FEATURES
Epoxy resin bushings for oil transformers with plug-in cable
connection in compliance with EN 50180.
All versions include: plastic cap on cable connection, fixing
hardware for lower connection, screen earthing plaque
with its screw.
Earthing cable is available as an alternative to the plaque.
On request is also available the fixing system in compliance
with EN 50180-2/3:
ü Aluminium flange
ü NBR gasket
ü Stainless steel washers
ü Stainless steel nuts
REFERENCE STANDARDS
IEC 60137, EN 50180
withstand
operating
Lightning
EN 50180
Interface
Drawing
Nominal
impulse
voltage
voltage
voltage
current
Power
Name
Max.
TBR
92420 B2 400 A
36/400
36 kV 170 kV 77 kV
TBR
92430 C1 630 A
36/630
www.venetaisolatori.it info@venetaisolatori.it
TBR
TBR Sliding
92420 B2 330.5 41.5 147 10 132 M16 Ø128 Ø87 4 2.7
36/400 PIN Ø14
TBR Bolted
92430 C1 332 41.5 147 10 133.5 M16 Ø128 Ø87 --- 2.9
36/630 M16
ASSEMBLY INSTRUCTIONS
1. Place the bushing on the top of the transformers tank using its NBR gasket.
2. At least one of the three screen outlets should be connected to the earth with the plaque or earthing cable.
3. Use the fixing hardware to secure the bushing to the tank with a torque force of 10÷15 Nm
BE AWARE OF:
ü Do not paint or damage the cable connection.
ü Cover the bushing with its safety cap when it is not connected to the cable termination
www.venetaisolatori.it info@venetaisolatori.it