Room Noise Level Test T&C Forms – Air Conditioning System

JKR/CKM/T & C :______________________

CAWANGAN KEJURUTERAAN MEKANIKAL


JABATAN KERJA RAYA

ROOM NOISE TESTING AND COMMISSIONING PROCEDURE

Room Noise Level Test

Noise Level Measurement

Room Served by Noise Noise Measured Results


No. : Require- (Pass /
AHU / ment Fail /
FCU / Comment)
Ventilation (NC) 63 125 250 500 1k 2k 4k 8k NC
Fan Hz Hz Hz Hz Hz Hz Hz Hz

Page 1 of 3
Room Noise Level Test T&C Forms – Air Conditioning System

Noise Level Specifications References

Area N. C. Level Area N. C. Level Range


Range
Lab. / Waiting Area / 30 - 40 Private Wards 25 - 35
Corridor

Area N. C. Level Area N. C. Level Range


Range
Outpatients treatment / 30 – 35 Conference 30 - 40
Casualty Rooms
Operation Theatre 25 - 30 Typing Rooms 55 - 60
Recovery / Anesthetic 25 - 30 General Office 35 - 45
Rooms Room
Sluice / Scrub / 35 - 45 Engineering 60 - 70
Sterilizers Workshop
Toilets / Bathrooms 40 - 50 Kitchen 50 – 60
General / Wards 30 - 35 Outside Main Plant 60 - 70
Room
• Assumed background noise levels range
The sound pressure level in all octave bands measured with all air conditioning plant
running, must not exceed the background noise criteria by 3 dB.
The requirements for other areas not specifically mentioned above shall follow the
nearest room function.

LEGEND:
NC = Noise Control
AHU = Air Handling Unit
FCU = Fan Coil Unit
S /A = Supply air
R/A = Return Air
ACMV = Air Condition and Mechanical Ventilation

Page 2 of 3
Room Noise Level Test T&C Forms – Air Conditioning System

Checked By Contractor: Witness By JKR Representative:

Sign:………………………………….. Sign :…………………………………

Name:………………………………… Name:…………………………………

Date:…………………………………… Date:…………………………………..

Page 3 of 3