Professional Documents
Culture Documents
Abstract. The growth of cities towards their suburban areas has led
to the construction of buildings increasingly closer to high voltage lines,
which has led to detailed studies of the electric and magnetic fields gener-
ated by these lines, and to determine the potential impact on the health
of people within their area of influence.
In this work, a 220 kV transmission line was studied in the City of
Cartagena de Indias. In order to analyze the system, it was necessary
to review the norm and measurement methodologies of national and in-
ternational organizations, which allowed, in a structured way, to take
reliable measurements in the work area. At the same time, references
and similar studies were investigated to compare the measured and cal-
culated results, and to determine more accurate conclusions about the
electromagnetic phenomena and the effects of these on the health of peo-
ple.
A computer application was developed to facilitate analysis and cal-
culation, given the various variables used. This allowed comparing the
measured data with the data obtained through the software developed,
to obtain more precise results and conclusions.
1 Introduction
The construction and location of new lines of transmission of energy produces
a rejection in the affected communities due to the preoccupation that exists on
the possible effects in the health that can produce the electromagnetic fields
of industrial frequency. Several international organizations have established the
limits of exposure to electromagnetic fields in work and public places. Among
these organizations are the International Commission on Protection against Non-
Ionizing Radiation (ICNIRP) [1] and the Institute of Electrical and Electronic
Engineers (IEEE) [2] that have set a limit of exposure to the electric field of 5
kV/m and a limit of exposure to the magnetic field 100 µT for the general public
?
Supported by UTB.
2 Rueda L.E. et al.
The equipment used was Aronia Spectran NF 5035. This equipment records
the magnetic field in µT and the electric field strengths in V/m. Figure 1 shows
the 220kV transmission line used in the study
For the measurement of the electric field, the procedure described in IEEE
644 -1994 [2] standard was carried out, as follows:
Computation of Electromagnetic fields for 220 kV Power line 3
xp − xr
Cosθ2 = (12)
R0
h − yp
Sinθ1 = (13)
R
h + yp
Sinθ2 = (14)
R0
For N conductors the electric field is:
N
qi X (x − xi ) (x − xi )
Ex = − (15)
2π0 i=1 (xi − x)2 + (yi − y)2 (xi − x)2 + (yi + y)2
N
−qi X (yi − y) (yi + y)
Ey = − (16)
2π0 i=1 (xi − x)2 + (yi − y)2 (xi − x)2 + (yi + y)2
The total electric field is:
q
E= Ex 2 + Ey 2 (17)
6 Rueda L.E. et al.
The low frequency magnetic field in a power line depends on the electrical
currents in its conductors [8] - [14]. Generally, if the currents are known, the
magnetic field can be calculated with Ampere’s law, assuming that the con-
ductors are infinite and that the magnetic permeability of the air is equal to
µ0 = 4π ∗ 10−7 [H/m]. The superposition principle will be applied to take into
account the influence of multiple conductors.
For an infinite conductor carrying a current I, the magnetic flux density B,
according to the Ampere Law, is:
µ0 I
B= (18)
2πR
The figure 4 shows the distance from the conductor at (xi , yi ) to point (xp , yp ):
Fig. 4. Lateral profile of the electric field form the 220 kV power line.
q
R= (xp − xi )2 + (yp − yi )2 (19)
µ0 I
B= p (20)
2π (xp − xi )2 + (yp − yi )2
µ0 I0 Sinθ
Bx = − p (21)
2π (xp − xi )2 + (yp − yi )2
Computation of Electromagnetic fields for 220 kV Power line 7
µ0 I0 Cosθ
By = − p (22)
2π (xp − xi )2 + (yp − yi )2
Where:
yp − yi
Sinθ = p (23)
(xp − xi )2 + (yp − yi )2
xp − xi
Cosθ = p (24)
(xp − xi )2 + (yp − yi )2
For N conductors the magnetic field is:
N
µ0 I0 X (yp − yi )
Bx = − (25)
2π i=1 (xp − xi )2 + (yp − yi )2
N
µ0 I0 X (xp − xi )
By = − (26)
2π i=1 (xp − xi )2 + (yp − yi )2
Finally, the magnetic flux density will be calculated using the formula:
q
B = Bx 2 + By 2 (27)
3 Results
data for the program are the coordinates of each conductor, the diameter of the
conductor, the phase voltages, the currents of each conductor and the height
above ground level. The input data of the position of the conductors in the line
is obtained from the structure of the pylon as shown in figure 6.
Fig. 6. Lateral profile of the electric field form the 220 kV power line
The program can generate quite accurate profiles for the total field, E and
B. The precision of the results has been verified taking into account a series
of calculations published in [5], [9], [12], and introducing these data into the
program. The results obtained by direct measurement were also compared in
the 220kV power line of the Bolivar-Bosque circuit in the city of Cartagena de
Indias.
Figure 7 shows the profile of the electric field obtained at a height of 1m
according to the IEEE standard 644-1994. The measured data show a tendency
to continue the profile of the calculated electric field.
As seen in the experimental results shown in Table 1, the electric field
strength measured at the center of the 220 kV line is 2,238 kV/m and the calcu-
lated one is 2,120 kV/m, which results in an error of 5.27% Figure 8 shows the
profile of the magnetic field obtained at a height of 1m according to the IEEE
standard 644-1994. The measured data show a tendency to continue the profile
of the calculated magnetic field. As seen in the experimental results shown in
Computation of Electromagnetic fields for 220 kV Power line 9
Fig. 7. Lateral profile of the electric field form the 220 kV power line
Table 1. Electric field measured and calculated at 1 m height from the ground
Electric field
Distance to Measured Calculated Error [%]
the center [m] [kV/m] [kV/m]
-25 0.038 0.029 23.68
-20 0.223 0.172 22.86
-15 0.620 0.507 18.22
-10 1.043 1.124 7.76
-5 1.75 1.807 3.28
0 2.238 2.120 5.27
5 1.980 1.834 7.3
10 1.203 1.124 6.56
15 0.587 0.508 13.4
20 0.132 0.151 12,5
25 0.034 0.029 14,7
10 Rueda L.E. et al.
Fig. 8. Lateral profile of the magnetic field form the 220 kV power line
Table 2, the magnetic flux density measured at the center of the 220 kV line is
2.305 mu T and the calculated one is 2.229 mu T, which results in an error of
0.65%
4 Conclusions
Based on the regulations concerning the 220kV lines, a work guide was de-
signed for the measurement of the electromagnetic field with specialized equip-
ment for this purpose.
A procedure based on the IEEE-Std 644-1994 standard was developed for the
measurement of electric and magnetic fields generated by 220kV high voltage
transmission lines that are supported by structures with double vertical electric
circuit and with double cable of guard, at a maximum height of 25 meters and
a stretch of 2 km long, bordering a saltwater marsh in the suburbs of the city of
Cartagena de India, located in the Caribbean zone of Colombia.
The 220kV transmission system was modeled, based on the documentation,
regulations and experience of the researchers in order to design and implement
an application supported on the MATLAB platform, to calculate the electric and
magnetic fields in various space points according to the required configuration.
The measured data were compared with the results of the program and an
admissible margin of error was obtained with very little dispersion. The average
errors for the electric field and the magnetic field were 6 and 2.76 per cent
respectively. The measurements taken at points far from the axis of the structure,
due to changes in the profile of the terrain, and in the presence of natural and
artificial obstacles, the electric and magnetic field yielded data with distortions
that altered the map of equipotential curves.
The levels obtained from Electric Field and Magnetic Field do not show risk
to human health in the area under study, complying with the regulations of the
International Commission on Non-Ionizing Radiation Protection, ICNIRP and
RETIE.
It is expected that the methodology implemented will serve researchers in the
area, as a basis in subsequent studies applicable to a high voltage transmission
line with a specific configuration.
References
1. International Commission on Non Ionizing Radiation Protection, ”Guidelines for
limiting exposure to time-varying electric, magnetic and electromagnetic fields (1
Hz to 100 kHz)”, Health Physics 99( 6),2010,818-836.
2. IEEE Standard Procedures for Measurement of Power Frequency Electric and Mag-
netic Fields From AC Power Lines,Std. 644-1994.
3. RETIE Reglamento Tcnico de Instalaciones Elctricas (Colombia)
4. Xiao, Lei E. Holbert, Keith. (2014). Development of software for calculating elec-
tromagnetic fields near power lines. 2014 North American Power Symposium, NAPS
2014. 1-6. 10.1109/NAPS.2014.6965378.
5. Sahbudin, R.K.Z. S.A, Fauzi Hitam, Salasiah Mokhtar, Mohsen. (2010).
Investigation of Electrical Potential and Electromagnetic Field for Overhead
High Voltage Power Lines in Malaysia. Journal of Applied Sciences. 10.
10.3923/jas.2010.2862.2868.
6. Himadri, D. . Implementation of Basic Charge Configurations to Charge Simulation
Method for Electric Field Calculations. vol. 3, no.5, pp. 9607-9611 (2014)
12 Rueda L.E. et al.