Professional Documents
Culture Documents
CHAPTER 4
MIX DESIGN PROCEDURES AND TEST RESULTS OF
SELF-COMPACTING CONCRETE (SCC)
4.1. General
The strengths of SCC are tested by making four different concrete mixtures
(identified as A, B, C, D and E ). Mix design procedures are calculated step by step
according to ACI method. And then, SCC are cast into cube mold of cast irons. All
specimens are submerged in a tank of fresh water for a period before testing. Finally,
they are tested for 7 days, 14 days and 28 days compressive strength.
Silica
No. Mixture Water/ cement ratio ViscoCrete -6100 Fly Ash
Fumes
1 A 0.36 1.4% by wt of cement 10% 10%
Step 3 : According to Table A.1, the amount of water is 360 lb/yd³. But
this table is applicable for normal concrete mix design. For
SCC, the amount of water is reduced 18% according to the
result of trial mix design and properties of admixture.
Therefore, required g water = 360 - (360×0.18) = 295.2 lb/yd³.
Step 4 : Design strength is 6525 psi. Therefore, targeted compressive
strength is 7917 psi according to Table A.2.
Step 5 : Water cement ratio, w/c= 0.36 (from Table A.3)
295.2
Step 6 : Cement Content = = 820 lb/yd³
0.36
So, ViscoCrete -6100 = 820 ×0.014= 11.48 lb/yd³
80 ×820
Cement content(80 %by wt of cement)= =656 lb/yd³
100
10× 820
Fly ash content(10%by wt of cement)=
100
= 82 lb/yd³
10× 820
Silica Fume content (10%by wt of cement)=
100
= 82
lb/yd³
Step 3 : According to Table A.1, the amount of water is 360 lb/yd³. But
this table is applicable for normal concrete mix design. For
SCC, the amount of water is reduced 18% according to the
result of trial mix design and properties of admixture.
Therefore, required g water = 360 - (360×0.18) = 295.2 lb/yd³.
Step 4 : Design strength is 6525 psi. Therefore, targeted compressive
strength is 7917 psi according to Table A.2.
Step 5 : Water cement ratio, w/c= 0.36 (from Table A.3)
295.2
Step 6 : Cement Content = = 820 lb/yd³
0.36
So, ViscoCrete -6100 = 820 ×0.014= 11.48 lb/yd³
80 ×820
Cement content(80 %by wt of cement)= =656 lb/yd³
100
20× 840
Fly ash content(20%by wt of cement)=
100
= 164 lb/yd³
295.2
Volume of water = = 4.7308 ft3/yd3
1× 62.4
656
Volume of cement= = 3.3695 ft3/yd3
3.12× 62.4
11.48
Volume of Viscocrete-6100 = = 0.1736 ft3/yd3
1.06× 62.4
Volume of air content = 0.02 × 27 = 0.54 ft3/yd3
164
Volume of Fly Ash = = 1.1892 ft3/yd3
2.21× 62.4
Total Volume = 10.0031 ft3/yd3
Volume of aggregate = 27 – 10.0031 = 16.9969 ft3/yd3
Volume of coarse aggregate according to Table A.4 = 0.71
54
ft3/yd3(1431.7730 lb/yd3)
Cement = 752.044 lb
10 mm)
ViscoCrete-6100 = 10.528 lb
Step 3 : According to Table A.1, the amount of water is 360 lb/yd³. But
this table is applicable for normal concrete mix design. For
SCC, the amount of water is reduced 17.5% according to the
result of trial mix design and properties of admixture.
Therefore, required g water = 360 - (360×0.175) = 297 lb/yd³.
Step 4 : Design strength is 6525 psi. Therefore, targeted compressive
strength is 7917 psi according to Table A.2.
56
ft3/yd3(810.88 lb/yd3)
57
Coarse aggregate are too much. Assume 27.167 % will be reduced according to the
recommendations of EFNARC to get better flowability.
Weight of coarse aggregate = 2098.510 -(2098.510 × 0.272)=
(1432.840 lb/yd3)
Cement = 775.864 lb
of 10 mm)
ViscoCrete-6100 = 10.862 lb
Step 3 : According to Table A.1, the amount of water is 360 lb/yd³. But
this table is applicable for normal concrete mix design. For
SCC, the amount of water is reduced 15% according to the
result of trial mix design and properties of admixture.
Therefore, required g water = 360 - (360×0.15) = 306 lb/yd³.
Step 4 : Design strength is 6525 psi. Therefore, targeted compressive
strength is 7917 psi according to Table A.2.
Step 5 : Water cement ratio, w/c= 0.36 (from Table A.3)
59
306
Step 6 : Cement Content = = 850 lb/yd³
0.36
So, ViscoCrete -6100 = 850 ×0.014= 11.9 lb/yd³
90 ×850
Cement content(90%by wt of cement)= =765 lb/yd³
100
5× 850
Fly ash content(5%by wt of cement)=
100
= 42.5 lb/yd³
5× 850
Silica Fume content (5%by wt of cement)=
100
= 42.25
lb/yd³
ft3/yd3(801.5796 lb/yd3)
Coarse aggregate are too much. Assume 26.547 % will be reduced according to the
recommendations of EFNARC to get better flowability.
Weight of coarse aggregate = 2074.41 -(2074.41 × 0.265)=
60
ft3/yd3(1434.968 lb/yd3)
Cement = 800.83487 lb
of 10 mm)
ViscoCrete-6100 = 11.2116 lb
Step 3 : According to Table A.1, the amount of water is 360 lb/yd³. But
this table is applicable for normal concrete mix design. For
SCC, the amount of water is reduced 15% according to the
result of trial mix design and properties of admixture.
Therefore, required g water = 360 - (360×0.15) = 306 lb/yd³.
Step 4 : Design strength is 6525 psi. Therefore, targeted compressive
strength is 7917 psi according to Table A.2.
Step 5 : Water cement ratio, w/c= 0.36 (from Table A.3)
62
306
Step 6 : Cement Content = = 850 lb/yd³
0.36
So, ViscoCrete -6100 = 850 ×0.014= 11.9 lb/yd³
92× 850
Cement content(92%by wt of cement)= =782 lb/yd³
100
5× 850
Fly ash content(5%by wt of cement)=
100
= 42.5 lb/yd³
3× 850
Silica Fume content (3%by wt of cement)=
100
= 25.5
lb/yd³
ft3/yd3(801.5796 lb/yd3)
Coarse aggregate are too much. Assume 26.547 % will be reduced according to the
recommendations of EFNARC to get better flowability.
Weight of coarse aggregate = 2074.41 -(2074.41 × 0.265)=
63
ft3/yd3(1434.968 lb/yd3)
Cement = 811.578712 lb
of 10 mm)
64
ViscoCrete-6100 = 11.3621 lb
Aggregate
(lb/yd³)
ViscoCrete
6. 10.51 10.53 10.86 11.21 11.36
-6100 (lb)
EFNARC Mixtures
Items
recommendations A B C D E
Coarse Aggregate
content of the 750 – 1000 915.07 908.1 906.7 903.9 901.1
mix(kg/m3)
Total powder
380 – 600 kg/m3
content 534.60 535.3 529.3 522.6 519.9
Fine Aggregate
content of the > 40% 48.05 48.33 48.39 48.5 48.6
mortar
171.0
Water content (kg) 150-210 160.38 160.6 165.7 173.3
Water/powder ratio
0.80 – 1.10 0.88 0.87 0.93 0.99 1.01
by volume
According to the result data obtained from the measurements and the tests
conducted in ITC (Mandalay),all the trial mixtures in proportions which are in
conformity with the recommendations of EFNARC for SCC mix design.
66
4.3.4.1. Equipment
The apparatus is shown in figure(4.1).. Mould is in the shape of a truncated
cone with the internal dimensions 200mm at the base, 100mm diameter at the top and
a height of 300mm.Base plate of a stiff non-absorbing material, at least 700mm
square, marked with a circle marking the central location for the slump cone, and a
further concentric circle of 500mm diameter. The apparatus usually required for this
test are as trowel, scoop, ruler and stopwatch.
4.3.4.2. Procedure
(a) About six liters of concrete is needed to perform the test, sampled
normally.
(b) Moisten the base plate and inside of slump cone. Place base plate on
level stable ground and the slump cone centrally on the base plate and
hold down firmly.
(c) Fill the cone with the scoop. Do not tamp, simply strike off the concrete
level with the top of the cone with trowel.
(d) Remove any surplus concrete from around the base of the cone.
(e) Raise the cone vertically and allow the concrete to flow out freely.
68
(f) Simultaneously, start the stopwatch and record the time taken for the
concrete to reach the 500mm spread circle. (This is T50 time).
(g) Measure the final diameter of the concrete in two perpendicular
directions.
(h) Calculate the average of the two measured diameters. (This is slump
flow in mm).
4.3.5.1. Equipment
The apparatus usually required for this test are as trowel, scoop, ruler.
69
4.3.5.2. Procedure
(a) About fourteen liters of concrete is needed to perform the test, sampled
normally.
(b) Set the apparatus level on firm ground, ensure that the sliding gate can
open freely and close it.
(c) Moisten the inside surfaces of the apparatus, remove any surplus water.
(d) Fill the vertical section of the apparatus with the concrete sample.
(e) Leave it to stand for one minute.
(f) Lift the sliding gate and allow the concrete to flow out into the horizontal
section.
(g) When the concrete stops flowing, the distance “H1” and “H2” are
measured.
(h) Calculate H2/H1, the Blocking Ratio.
(i) The whole test has to be performed within five minutes.
4.3.6.1. Equipment
The apparatus usually required for this test are as V-funnel, bucket (+/- 12
liter), trowel, scoop and stopwatch.
(d) Keep the trap door open to allow any surplus water to drain.
(e) Close the trap door and place a bucket underneath.
(f) Fill the apparatus completely with concrete without compacting or
tamping; simply strike off the concrete level with the top with the trowel.
(g) Open within ten seconds after filling the trap door and allow the concrete
to flow out under gravity.
(h) Start the stopwatch when the trap door is opened, and record the time for
the discharge to complete (the flow time). This is taken to be when light
is seen from above through the funnel.
(i) The whole test has to be performed within five minutes.
According to the result data obtained from the specific tests which are
conducted at ITC(Mandalay),all the trial mixtures are in conformity with the
recommendations of EFNARC as the result data are within the limits.
74
2 7 0.36 5398.76
3 7 0.36 5393.37
4 14 0.36 7565.35
6 14 0.36 7565.77
7 28 0.36 8042.60
9 28 0.36 8058.63
9000
8000
7000
Compressive strength (psi)
6000
5000
4000
3000
2000
1000
0
Days
Compressive Average
Curing Period Water Cement
No Strength Compressive
(Days) Ratio
(psi) Strength (psi)
1 7 0.36 5019.50
3 7 0.36 5012.78
4 14 0.36 7070.44
6 14 0.36 7068.71
7 28 0.36 7599.15
9 28 0.36 7595.69
77
8000
7000
6000
Compressive strength (psi)
5000
4000
3000
2000
1000
0
Days
8000
7000
6000
5000
4000
3000
2000
1000
0
Days
Figure 4 .10. Compressive Strength Test Results of Mixture C
4.4.4. Compressive Strength Test Results of Mixture D
The compressive strength test results of mixture D is shown in Table 4.8 and
these are plotted in Figure 4.11. The average compressive strength of mixture D are
achieved 4562 psi (or)31.5MPa at 7 days, 6421 psi (or) 44.3 MPa at 14 days and
6911psi (or) 47.7MPa respectively. Mixture D reaches design strength at 28 days.
8000
7000
5000
4000
3000
2000
1000
0
Days
7 28 0.36 6847.04
9 28 0.36 6838.74
80
8000
7000
Compressive strength (psi)
6000
5000
4000
3000
2000
1000
0
Days
Mixture
7 days 14 days 28 days
There are factors that cannot be easily quantified in money amount but
nonetheless the benefits of SCC cannot be overlooked. A material and cost difference
exists from one location to another. As noted earlier, chemical admixtures must be
used to achieve these SCC properties. Admixture costs can vary depending on dosage
and effectiveness. Use of pozzolanic materials such as fly ash and Silica fume to
replace a part of cement in the mixture can result in significant cost savings. The costs
82
per cubic meter information are calculated using research mixtures with ACI mix
design, but using costs for materials are taken from construction market.
Table 4.11. Costs Comparison of One Cubic-meter SCC Mixtures and Normal
Concrete Mixture (W/C = 0.36)
Normal
SCC mix
mix
Ingredients
A B C D E
(Double
49000 49070 50630 52260 52960 81850
Rhinos)
Water
Sand 2270 2280 2280 2280 2290 1100
Chipping
2030 2010 2010 2010 2000 2360
(20 mm)
B Aggregate
2030 2010 2010 2010 2000 2360
(10 mm)
The cost of SCC mixture A (Viscocrete-6100, 1.4%, fly ash 10%,silica fume
10% and water cement ratio 0.36) for one cubic meter is 89390 kyats, 1715 kyats
more than normal concrete. Similarly, the cost of SCC mixture B (Viscocrete-6100,
1.4%, fly ash 20%,silica fume 0% and water cement ratio 0.36)for one cubic meter is
85480 kyats, more cost effective than normal concrete. Moreover, the cost of SCC
mixture C (Viscocrete-6100, 1.4%, fly ash 10%,silica fume 5% and water cement
ratio 0.36) for one cubic meter is 89130 kyats, less cost-effective than normal concrete.
Similarly, the cost of SCC mixture D (Viscocrete-6100, 1.4%, fly ash 5%,silica fume
5% and water cement ratio 0.36) for one cubic meter is 90840 kyats less cost effective
than normal concrete. Similarly, the cost of SCC mixture E(Viscocrete-6100, 1.4%,
fly ash 5%,silica fume 3% and water cement ratio 0.36) for one cubic meter is 90710
kyats ,less cost effective than normal concrete.