Tawe 070 003 - C71
Tawe 070 003 - C71
Contents
7-1
7.1 Troubleshooting
7.1 Troubleshooting
Troubles concerning integrated weld control bus connection may occur when power is turned on and
when weld is going on, and are related to to DPR communication and welder system software.
(2) In case that welder version differs from that used previously, data between weld
sequences and linear auto stepper and welder parameters may be different. If it is
different, a warning message "W1141 Welder version is unmatched." is issued.
Initialize welder data. (Ref: Chapter 3, 3.12)
(2) If welder’s isolation contact is closed and does not open, an error message "E0760
Isolation contact stuck close." is displayed. Confirm the welder’s isolation contact.
7-2
7 Troubleshooting
7.1 Troubleshooting
(3) If welder’s SCR1 has an abnormal temperature, an error message "E0749 Spot
Welder SCR1 thermal switch actuated." is displayed. Please refer to the welder’s
manual.
(4) If SCR2 of ext. input signals has an abnormal temperature, an error message "E0750
Spot Welder SCR2 thermal switch actuated." is displayed. Please refer to the welder’s
manual.
(5) If error occurred in welder when welding was executed, an warning message "W1142
Welder error occurred." is displayed. This abnormality is displayed as FAULT or
ALERT error according to the setting described in Chapter 3, 3.9 [Welder parameter].
Please refer to Chapter 6, 6.1 [3] [Weld result monitor] or 6.1 [4] [Welder I/F monitor]
for its detail and remove the abnormality.
(1) If not connected to welder timer, an error message "E0674 Welder communication
fault (No reply)." is displayed. Upload the weld data. Replace the welder timer if the
error is repeated. (Ref: Chapter 3, 3.13)
(2) If communication data received from welder timer is abnormal, error message "E0675
Welder communication fault (Check sum)." or "E0676 Welder communication fault
(Message wrong)." is displayed. Turn on power again. Replace the welder timer if the
error is repeated.
(3) If there exists checksum error of welder timer, the following error messages are
displayed:
"E0694 Executive EPROM checksum error."
"E0695 LCA EPROM checksum error."
"E0696 Application EPROM checksum error."
"E0697 DPR error."
Install system software again when these errors occurred.
7-3
7 Troubleshooting
7.1 Troubleshooting
(4) If software version of welder timer is old, error message "E0757 Weld control is not
supported by weld control network command." is displayed. When this error occurred,
install the system software again.
7-4
7 Troubleshooting