KITCHEN HOODS

AS 1668.2 - CONVENTIONAL FRYING

CANOPY-TYPE HOOD (AGAINST WALL)

Q = 400.W.L
or Q = 250.P.H
P = 2.W+L

W (bench) 1050 mm
L (bench) 2500 mm Q= 1450 l/s
overhang 200 mm
W 1250 mm P = 5400 mm
L 2900 mm
H 1200 mm Q= 1620 l/s

W (bench) 1200 mm
L (bench) 3000 mm Q= 1904 l/s
overhang 200 mm
W 1400 mm P = 6200 mm
L 3400 mm
H 1200 mm Q= 1860 l/s

W (bench) 1050 mm
L (bench) 5000 mm Q= 2700 l/s
overhang 200 mm
W 1250 mm P = 7900 mm
L 5400 mm
H 1200 mm Q= 2370 l/s

W (bench) 1200 mm
L (bench) 6000 mm Q= 3584 l/s
overhang 200 mm
W 1400 mm P = 9200 mm
L 6400 mm
H 1200 mm Q= 2760 l/s

INDUSTRIAL VENTILATION - Page 10-33


Entry Loss = (filter resistance + 25Pa) + 0.5*VP (straight take-off)
Entry Loss = (filter resistance + 25Pa) + 0.25*VP (tapered take-off)

Duct Velocity = 10 m/s


Velocity Pressure = 60 Pa
Filter Resistance = 40 Pa (final)

Entry Loss = 95 Pa (straight take-off)


80 Pa (tapered take-off)

492491570.xls Page 1 of 2
KITCHEN HOODS

AS 1668.2 - CONVENTIONAL FRYING

ISLAND TYPE HOOD

Q = 635.W.L **
or Q = 250.P.H
P = 2(W+L)

W (bench) 1200 mm
L (bench) 3500 mm Q= 3962 l/s
overhang 200 mm
W 1600 mm P = 11000 mm
L 3900 mm
H 1200 mm Q= 3300 l/s

W (bench) 1500 mm
L (bench) 4000 mm Q= 5309 l/s
overhang 200 mm
W 1900 mm P = 12600 mm
L 4400 mm
H 1200 mm Q= 3780 l/s

W (bench) 1700 mm
L (bench) 4500 mm Q= 6534 l/s
overhang 200 mm
W 2100 mm P = 14000 mm
L 4900 mm
H 1200 mm Q= 4200 l/s

W (bench) 2000 mm
L (bench) 6000 mm Q= 9754 l/s
overhang 200 mm
W 2400 mm P = 17600 mm
L 6400 mm
H 1200 mm Q= 5280 l/s

INDUSTRIAL VENTILATION - Page 10-33


Entry Loss = (filter resistance + 25Pa) + 0.5*VP (straight take-off)
Entry Loss = (filter resistance + 25Pa) + 0.25*VP (tapered take-off)

Duct Velocity = 10 m/s


Velocity Pressure = 60 Pa
Filter Resistance = 40 Pa (final)

Entry Loss = 95 Pa (straight take-off)


80 Pa (tapered take-off)

492491570.xls Page 2 of 2