Design calculation sheet

Project Name: Asharf Al - Jabari Date: 4/7/2019 Sheet no.: 1 of 1 Computed by:

Checked by: -
Subject: Car Park Ventilation - Basements
Approved by: -
Basement 4,3,2 - Parking

Air Change per Hour =6 ACH

Parking Height =3 M

Parking Area = 700 M2

Exhaust Flow Rate = 3500 L/S

Exhaust Fan Flow Rate = 3500 L/S

Selected Exhaust Fan Flow Rate = 10500 L/S 1 fans

Selected Fresh Fan Flow Rate = 2600 L/S 3 fans

Basement 1 - Store

Air Change per Hour =4 ACH

Store Height =3 M

Parking Area = 700 M2

Exhaust Flow Rate = 2333 L/S

Flow Rate Per Fan = 2333 L/S

Selected Exhaust Fan Flow Rate = 2400 L/S 1 fans

Selected Fresh Fan Flow Rate = 2000 L/S 1 fans