Equipment: Hilti-PS200 S – Ferro scanner.


Page |2

SCANNING REPORT PREPARED BY:

Access Engineering Solution


House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.
Email:aesolutionbd@gmail.com,Hotline-01764-958939.

DATE:
Inspection Date : March 13, 2019
Submission Date : March 14, 2019

Test Performed by:


Engr. Md. Afzal Hossen
B.Sc.in Civil Engineering

Supervised by:
Engr. Md. Abu Baker
B.Sc.in Engineering
MIEB: F-5097

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
Page |3

LETTER OF DECLARATION

We do hereby declare that this report is prepared based on the scanning data from
different location in the structure as suggested by the engineer/consultant using Hilti
PS 200 under the guidance and supervision of us. We will be responsible for
rationality and verification of any data presented in this report based on scanning
only. While scanning and analyzing, civil engineering knowledge and judgment was
applied where necessary.

This report is prepared based on image scan and quick scan only.

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
Page |4

Details of Image Scan Test Report

Sl. Nature of Remark


Grid no/Location Reinforcement details
No Structure (if any)

01 Scan-01 (C1) Column Face-1 2-22mm dia bar


Grid no. D/9 (20ʺx10ʺ) +
Ground Floor 4-20mm dia bar Middle Point
Face-2 2-22mm dia bar
+
1-20mm dia bar
Tie/Ring: 10 mm dia @ 7ʺ C/C

Face-1 Face-2

Along 20’’ Along 10”

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
Page |5

Details of Image Scan Test Report

Sl. Nature of Remark


Grid no/Location Reinforcement details
No Structure (if any)

02 Scan-02 (C2) Column Face-1 8-20mm dia bar


Grid no. C/9 (24ʺx10ʺ)
Ground Floor Face-2 3-20mm dia bar Middle Point

Tie/Ring: 10 mm dia @ 7ʺ C/C

Face-1 Face-2

Along 24’’ Along 10’’

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
Page |6

Details of Image Scan Test Report

Sl. Nature of Remark


Grid no/Location Reinforcement details
No Structure (if any)

03 Scan-03 (C3) Column Face-1 7-20mm dia bar


Grid no. K/7 (20ʺx15ʺ)
Ground Floor Face-2 4-20mm dia bar Middle Point

Tie/Ring: 10 mm dia @ 7ʺ C/C

Face-1 Face-2

Along 20’’ Along 15’’

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
Page |7

Details of Image Scan Test Report

Sl. Nature of Remark


Grid no/Location Reinforcement details
No Structure (if any)

04 Scan-04 (C4) Column Face-1 5-22mm dia bar


Grid no. K/6 (22ʺx18ʺ) +
Ground Floor 2-20mm dia bar Middle Point
Face-2 3-22mm dia bar
+
2-20mm dia bar
Tie/Ring: 10 mm dia @ 7ʺ C/C

Face-1 Face-2

Along 22’’ Along 18’’

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
Page |8

Details of Image Scan Test Report

Sl. Nature of Remark


Grid no/Location Reinforcement details
No Structure (if any)

05 Scan-05 (C5) Column Face-1 8-22mm dia bar


Grid no. H/6 (22ʺx22ʺ)
Ground Floor Face-2 7-22mm dia bar Middle Point

Tie/Ring: 10 mm dia @ 8ʺ C/C

Face-1 Face-2

Along 22’’ Along 22’’

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
Page |9

Details of Image Scan Test Report

Sl. Nature of Reinforcement details


Grid no/Location Sl. No
No Structure
06 Scan-06 (C6) Column Face-1 8-20mm dia bar
Grid no. I/5 (22”x22ʺ)
Ground Floor Face-2 Not available Middle Point

Tie/Ring: 10 mm dia @ 7ʺ C/C

Face-1 Face-2

Not available

Along 22’’ Along 22”

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
P a g e | 10

Details of Image Scan Test Report

Sl. Nature of Remark


Grid no/Location Reinforcement details
No Structure (if any)

07 Scan-07 (C1) Column Face-1 4-20mm dia bar


Grid no. J/4 (20ʺx20ʺ)
Ground Floor Face-2 4-20mm dia bar Middle Point

Tie/Ring: 10 mm dia @ 7ʺ C/C

Face-1 Face-2

Along 20’’ Along 20’’

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
P a g e | 11

Details of Image Scan Test Report

Sl. Nature of Remark


Grid no/Location Reinforcement details
No Structure (if any)

08 Scan-08 (C4) Column Face-1 4-20mm dia bar


Grid no. G/1 (22ʺx22ʺ) +
4th Floor 3-16mm dia bar Middle Point
Face-2 3-20mm dia bar
+
2-16mm dia bar
Tie/Ring: 10 mm dia @ 7ʺ C/C

Face-1 Face-2

Along 22’’ Along 22”

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
P a g e | 12

Details of Image Scan Test Report

Sl. Nature of Remark


Grid no/Location Reinforcement details
No Structure (if any)

09 Scan-09 (C5) Column Face-1 4-20mm dia bar


Grid no. G/6 (22ʺx22ʺ) +
4th Floor 3-16mm dia bar Middle Point
Face-2 3-20mm dia bar
+
4-16mm dia bar
Tie/Ring: 10 mm dia @ 7ʺ C/C

Face-1 Face-2

Along 22’’ Along 22”

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
P a g e | 13

Details of Image Scan Test Report

Sl. Nature of Remark


Grid no/Location Reinforcement details
No Structure (if any)

10 Scan-10 (C5) Column Face-1 4-20mm dia bar


Grid no. H/6 (22ʺx22ʺ) +
6th Floor 2-16mm dia bar Middle Point
Face-2 3-20mm dia bar
+
3-16mm dia bar
Tie/Ring: 10 mm dia @ 7ʺ C/C

Face-1 Face-2

Along 22’’ Along 22’’

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
P a g e | 14

Details of Image Scan Test Report

Sl. Nature of Remark


Grid no/Location Reinforcement details
No Structure (if any)

11 Scan-11 (C6) Column Face-1 6-20mm dia bar


Grid no. I/6 (24ʺx24ʺ)
6th Floor Face-2 5-20mm dia bar Middle Point

Tie/Ring: 10 mm dia @ 7ʺ C/C

Face-1 Face-2

Along 24’’ Along 24’’

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
P a g e | 15

Details of Image Scan Test Report

Sl. Nature of Remark


Grid no/Location Reinforcement details
No Structure (if any)

12 Scan-02 (C3x) Column Face-1 4-20mm dia bar 18” has taken
Grid no. I/2 (30ʺx12ʺ) due to brick wall
Ground Floor Face-2 Not available

Tie/Ring: 10 mm dia @ 7ʺ C/C

Face-1 Face-2

Not available

Along 30’’ Along 12’’

House#12, Road#19, Block#C, Mirpur-12, Dhaka-1216.


Email:aesolutionbd@gmail.com Hotline-01764-958939
P a g e | 16

Note:

1) This is a test result only. Not a safety report.


2) Rebar dia & No. of rebar may vary from due to excessive clear cover.
3) Interference in images may occur due to
a) When the surface is rough
b) Scraps of reinforcement in the concrete
c) Aggregates with ferromagnetic properties
d) Ends of bars lying parallel to the scanning plate
e) Ends of bars lying at right angles to the scanning plane (standing
bars)
4) The dimensions found at the site may differ from the actual drawing
.dimensions. We only include the dimension found from the site.
Limitation:

* Machine range is from1mm-150mm.