Evaporated
water
Cooling box
Strana 1
READ!ME
e temperature at the cooling box for given mass flowrate of motion steam
ion of time course of temperature in the cooling box
Strana 2
COOLING-STEADY STATE
Evaporation cooling 70
STEADY STATE COOLING
Thermocompressor design 60
Q-[kW]
T1= 157.7967 Area of cooling box walls [m ]
2
30
M [kg/s]= 0.01 100 20 Qch
Condenser , cooling water Heat transfer coef. [W.m-2.K-1] Qzt
10
T5[C] 40 30
0
p5[MPa] 0.007351 Antoine equation lnp=A-B/(C+T) is used 20 22 24 26 28
T-suction [C]
Evaporated water (the compressor suction) Kappa= 1.13 0.115044248
T2[C] p2[MPa] Pe=p1/p2 Pk=p5/p2 fe=Me/Mp fm=Mp/Me Me[kg/s] Qchl[kW]
30 0.00422 147 1.74 1.86 0.54 0.018609 44.662
29 0.00398 156 1.85 1.74 0.58 0.017386 41.727
28 0.00375 165 1.96 1.63 0.61 0.016324 39.178
27 0.00354 175 2.08 1.54 0.65 0.015390 36.937
26 0.00333 186 2.21 1.46 0.69 0.014562 34.949
25 0.00314 197 2.34 1.38 0.72 0.013821 33.171
24 0.00296 210 2.49 1.32 0.76 0.013153 31.568
23 0.00278 223 2.64 1.25 0.80 0.012548 30.114
22 0.00262 237 2.81 1.20 0.83 0.011995 28.789
21 0.00246 252 2.99 1.15 0.87 0.011489 27.574
20 0.00231 268 3.18 1.10 0.91 0.011024 26.457
19 0.00217 286 3.39 1.06 0.94 0.010593 25.423
18 0.00204 304 3.61 1.02 0.98 0.010194 24.465
17 0.00191 324 3.85 0.98 1.02 0.009822 23.574
16 0.00179 346 4.10 0.95 1.06 0.009476 22.742
15 0.00168 369 4.38 0.92 1.09 0.009151 21.963
14 0.00157 394 4.67 0.88 1.13 0.008847 21.233
Strana 3
COOLING-STEADY STATE
70
STEADY STATE COOLING
60
50
40
30
20 Qchl[kW]
Qztraty[kW]
10
0
20 22 24 26 28 30 32
T-suction [C]
Qztraty[kW]
30
33
36
39
42
45
48
51
54
57
60
63
66
69
72
75
78
Strana 4
TRANSIENT
T [C]
Condenser , cooling water Heat transfer coef. [W.m .K ]
-2 -1 15
10
T5[C]= 40 5
5
p5[MPa] 0.007351 Antoine equation lnp=A-B/(C+T) is used
0
Evaporated water (the compressor suction) Kappa= 1.13 0.115044247787610
t [s]
500 1000 1500 2000 2500
Assuming, that the largest mass of water is in the evaporator tank, the analysis of transient start-up or shut-down
M.cp.dT/dt = - Me.r+S.k.(Te-T), where Me is the mass flowrate of evaporated water and r(T) is the latent heat of
This is a ordinary differential equation which must be evaluated numerically if the heat of evaporation is not a co
Nevertheless it will be interesting to compare the numerically obtained results with the analytical solution for r=c
Its your bussines to find out the analytical solution. The numerical solution in the column A is explicit
Time step of numerical integratio 100 [s]
T2[C] p2[MPa] Pe=p1/p2 Pk=p5/p2 fe=Me/Mp r[kJ/kg] Me[kg/s] Qcool[kW]
30 0.00422 147 1.74 1.86 2459 0.018609 45.760
20.30 0.00235 263 3.12 1.12 2485 0.011157 27.727
16.04 0.00180 345 4.09 0.95 2496 0.009489 23.689
13.25 0.00150 414 4.91 0.86 2504 0.008631 21.611
11.29 0.00131 472 5.60 0.81 2509 0.008109 20.346
9.86 0.00119 520 6.16 0.78 2513 0.007764 19.509
8.81 0.00111 559 6.62 0.75 2515 0.007525 18.928
8.01 0.00105 590 7.00 0.74 2518 0.007354 18.513
7.41 0.00101 615 7.29 0.72 2519 0.007229 18.210
6.96 0.00098 635 7.53 0.71 2520 0.007136 17.986
6.61 0.00095 651 7.71 0.71 2521 0.007067 17.817
6.34 0.00094 663 7.86 0.70 2522 0.007015 17.690
6.14 0.00092 673 7.97 0.70 2522 0.006975 17.594
5.98 0.00091 680 8.06 0.69 2523 0.006945 17.521
5.86 0.00090 686 8.13 0.69 2523 0.006922 17.464
5.76 0.00090 690 8.19 0.69 2523 0.006904 17.421
5.69 0.00089 694 8.23 0.69 2524 0.006890 17.388
5.64 0.00089 697 8.26 0.69 2524 0.006880 17.363
5.59 0.00089 699 8.29 0.69 2524 0.006872 17.343
5.56 0.00089 700 8.30 0.69 2524 0.006865 17.328
5.53 0.00088 702 8.32 0.69 2524 0.006861 17.316
5.51 0.00088 703 8.33 0.69 2524 0.006857 17.307
5.50 0.00088 703 8.34 0.69 2524 0.006854 17.300
Strana 5
TRANSIENT
Strana 6
TRANSIENT
cp[J/kg/K]=4.2
T 50
ART UP - COOLING
45
Q [kW]
40
35
30 Q [kW]
25
20
15
10
5
0
t [s]
0 1000 1500 2000 2500 3000 3500
nt start-up or shut-down can be restricted to the heat balance of evaporator
r(T) is the latent heat of water
of evaporation is not a constant
nalytical solution for r=const.
umn A is explicit. Rewrite it to the more precise implicit form.
Strana 7
TRANSIENT
Strana 8
GRAPHS
70
STEADY STATE COOLING
60 Qchl[kW]
Qztraty[kW]
50
40
Q-[kW]
30
20
10
0
20 22 24 26 28 30 32
T-suction [C]
35 50
START UP - COOLING 45
30
40
25 T
35
Q [kW]
30
20
Q [kW]
25
T [C]
15
20
10 15
10
5
5
0 0
0 500 1000 1500 2000 2500 3000 3500
t [s]
Strana 9