Current relays (IT, IS, IA, ID, IP, NT, IM, RT, FI and IV)
Data Sheet
DSE_PL70current_eng_AU
FUNCTIONS TABLE
Protection
The following table reflects the protection functions incorporated into each unit.
Functions IT IS IA ID IP NT IM RT FI IV
Undercurrent (37) X X
Phase overcurrent (50/51) X X X X** X
Thermal image (49) X X X X X X
Current unbalance (46), Broken conductor (46FA) X X X X
Neutral overcurrent (50/51N) X X X X**
Sensitive neutral overcurrent (50/51NS) X
Residual neutral overcurrent (50/51NR) X X X X
Neutral overcurrent 2 (50/51N2 or G1)) X X
Neutral overcurrent 3 (50/51N3 or G2) X
Voltage controlled overcurrent (51V) X
Breaker failure protection (50BF) X X X X X X X X X
Restricted earth fault protection (87N) X X
Directional neutral overcurrent (67N) X
Insulated neutral directional overcurrent (67NA) X
Overexcitation X
Flashover X
End fault X
Cold load pickup (CLP) O O
Recloser O O
Trip and close circuit surveillance (74TC/CC)* X X X X X X X X X X
Note:
X: Available function O: Optional function *Only with I/O extension module **Single-phase 50/51 or 50/51N depending on the connection
PROTECTION SETTINGS
Undercurrent protection (37) - IT, IS Models
Protects motors and pumps against drops in supply current.
This function may be used in those situations in which a neutral transformer is not available.
Setting Remarks
Enabled YES/NO
Cold load time 0 to 10000 sec.
Operation time 0 to 3600 sec.
Breaker failure protection (50BF) - IT, IS, ID, IP, IM, NT, RT, FI, IV models
Verifies the correct functioning of a breaker when clearing a fault. In the event of an incorrect functioning of a breaker
when clearing a fault, the protection trips the breakers necessary to isolate the fault.
YES/NO
Enabled
Detects breaker operation failure when receiving an open command. It can work in single-pole or three-pole mode.
Detects breaker operation failure when receiving a three-pole or two-pole trip command being some of the breakers closed
or having neutral current flow.
Flashover – FI model
Protects against damage in the breaker due to internal arc between its contacts.
Enabled YES/NO
End fault threshold (A) 0,1 100 0,1
End fault definite time (sec) 0 1 0,001
AUTOMATISM FUNCTIONS
Recloser (79) - Optional IT, IS models
Enables the automatic reconnection of the system following transient faults.
Sequence coordination
This function supervises a reclosing sequence performed by the relay closer to the fault by following the whole cycle.
Operating logic
Ensures the correct functioning of the breaker and protects the relay. Also generates an alarm in the event of the non-completion
of an effected operation.
MEASUREMENTS
Measurements IT IS IA ID IP IM NT RT FI IV
IA X X X X X X
IB X X X X X
IC X X X X X
Medium X X X X X
IN X X X X X X
INS X X
IN2 X
IN3 X
V comp X X
VN X X
Current maximeter X X X X X X
COMMUNICATION PROTOCOLS
Communication via front port (Port 1_1):
Serial (RS232C)
PROCOME
Communication via rear port 2 (Port 1_2):
LOCAL KEYPAD/DISPLAY
4-KEY KEYBOARD
RS232 CONNECTOR
TESTS
TECHNICAL SPECIFICATIONS
Auxiliary power supply
220 Vac
Range 176-264 Vac.
Ripple 20 % over the rated value
12 Vdc
Range 9-15 Vdc
Ripple 20 % over the rated value
24-48 Vdc
Range 19-58 Vdc
Ripple 20 % over the rated value
110-125-220 Vdc
Range 86-280Vdc
Ripple 20% over the rated value
Burden 7W min/ 12W max
Current circuits
Thermal capacity for phase I (unified rated current 5/1A)
Continuous 20 A
Short term (1 s.) 500 A
Very short term (½ cycles) 1250 A
Burden at In = 5 A <0.2 VA
Burden at In = 1A <0.02 VA
Thermal capacity for sensitive neutral I (Single rated current 0.25/0.025 A)
Continuous 20 A
Short term (1 s.) 100 A
Burden at In = 0.25 A <0.0010VA
Voltage circuits
Thermal capacity
Permanent 260 V
Burden at 63.5 V 0.015 VA
Burden at 100V <0.03 VA
Programmable phase shift: ABC or CBA
RS485
RS485 connector DTE pin D type female
Cable type Shielded twisted pair
Cable length 1000 m max.
Insulation 500V
G.F.O.
G.F.O. Connector ST
Wavelength 820 nm
Permitted attenuation 8 db with 62.5 /125 µm glass fibre
Multimode glass fibre optic 62.5 /125 µm
P.F.O.
P.F.O. connector HP standard
Wavelength 660 nm
24.7 db with 1mm plastic cable
Permitted attenuation
22 db with 200 µm silica cable
115 m with 1mm low frequency plastic
Maximum distance cable
1.9 Km with 200 µm silica cable
Ethernet RJ45
RJ45 connector RJ45 Female
Cable type Shielded
Cable length 100 m max.
Insulation 500V
Baud rate 10/100 Mbps
IRIG-B port (optional)
Input Demodulated
Input level TTL
Cable type 2-wire, shielded
Insulation 500V
Accuracy
For unified rated current 5/1A Class 1 for V, I and P (up to120% nominal)
Accuracy in the protected range 3%
Curve operation accuracy ±5% or 30ms (the highest of the two values)
Bank voltage monitoring (optional)
24-48 Vdc
Range 19 to 58 Vdc
110-125-220 Vdc
Range 86 to 280 Vdc
12 Vdc
Range 9 to 15 Vdc
220 Vac
Range 176 to 264 Vac
Mechanical characteristics
Weight 1.6 Kg
Approx. weight With packaging and documentation 2.6 Kg
Front IP IP40
Optional front IP IP54
ENVIRONMENTAL CONDITIONS
Operating temperature
24-48 Vdc -20ºC to 65 ºC
110-125-220 Vdc -20ºC to 60 ºC
12 Vdc -20ºC to 70 ºC
220 Vac -20ºC to 70 ºC
Storage temperature -40ºC to 85ºC
Up to 95% without
Relative humidity
condensation
The LCD contrast is not operative for temperatures below -20º and above 70ºC.
CONSTRUCTIVE CHARACTERISTICS
PL70IT, IS, IA, ID, IP, NT, IM, RT, FI and IV dimensions
CONNECTION DIAGRAMS
The following figures reflect only one of the possible digital input and output programming options (very simple).
IT family
IS family
ID, IA families
IP family
NT family
IM family
RT family
FI family
IV family