THE NATIONAL

BUILDING CODE
(CONDO)
DE GUZMAN, SUSHMITA SEN
C. GUERRIN, GLADYS ANNE
MEJIA, ELAND JETHRO
PUZON, DANE STEFI MARIE P.
SANTOS, KITT
TEMPLO, CHARMAINE Y.
CLASSIFICATION AND GENERAL
REQUIREMENTS OF ALL BUILDINGS
BY USE OR OCCUPANCY
USE OR UNIT AREA PER Minimum of Two
OCCUPANCY OCCUPANT Exits other than
(Sq. m.) elevators are
required where
A. Dwellings 28 number of10occupant
B. Hotels 18.6 10
Apartments 18.6 10
Dormitories 18.6 10

National Building Code of the Philippines


• Section 701 OCCUPANCY TYPE
GROUP A RESIDENTIAL DWELLINGS
GROUP B
RESIDENTIAL
, HOTEL, AND
APARTMENTS

• Section 702

No change shall be made in the character of occupancy of any


building.

• Section 703

One-storey building with more than one occupancy each portion


shall conform to the requirement of each.
TYPES OF OCCUPANCY
SEPARATION
1.) One – Hour Fire Resistive
Operation

2.) Two – Hour Fire resistive


Operation

3.) Three – Hour Fire Resistive


Operation

4.) Four – Hour Fire Resistive


Operation

http://continuingeducation.construction.com/article.php
LOCATION ON PROPERTY
No buildings shall be constructed unless it adjoins a street

National Building Code of the Philippines


LOCATION ON PROPERTY
LOCATION ON PROPERTY
LOCATION ON PROPERTY
MAXIMUM HEIGHT OF
BUILDINGS
MAXIMUM HEIGHT OF
BUILDINGS
MEASUREMENT AND
PERCENTAGE OF SITE
OCCUPANCY
MEASUREMENT AND
PERCENTAGE OF SITE
OCCUPANCY

National Building Code of the Philippines


MEASUREMENT AND
PERCENTAGE OF SITE
OCCUPANCY

National Building Code of the Philippines


SETBACK REQUIREMENT

Type of Residential Use / Occupancy


YARD R-1 R-2 R-3 R-4 R-5
(meters) Basic Maximum Basic Maximum (individ (meters)
(meters) (meters) (meters) (meters) ual lot /
unit
Front 4.50 3.00 8.00* 3.00 8.00* meters)
4.50 6.00
Side 2.00 2.00** 2.00** *** 2.00 2.00 3.00
(optional) (optional)
Rear 2.00 2.00 2.00 *** 2.00 2.00 3.00

National Building Code of the Philippines


PARKING REQUIREMENT

• 3.60m * 12.00m – bus/tracks


PARKING REQUIREMENT
PARKING REQUIREMENT

1.20 M
3.70 M
ELEVATOR

10.1 ACCESSIBLE ELEVATOR SHOULD


BE LOCATED NOT MORE THAN
30.00 M FROM THE
ENTRANCEAND SHOULD BE
EASY TO LOCATE WITH THE AID
OF SIGNS

10.2 ACCESSIBLE ELEVATORS


SHALL HAVE A MINIMUM
DIMENSION OF 1.10 M. x 1.4 M.

National Building Code of the Philippines


CEILING HEIGHTS

Min. 2.10 m
Min. 2.40 m

Min. 2.40 m

Min. 2.70m
National Building Code of the Philippines
CEILING HEIGHTS
1st Floor w/ Natural
Ventilation
Min. 2.70 m

MEZZANINE FLOORS

Min. 1.80 m.

Stairways 1

National Building Code of the Philippines


SIZE AND DIMENSIONS
OF ROOMS
Min. Area = 1.20 sq. m
0.90 m

National Building Code of the Philippines


PWD BATHROOM

30 M
KITCHEN
WINDOW OPENING

10 % FLOOR AREA
ARCADE

MIN. 3.00 M
ARCADE
BUILDING PROJECTION
OVER PUBLIC STREETS
CORRIDORS
3.4 A MINIMUM CLEAR LEVEL
SPACE OF 1.50 M X 1.50 M
SHALL BE PROVIDED BEFORE
EXTENDING BEYOND A DOOR;

EXCEPTION: WHERE A DOOR


SHALL OPEN ONTO BUT NOT
INTO A CORRIDOR, THE
REQUIRED CLEAR, LEVEL
SPACE ON THE CORRIDOR
SIDE OF THE DOOR MAY BE A
MINIMUM OF 1.20M
CORRIDOR WIDTH

3.5) PROTECTION SHOULD BE


PROVIDED FROM DOORS THAT
SWING INTO CORRIDORS
RAMPS

1:12 RATIO
National Building Code of the Philippines
STAIRWAYS

A B

National Building Code of the Philippines


STAIR LANDING

max.
3.60 m
Min. 2.00
m

Max. 1.20 m
HAND RAIL

3m
3m

0.80 m < x > 0.90 m


EXITS
Total Width of Exits > total occupant load served / 165
OCCUPANT LOAD NO. OF EXITS

Above first storey 2


More than 10
500-999 3

1000 or more 4

Occupant load of more


than 10

EXIT 1 EXIT 2

National Building Code of the Philippines


Exit 1 Exit 2
500 – 999 Occupant Load

EXIT DISTANCES
National Building Code of the Philipp
< 1/5

EXIT

EXIT
National Building Code of the Philipp
10.7 lux

MIN OF 1.10 M

National Building Code of the Philipp


MIN OF 2 M

Hazardous Areas/ 50 or
more load

DOOR EXIT
NATIONAL BUILDING CODE
OF THE PHILIPPINES
(Mall)

DE GUZMAN, SUSHMITA SEN C.


GUERRIN, GLADYS ANNE
MEJIA, ELAND JETHRO
PUZON, DANE STEFI MARIE P.
SANTOS, KEITH L.
TEMPLO, CHARMAINE Y.
Building Occupancy
• Group E:
▫ Business & Mercantile

National Building Code of the Philippine


PARKING REQUIREMENTS
Building Type Number of parking slot
1 slot/150 sq.m. of shopping floor
Markets
area
Restaurants, Fast-food centers,
1 slot/30 sq.m. of customer area
bars and beerhouses
Office buildings 1 slot/125 sq.m. of gross floor area
Other buildings in business/
1 slot/125 sq.m. of gross floor area
commercial zones
Public assembly buildings
(theaters, cinemas, auditorium, 1 slot/50 sq.m. of spectators area
stadium, etc.)
Building Type (Recreational Number of parking slot
Facilities)

Bowling Alleys 1 slot/4 alleys

Amusement center 1 slot/50 sq.m. of gross floor area


PERPENDICULAR PARKING

PARALLEL PARKING 5.00m

2.40m

2.00m
6.00m

12.00m

5.00m
2.40m
3.60m

Truck and Bus


Diagonal Parking
PARKING FOR PWD
 1 accessible parking slot for the handicapped per 50 parking lots up to 150
slots and an additional slot for every 100 slots
 Maximum distance of accessible parking area from facility served. Parking
areas for the physically handicapped shall be within 60.00m of the facility
being served.

FACILITY SERVED

WALKWAY

PARKING PARKING PARKING PARKING PARKING


SLOT SLOT SLOT SLOT SLOT
ONE WAY3.00m
TWO WAY
7.20m
13.50m
90 DEG. PARKING BAY
ONE SIDE
5.70m
Planning and Designers Handbook (Second Edition)
Max B. Fajardo Jr.
2.55m to 2.70m
ONE WAY 19.00m to TWO WAY
3.00m 19.50m
7.20m

5.70m

2.55m to 2.70m

90 DEG. PARKING
BAY TWO SIDES
D A B C X Y Z
90 18.60 5.70 7.20 18.60 5.70 7.20
60 18.00 6.30 5.40 16.65 5.65 5.40
anning 45 15.80
and Designers 5.80
Handbook (Second3.90
Edition) 13.85 4.97 3.90
Pl Max B. Fajardo Jr.
R = 17.00m
to 21.00m

UP

4.00m to DN
4.50m

4.00m to
4.50m

Planning and Designers Handbook (Second Edition)


Max B. Fajardo Jr.
Bus

17.60m

2.10m
7.60m
3.00m
2.70m
Section 1207. Stairs, Exits, and Occupant Loads

C – 1: Exit Door shall swing in the direction of travel.


Double Acting Doors shall not be used as exits.

NATIONAL BUILDING CODE OF THE PHILIPINES


Section 1207. Stairs, Exits, and Occupant
Loads
• C-3: Exit doorway shall be of a size as to permit the
installation of a door not less than 900mm and not
less than 2.00m in height

NATIONAL BUILDING CODE OF THE PHILIPINES


Section 1207. Stairs, Exits, and Occupant
Loads
• C-5: Revolving, sliding, and overhead doors shall
not be used as required exits.
Section 1207. Stairs, Exits, and Occupant
Loads
• D-1: Every corridor or exit balcony shall not be
less than 1.10 meters in width

NATIONAL BUILDING CODE OF THE PHILIPINES


Section 1207. Stairs, Exits, and Occupant
Loads
• D-3: When more than one exit is required, they shall
be arranged to allow going to either direction from
any point in the corridor.
Section 1207. Stairs, Exits, and Occupant
Loads
• Corridors and exterior exit balconies with dead ends
are permitted when the dead end does not exceed
6.00 meters in length

NATIONAL BUILDING CODE OF THE PHILI


Section 1207. Stairs, Exits, and Occupant
Loads
• E-1: Stairway widths
• Occupant Load (X) = Minimum Width
X > 50 = 1100MM
X < 50 = 900MM
X < 10 = 750MM
Trim and handrails shall not reduce the required width by
more than 100MM
Section 1207. Stairs, Exits, and Occupant
Loads
• E-3: Winding stairways may be used if the required
width of the run is provided at a point not more than
300MM from the side where the treads are
narrower.

NATIONAL BUILDING CODE OF THE PHILI


Section 1207. Stairs, Exits, and Occupant
Loads
• E-5: Every landing shall be a dimension measured in
the direction of travel equal to the width of the stairway.
Such dimension need not exceed 1.20m when the stairs
has a straight run.

NATIONAL BUILDING CODE OF THE PHILI


Section 1207. Stairs, Exits, and Occupant
Loads
• K: Exits shall be illuminated at any time the
building is occupied.

NATIONAL BUILDING CODE OF THE PHILI