 43 39 33 27 19 45 38
ACK025AW/
Med 45 43 40 35 29 21 15 42 35
AWH
Low 43 42 38 32 27 19 14 40 33
High 50 48 47 43 37 35 28 49 42
*ACK030AW/
Med 48 45 43 38 32 31 27 45 38
AWH
Low 46 43 41 35 30 30 26 43 36
High 50 49 49 46 39 38 31 51 45
*ACK040AW/
Med 48 47 47 43 36 34 25 48 42
AWH
Low 46 45 46 41 34 30 23 46 41
High 54 52 51 48 43 42 34 53 47
*ACK050AW/
Med 52 50 50 46 41 40 32 52 46
AWH
Low 51 49 49 45 39 39 31 50 45
Microphone position: 1.4m/*1.5m below the face center of the air return of the unit.
15
Sound Data
1/1 Octave A-Weighted Sound Pressure (dBA), ref 20μPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 44 45 40 36 26 19 10 42 35
ACK010CW Med 40 38 34 28 19 9 7 35 29
Low 37 32 27 20 14 7 7 29 21
High 48 48 44 39 31 27 15 45 39
ACK015CW Med 42 42 36 30 22 13 7 38 31
Low 39 36 28 20 15 6 6 30 23
High 52 51 46 41 34 31 19 48 41
ACK020CW Med 44 43 39 33 26 18 8 40 33
Low 41 39 35 28 22 11 7 36 30
Microphone position: 1.4m below the face center of the air return of the unit.
1/1 Octave A-Weighted Sound Pressure (dBA), ref 20μPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 44 43 42 35 29 23 15 42 37
ACK020EW Med 40 40 38 30 23 16 14 38 33
Low 35 34 32 23 15 10 14 32 26
High 48 47 45 39 34 28 17 46 40
ACK025EW Med 44 42 42 34 28 21 10 42 37
Low 39 37 36 26 19 10 6 35 31
High 49 48 46 42 37 35 22 48 41
*ACK030EW Med 44 44 42 36 32 27 14 43 37
Low 41 39 37 31 26 17 8 38 32
High 51 49 49 45 37 36 24 50 45
*ACK040EW Med 48 46 47 40 33 31 18 47 43
Low 44 42 43 35 28 23 10 43 38
High 53 54 50 47 39 38 28 52 46
*ACK050EW Med 49 48 47 43 36 35 25 49 43
Low 46 45 44 39 32 30 22 45 39
Microphone position: 1.4m/*1.5m below the face center of the air return of the unit.
1/1 Octave A-Weighted Sound Pressure (dBA), ref 20μPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 45 46 47 46 41 38 29 50 45
ACM020DW Med 42 43 45 42 38 34 24 47 41
Low 36 37 39 35 31 24 15 40 34
High 48 51 51 50 45 41 33 54 49
ACM025DW Med 47 50 50 49 44 40 32 53 48
Low 45 47 48 47 41 36 27 50 46
High 45 48 48 47 43 33 24 51 46
*ACM030DW Med 44 47 47 46 42 32 23 50 45
Low 43 45 45 44 39 29 20 48 43
High 51 53 51 50 47 37 30 54 49
*ACM040DW Med 48 51 50 49 46 36 28 53 48
Low 46 50 49 48 44 35 27 52 47
High 51 53 51 50 47 37 30 54 49
*ACM050DW Med 48 51 50 49 46 36 28 53 48
Low 46 50 49 48 44 35 27 52 47
Microphone position: 1m in front of the unit and 0.8m/*1m below the air discharge opening.
16
Sound Data
1/1 Octave A-Weighted Sound Pressure (dBA), ref 20μPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 42 46 49 44 43 36 31 50 45
ACM15EW Med 36 40 43 37 36 27 20 43 38
Low 34 38 41 34 33 23 15 41 36
High 45 47 51 48 47 40 34 53 48
ACM20EW Med 43 46 49 46 44 37 31 51 45
Low 42 46 47 44 42 35 27 49 43
High 47 50 53 50 50 43 39 56 51
ACM25EW Med 44 46 49 46 45 38 33 51 46
Low 38 40 43 38 37 28 22 44 38
Microphone position: 1m in front of the unit and 1m below the air discharge opening.
1/1 Octave A-Weighted Sound Pressure (dBA), ref 20μPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 43 35 35 30 26 18 13 36 30
ACC010CW Med 43 34 34 28 25 17 12 35 29
Low 42 31 31 27 22 14 9 33 25
High 46 40 40 33 29 21 17 40 35
ACC015CW Med 45 38 38 31 27 18 14 38 33
Low 40 33 33 26 21 11 9 33 28
High 47 41 43 35 31 24 19 42 38
ACC020CW Med 47 41 41 34 31 23 18 41 36
Low 47 39 39 33 29 21 16 40 34
High 48 41 40 35 31 24 19 41 35
ACC025CW Med 47 39 39 34 29 22 17 40 34
Low 44 35 35 30 25 17 12 36 30
High 45 42 39 35 31 26 22 41 34
ACC028CW Med 42 38 37 32 28 22 17 38 32
Low 36 33 33 27 23 16 11 34 27
High 50 45 43 42 37 31 26 46 41
ACC030CW Med 45 40 40 38 32 26 20 42 37
Low 42 36 37 33 28 22 15 38 32
High 54 51 48 46 41 36 31 51 45
ACC038CW Med 51 48 46 45 37 32 26 48 44
Low 47 45 44 41 34 28 22 45 40
High 54 47 47 45 39 35 29 49 44
ACC040CW Med 49 42 43 41 35 31 24 45 40
Low 45 39 41 37 30 26 18 41 36
High 54 49 49 48 43 37 32 52 47
ACC050CW Med 53 47 46 47 40 35 29 50 46
Low 51 45 44 44 36 32 26 47 43
High 55 49 49 50 44 37 33 53 49
ACC060CW Med 53 46 47 47 39 34 28 50 46
Low 51 43 44 43 35 30 24 47 42
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and air return inlet)
17
Sound Data
1/1 Octave A-Weighted Sound Pressure (dBA), ref 20μPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 57 50 47 44 40 35 24 50 43
ADB075BW Med 57 46 44 40 35 30 17 46 41
Low 48 42 41 35 30 24 6 42 36
High 57 53 50 50 44 40 31 54 49
ADB100BW Med 55 51 49 48 42 38 28 52 47
Low 54 50 48 46 40 35 25 50 45
ABD125BW High 57 55 56 53 51 46 38 58 53
ADB150BW High 57 55 56 53 51 46 38 58 53
Microphone position: 1m in front of the unit and center of the unit.
1m away from every side of the unit and 1m above floor level.
18
Sound Data
19
Sound Data
20
Sound Data
21
Sound Data
NC Curve
AWM07LW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 NC-50
NC-45
40 NC-40
NC-35
H
30 NC-30
M
L NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
AWM010LW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50 NC-50
NC-45
40 NC-40
NC-35
H
30 M NC-30
L NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
22
Sound Data
AWM15LW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50
NC-50
NC-45
40 H NC-40
M NC-35
30 L NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
AWM20LW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 NC-50
NC-45
40 H NC-40
M NC-35
30
L
NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
23
Sound Data
AWM25LW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50 NC-50
NC-45
H
40 NC-40
M
NC-35
L
30 NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
AWM301W
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50
NC-50
H
NC-45
M
40 L NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
24
Sound Data
ACK020AW/AWH
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50
NC-50
NC-45
40 H NC-40
M NC-35
30
L
NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACK025AW/AWH
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50 NC-50
NC-45
H
40 NC-40
M
NC-35
L
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
25
Sound Data
ACK030AW/AWH
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50
NC-50
H
NC-45
M
40
NC-40
L NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACK040AW/AWH
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 H NC-50
M NC-45
40 L NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
26
Sound Data
ACK050AW/AWH
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
H
50 NC-50
M
L NC-45
40 NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACK10CW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 NC-50
NC-45
40 H NC-40
NC-35
M
30 NC-30
L
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
27
Sound Data
ACK15CW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50 NC-50
NC-45
H
40 NC-40
M NC-35
30 NC-30
L NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACK20CW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50
NC-50
H NC-45
40
M NC-40
NC-35
L
30 NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
28
Sound Data
ACK20EW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50
NC-50
NC-45
40 H NC-40
M NC-35
30 L NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACK25EW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50 NC-50
H NC-45
40 M NC-40
NC-35
L
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
29
Sound Data
ACK30EW
70
Sound pressure level (dB, ref 20PPa)
60
NC-55
50
NC-50
H
NC-45
40 M
NC-40
L NC-35
30 NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
ACK40EW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 NC-50
H
M NC-45
40 L NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
30
Sound Data
ACK50EW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50 H NC-50
M NC-45
40 L NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACM020DW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50
H NC-50
NC-45
40
M
NC-40
L NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
31
Sound Data
ACM025DW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
H
50 NC-50
M
L NC-45
40 NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACM030DW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50 H NC-50
M
NC-45
L
40
NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
32
Sound Data
ACM040DW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
H
50 M NC-50
L NC-45
40 NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACM050DW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
H
50 M NC-50
L NC-45
40 NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
33
Sound Data
ACM15EW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50
H NC-50
NC-45
M
40 NC-40
L NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACM20EW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50
H
NC-50
M
NC-45
L
40 NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
34
Sound Data
ACM25EW
70
60
Sound pressure level (dB, ref 20PPa)
H NC-55
50
NC-50
M
NC-45
40
L NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACC10CW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 NC-50
NC-45
40 NC-40
H NC-35
30 M NC-30
L
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
35
Sound Data
ACC15CW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50 NC-50
NC-45
40 NC-40
H
NC-35
M
30 L NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACC20CW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50
NC-50
NC-45
40 H
M NC-40
L NC-35
30 NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
36
Sound Data
ACC25CW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 NC-50
NC-45
40 H NC-40
M NC-35
30 L NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACC28CW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50 NC-50
NC-45
40 H NC-40
NC-35
M
30 NC-30
L
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
37
Sound Data
ACC30CW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 NC-50
H NC-45
40 NC-40
M
NC-35
L
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ACC38CW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50 NC-50
H
M NC-45
40 L NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
38
Sound Data
ACC40CW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50
H NC-50
NC-45
M
40
NC-40
L
NC-35
30 NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
ACC50CW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 H NC-50
M
NC-45
L
40 NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
39
Sound Data
ACC60CW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
50 H
NC-50
M
NC-45
40 L
NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ADB75BW
70
60
Sound pressure level (dB, ref 20μPa)
NC-55
50 NC-50
H
NC-45
M
40 NC-40
L NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
40
Sound Data
ADB100BW
70
60
Sound pressure level (dB, ref 20PPa)
NC-55
H
50 NC-50
M
L NC-45
40 NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
ADB125BW
70
60
Sound pressure level (dB, ref 20PPa)
H
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30 NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
41
Sound Data
ADB150BW
70
60
Sound pressure level (dB, ref 20μPa)
H
NC-55
50 NC-50
NC-45
40 NC-40
NC-35
30 NC-30
NC-25
20 NC-20
10
0
125 250 500 1000 2000 4000 8000
42
Selection Process
Selection Process
The following table summarizes the pulley data, motor size used for the ADB series, as manufactured:
Motor Pulley
Pulley Center Distance, C Blower Pulley, Db
Diameter, Dm
Model Motor, kW Motor RPM
Horizontal Vertical Taper # Taper #
(mm) (mm) (mm) (mm)
ADB125BW 340 350 1.5 1500 80 150
ADB150BW 320 N/A 2.2 1500 80 160
43
Fan Performance Chart
ACC10CW
Pa mmAq
69 7
49 5
External Static Pressure
39 4
29 3
20 2
10 1
0 0
200 250 300 350 400 450 CFM
340 400 450 500 550 600 650 700 765 CMH
Air Flow
44
Fan Performance Chart
ACC15CW
Pa mmAq
69 7
59 6
49 5
External Static Pressure
39 4
29 3
20 2
10 1
0 0
300 350 400 450 500 550 600 650 700 750 800 CFM
510 600 700 800 900 1000 1100 1200 1300 1360 CMH
Air Flow
45
Fan Performance Chart
ACC20CW
Pa mmAq
69 7
HIGH
59 6 MEDIUM
LOW
49 5
External Static Pressure
39 4
29 3
20 2
10 1
0 0
550 600 650 700 750 800 850 900 950 CFM
935 1000 1100 1200 1300 1400 1500 1615 CMH
Air Flow
46
Fan Performance Chart
ACC25CW
Pa mmAq
69 7
59 6
LOW MEDIUM HIGH
49 5
External Static Pressure
39 4
29 3
20 2
10 1
0 0
450 500 550 600 650 700 750 800 850 900 950 CFM
765 900 1000 1100 1200 1300 1400 1500 1615 CMH
Air Flow
47
Fan Performance Chart
ACC28CW
Pa mmAq
118 12
LOW MEDIUM HIGH
98 10
78 8
External Static Pressure
59 6
39 4
20 2
0 0
300 400 500 600 700 800 900 1000 1100 1200 CFM
510 700 900 1100 1300 1500 1700 1900 2040 CMH
Air Flow
48
Fan Performance Chart
ACC30CW
Pa mmAq
177 18
HIGH
157 16
MEDIUM
LOW
137 14
118 12
External Static Pressure
98 10
78 8
59 6
39 4
20 2
0 0
400 600 800 1000 1200 1400 CFM
680 900 1100 1300 1500 1700 1900 2100 2380 CMH
Air Flow
49
Fan Performance Chart
ACC38CW
Pa mmAq
177 18
HIGH
157 16
MEDIUM
LOW
137 14
118 12
External Static Pressure
98 10
78 8
59 6
39 4
20 2
0 0
400 600 800 1000 1200 1400 CFM
680 900 1100 1300 1500 1700 1900 2100 2380 CMH
Air Flow
50
Fan Performance Chart
ACC40CW
Pa mmAq
177 18
HIGH
MEDIUM
157 16
LOW
137 14
External Static Pressure
118 12
98 10
78 8
59 6
39 4
20 2
0 0
600 700 800 900 1000 1100 1200 1300 1400 1500 CFM
1020 1200 1400 1600 1800 2000 2200 2400 2550 CMH
Air Flow
51
Fan Performance Chart
ACC50CW
Pa mmAq
177 18
HIGH
MEDIUM
LOW
157 16
137 14
118 12
External Static Pressure
98 10
78 8
59 6
39 4
20 2
0 0
900 1000 1100 1200 1300 1400 1500 1600 1700 1800 CFM
1530 1700 1900 2100 2300 2500 2700 2900 3060 CMH
Air Flow
52
Fan Performance Chart
ACC60CW
Pa mmAq
177 18
HIGH
MEDIUM
157 16
LOW
137 14
118 12
External Static Pressure
98 10
78 8
59 6
39 4
20 2
0 0
1000 1200 1400 1600 1800 2000 CFM
1700 1900 2100 2300 2500 2700 2900 3200 3400 CMH
Air Flow
53
Fan Performance Chart
ADB75BW
Pa mmAq
137 14
98 10
External Static Pressure
78 8
59 6
39 4
20 2
0 0
0 500 1000 1500 2000 2500 3000 CFM
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5100 CMH
Air Flow
54
Fan Performance Chart
ADB100BW
Pa mmAq
137 14
118 12
98 10
External Static Pressure
78 8
59 6
39 4
20 2
0 0
2000 2500 3000 3500 4000 CFM
3400 4000 4500 5000 5500 6000 6500 6800 CMH
Air Flow
55
Fan Performance Chart
ADB125BW
RPM
500
1.5 kW
450 900
400
350 800
1.1 kW
Standard
Point
Total Static Pressure (Pa)
300
250 700
200
600
150
Internal Static
Pressure with air filter
100
Internal Static
Pressure w/o air filter
50
0
3500 4000 4500 5000 CFM
Air Flow
56
Fan Performance Chart
ADB150BW
RPM
600
2.2 kW
1000
500
1.5 kW
900
400
Standard
Point
Total Static Pressure (Pa)
1.1 kW
800
300
700
Internal Static
Pressure with filter
200
Internal Static
Pressure w/o filter
100
0
3500 4000 4500 5000 5500 CFM
1652 1850 2050 2250 2450 2596 L/s
Air Flow
57
Engineering & Physical Data
58
Engineering & Physical Data
FAN
LOW RPM 1112
HIGH % N/A
FAN EFFICIENCY MEDIUM % N/A
LOW % N/A
TYPE INDUCTION
INDEX OF PROTECTION (IP) IPX0
INSULATION GRADE B
HIGH W 74
RATED INPUT
MEDIUM W 59
POWER
LOW W 46
HIGH A 0.32
RATED RUNNING
FAN MOTOR MEDIUM A 0.26
CURRENT
LOW A 0.21
STARTING CURRENT A N/A
MOTOR OUTPUT W 40
HIGH % N/A
MOTOR
MEDIUM % N/A
EFFICIENCY
LOW % N/A
POLES 4
MATERIAL COPPER
TUBE
DIAMETER mm 9.52
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.29
ROW 2
WATER VOLUME litre 1.425
WASHABLE SARANET
AIR TYPE
FILTER FILTER
QUALITY
QUANTITY pc 2
CASING COLOUR WHITE
59
Engineering & Physical Data
60
Engineering & Physical Data
61
Engineering & Physical Data
62
Engineering & Physical Data
63
Engineering & Physical Data
64
Engineering & Physical Data
65
Engineering & Physical Data
66
Engineering & Physical Data
67
Engineering & Physical Data
68
Outlines & Dimensions
Note: Dimension in mm
69
Outlines & Dimensions
Model: AWM20/25LW
Note: Dimension in mm
70
Outlines & Dimensions
Model: AWM301W
INSTALLATION PLATE
D
SIDE VIEW
C
FRONT VIEW
TOP VIEW
A
A B C D E
1120,0 (44,1) 360,0 (14,2) 200,0 (7,9) 730,0 (28,7) 347,0 (13,7)
Note: Dimension in mm
71
Outlines & Dimensions
Model: ACK20/25/30/40/50AW
930
622
642 555
555
930
SEE DETAIL A
28
363
335
DETAIL A
113
158
63
WATER OUTLET
WATER INLET
820
820
Note: Dimension in mm
72
Outlines & Dimensions
Model: ACK20/25/30/40/50AWH
G
I
J
K
H
F
E
C
D
B
Model A B C D E F G H I J K
ACK20AWH 820 820 363 335 28 930 930 642 622 555 555
ACK25AWH 820 820 363 335 28 930 930 642 622 555 555
ACK30AWH 820 820 363 335 28 930 930 642 622 555 555
ACK40AWH 820 820 363 335 28 930 930 642 622 555 555
ACK50AWH 820 820 363 335 28 930 930 642 622 555 555
Note: Dimension in mm
73
Outlines & Dimensions
Model: ACK010/015/020CW
640
H
408
G
364
F
408
K
364
D
E
SEE DETAIL A
DETAIL A
25C0
J
I
WATER OUTLET
WATER INLET
57B0
Dimension
A B C D E F G H I J K
Model
ACK010CW/
ACK015CW/ 570 570 250 640 408 364 408 640 75 98 364
ACK020CW
Note: Dimension in mm
74
Outlines & Dimensions
Model: ACK020/025/030/040/050EW
930
622
642 555
555
930
SEE DETAIL A
28
363
335
DETAIL A
113
158
63
WATER OUTLET
WATER INLET
820
820
Note: Dimension in mm
75
Outlines & Dimensions
Model: RCM20/25/30/40/50DW
P
P
Q
Q
DETAIL A
DETAIL B
WATER INLET
N
WATER OUTLET
WATER INLET
WATER OUTLET
H
G
C
L
A
B D J K
Model A B C D E F G H I J K L M N O P Q
RCM20DW 1174 75 1082 68 58 156 1214 57 670 216 319 879 517 65 - 120 40
RCM25DW 1174 75 1082 68 58 156 1214 57 670 216 319 879 517 65 - 120 40
RCM30DW 1174 75 1082 68 93 156 1214 57 670 216 319 879 517 100 47 100 53
RCM40DW 1674 75 1582 68 93 156 1214 57 670 216 319 1379 517 95 40 100 45
RCM50DW 1674 75 1582 68 93 156 1214 57 670 216 319 1379 517 95 40 100 45
Note: Dimension in mm
76
Outlines & Dimensions
Model: ACM15/20/25EW
129.0
106.6
DETAIL A
DRAIN PIPE
143.6
155.5 57.0
212.5
21.0
SEE DETAIL A
630.0
230.0
+30.0
800.0 0.0
1090.0
20.0
20.0
+10.0
150.0 0.0
Note: Dimension in mm
77
Outlines & Dimensions
Note: Dimension in mm
78
Outlines & Dimensions
Note: Dimension in mm
79
Outlines & Dimensions
Note: Dimension in mm
80
Outlines & Dimensions
Note: Dimension in mm
81
Outlines & Dimensions
Note: Dimension in mm
82
Outlines & Dimensions
Note: Dimension in mm
83
Outlines & Dimensions
Note: Dimension in mm
84
Outlines & Dimensions
Note: Dimension in mm
85
Outlines & Dimensions
Note: Dimension in mm
86
Outlines & Dimensions
Note: Dimension in mm
87
Outlines & Dimensions
Note: Dimension in mm
88
Outlines & Dimensions
Note: Dimension in mm
89
Outlines & Dimensions
Note: Dimension in mm
90
Outlines & Dimensions
Note: Dimension in mm
91
Outlines & Dimensions
Note: Dimension in mm
92
Outlines & Dimensions
Note: Dimension in mm
93
Outlines & Dimensions
Note: Dimension in mm
94
Outlines & Dimensions
Note: Dimension in mm
95
Outlines & Dimensions
Note: Dimension in mm
96
Outlines & Dimensions
Note: Dimension in mm
97
1402.0
53.0 1232.0 117.0 33.0
Model: ADB75/100BW
WATER INLET
122.6
WATER OUTLET
162.5
122.6
50.0 50.0
394.0
ADB75BW
ADB100BW
SEE DETAIL A SEE DETAIL B
MODEL
48.5
20.0 1462.0 20.0
1502.0 761.0
96.0
A
60.0 605.0
287.0 270.0 288.0 270.0 287.0 SEE DETAIL A
35.0
94.0
72.0
177.0
291.8
537.0
437.0
572.0
295.0
122.6
65.0
SEE DETAIL B 33.0
100.0
A
35.0
533.0
Note: Dimension in mm
Outlines & Dimensions
98
99
1540.0
53.0 1370.0 117.0
Outlines & Dimensions
88.0
47.7
WATER INLET
50.0 50.0
257.5
WATER OUTLET
174.0
754.6
A
ADB150BW
ADB125BW
20.0 1600.0 20.0
MODEL
47.7
Model: ADB125/150BW (Horizontal Air Discharge)
1640.0
1040.0
1540.0
60.0 850.0 130.0
533.0 474.0 533.0
35.0
SEE DETAIL A
155.0
132.0
220.0
408.0
747.0
885.0
453.5
257.0
174.0
A
103.0
Note: Dimension in mm
1540.0
53.0 1370.0 117.0
47.7
88.0
WATER INLET
50.0 50.0
382.0
257.5
WATER OUTLET
174.0
754.6
408.0
A
ADB150BW
ADB125BW
SEE DETAIL A SEE DETAIL B
Model: ADB125/150BW (Vertical Air Discharge)
474.0 533.0
MODEL
533.0
60.0
47.7
20.0 1600.0 20.0
980.0
1640.0
850.0
1540.0 130.0
60.0
SEE DETAIL A
35.0
155.0
132.0
747.0
885.0
945.0
453.5
174.0
Note: Dimension in mm
Outlines & Dimensions
100
Wiring Diagrams
Wiring Diagrams
Model: AWM07/10/15/20/25LW
101
HEAT
VALVE WMGW W2_L
MAIN BOARD
DISPLAY BOARD
Model: AWM301W
ROOM THERMISTOR
RO OM
DRY
COOL
N1
SL EE P
F/HEAT
ID
CN 4
INDOOR COIL THERMISTOR
SWITCH BOARD
C N - D SP
N2
BLUE
BLUE
BLUE
RED
RLY2
RLY3
CAPACITOR CN-FAN
C N - W IR C N - S T P
LIVE VALVE
BLUE FAN MOTOR
PURPLE
ORANGE (LO)
BROWN (MED)
FM YELLOW (HI)
YELLOW/GREEN AS
RED
CAUTION!
FM FAN MOTOR COMP N2 N1 L
AS AIR SWING MOTOR
FIELD SUPPLY WIRING
L 220-240VAC
WITH JUMPER FOR HEAT PUMP N 1PHASE
HEAT
WITHOUT JUMPER FOR COOLING ONLY TO 3 WAY E 50Hz
WITH JUMPER FOR VALVE APPLICATION VALVE
VALVE
WITHOUT JUMPER FOR VALVELESS APPLICATION
102
103
LED/IR RECEIVER
Wiring Diagrams
WIRED
CONTROLLER
Model: ACK20/25/30/40/50AW
9 LCD WIRELESS
CONTROLLER
16
THERMISTOR
COIL SENSOR
RED
BROWN (FL)
PURPLE (FH)
ORANGE (FM)
WHITE
B LA C K
RED
RED
RED
BLUE
BLUE
BLACK
BL A C K
PURPLE
GREEN/YELLOW
A.C L.C
LEVEL SWITCH
M.C
FAN MOTOR DRAIN AIR SWING
PUMP MOTOR
GREEN/YELLOW
G R EE N / Y E L LO W
GR E EN /Y EL L O W
VALVE L N
CAUTION !
E 1 PHASE
FIELD SUPPLY WIRING N 220/240VAC 50Hz OR
WITH JUMPER FOR HEAT PUMP L 208/230VAC 60Hz
WITHOUT JUMPER FOR COOLING ONLY
TO 3 WAY
WITH JUMPER FOR VALVE APPLICATION VALVE
WITHOUT JUMPER FOR VALVELESS APPLICATION
G/Y
WIRED
CONTROLLER
LED/IR RECEIVER
Model: ACK20/25/30/40/50AWH
BLUE
BLUE
LEVEL SWITCH
POWER
SUPPLY
AUX.
CONTACT
BLACK
HTR
N
RED
BLACK
PURPLE
WHITE
AIR SWING
RED
G/Y
MOTOR
RED BLACK
G/Y G/Y
BL ACK
WHIT E
RED
ORANGE (FM)
BROWN (FL)
PURPLE (FH)
104
Wiring Diagrams
Model: ACK010/015/020CW
105
Wiring Diagrams
Model: ACK020/025/030/040/050EW
106
107
RETURN AIR SENSOR
Wiring Diagrams
CN_DSP
HEAT VALVE FAN_P CN_STP CN_WIR ROOM C_SEN H_SEN CN_12V
COIL SENSOR
SHED M4
M3 TRANSFORMER
M2
M1
TFULL
LED INDICATOR CN_TW
Model: RCM20/25/30/40/50DW
HTR
N1
IR RCV
UNOCP A_FR2
N2
CN5 LIVE
HI
AS
L
MED
LOW
WTP
CVLV
LCD WIRELESS
CONTROLLER
WIRED
BROWN
CONTROLLER
BLACK
RED
RE D
BLACK
PURPLE
A.C I.C
G R EE N/ Y E L L O W
VALVE L N
M.C
E 1 PHASE FAN MOTOR
N 220/240VAC 50Hz OR
CAUTION !
L 208/230VAC 60Hz
FIELD SUPPLY WIRING TO 3 WAY
WITH JUMPER FOR HEATING VALVE
WITHOUT JUMPER FOR COOLING
WITH JUMPER FOR VALVE APPLICATION
WITHOUT JUMPER FOR VALVE APPLICATION
NOI
TRANSFORMER
Model: ACM15/20/25EW
TFULL
LEVEL SWITCH
N1
HTR
A-FRZ
N2
L
CN5
LIVE
AS
HI
NOI
WTP
LOW
MED
CVLV
.AS. YELLOW FH
BROWN FM
ORANGE FL
RED
BLACK
GREEN
PURPLE
G/Y
BLACK
KEY : M.C
1 PHASE
FAN MOTOR
FIELD SUPPLY WIRING 220/240VAC 50Hz
AS AIRSWING MOTOR
TO 3 WAY VALVE 08 02 4 085929
Wiring Diagrams
108
Wiring Diagrams
109
Wiring Diagrams
110
Wiring Diagrams
111
Wiring Diagrams
112
Wiring Diagrams
Model: ADB75BW
113
Wiring Diagrams
Model: ADB100BW
114
Wiring Diagrams
Model: ADB125/150BW
115
Service & Maintenance
Moving machinery and electrical power hazards. May cause severe personal injury or death.
Disconnect from main power supply before servicing equipment.
The unit is designed to give long life operation with minimum maintenance required. However, it should
be regularly checked and the following items should be given due attention.
Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into the unit when
performing a leakage test or an air tight test. These gases could cause severe explosion and damage if
expose to high temperature and pressure.
116
Troubleshooting
Troubleshooting
Model Board
AWM07/10/15/20/25LW 50WJWXX
AWM301W W2
ACK020/025/030/040/050EW W3
ACK010/015/020CW W2
ACC10/15/20/25/28/30/38/40/50/60CW W2
RCM20/25/30/40/50DW W2
ACM15/20/25EW W2
ADB75/100/125/150BW N/A
Cool mode - -
Green
Heat mode - -
Red
Timer on - -
Sleep mode on - -
Fan mode on - -
Dry mode on - -
Hardware error (tact switch pin short) Call your dealer Blink E8
6 times
ON ON or OFF Blinking
117
Troubleshooting
118
While upmost care is taken in ensuring that all details in the publication are correct at time of going to press, we are constantly striving for
improvement and therefore reserve the rights to alter model specifications and equipment without prior notice. Details of specifications
andequipment are also subject to change to suit local conditions and equirements and not all models are available in every market.