You are on page 1of 2

TBR

FEATURES
Epoxy resin bushings for oil transformers with plug-in cable
connection in compliance with EN 50180.
All versions include: plastic cap on cable connection, fixing
hardware for lower connection, screen earthing plaque
with its screw.
Earthing cable is available as an alternative to the plaque.
On request is also available the fixing system in compliance
with EN 50180-2/3:
ü Aluminium flange
ü NBR gasket
ü Stainless steel washers
ü Stainless steel nuts

REFERENCE STANDARDS
IEC 60137, EN 50180

ROUTINE TESTS TESTS ON DEMAND


• Visual and dimensional check • Dry lighting impulse
• Glass transition temperature voltage
• Dry power frequency withstand • Bending stress
• Partial discharges • High temperature test
frequency
withstand

withstand
operating

Lightning
EN 50180
Interface
Drawing

Nominal
impulse
voltage

voltage

voltage

current
Power
Name

Max.

TBR
92420 B2 400 A
36/400
36 kV 170 kV 77 kV
TBR
92430 C1 630 A
36/630

www.venetaisolatori.it info@venetaisolatori.it
TBR

Interface Connect. N° fastening Weight


Name Drawing A B C D E F G H
EN 50180 type tabs (kg)

TBR Sliding
92420 B2 330.5 41.5 147 10 132 M16 Ø128 Ø87 4 2.7
36/400 PIN Ø14

TBR Bolted
92430 C1 332 41.5 147 10 133.5 M16 Ø128 Ø87 --- 2.9
36/630 M16

ASSEMBLY INSTRUCTIONS
1. Place the bushing on the top of the transformers tank using its NBR gasket.
2. At least one of the three screen outlets should be connected to the earth with the plaque or earthing cable.
3. Use the fixing hardware to secure the bushing to the tank with a torque force of 10÷15 Nm

EN 50180 Cable termination


4. Remove the safety cap
5. Clean the connection area
6. Smoothly cover the connection cone with silicone grease supplied with the cable termination
7. Connect the cable termination making sure that it abut against the insulator.
8. Be sure that all the safety features are correctly connected to the insulator.

BE AWARE OF:
ü Do not paint or damage the cable connection.
ü Cover the bushing with its safety cap when it is not connected to the cable termination

CT124 rev.0 del 01/06/2018

www.venetaisolatori.it info@venetaisolatori.it

You might also like