You are on page 1of 1

CADANGAN UBAHSUAI DALAMAN 1 UNIT KEDAI PEJABAT 3 TINGKAT KEPADA

HOTEL BAJET PADA TINGKAT 1, 2 & SEBAHAGIAN TINGKAT BAWAH, NO. PT 435,
H.S(D) 18061, NO. P36 PUSAT PERNIAGAAN MUTIARA GEMILANG, MUKIM &
DAERAH BENTONG, PAHANG DARUL MAKMUR UNTUK TETUAN YES LUXURY
HOTEL SDN BHD.

Smoke Spill System for Hotel Passage

Design Criteria :

i) Exhaust : 10 air change per hour (10 ACH)


ii) Make-up : 60% from exhaust

Note : Powered replacement air should not exceed 75% or be less than 50% of the
extracted air volume.

Calculation :

Passage - First Floor & Second Floor Level

Floor area : 54 m2
Floor height : 3.4 m

Volume, V = Floor Area x Floor Height


= (54 x 3.4) m3
= 183.6 m3
= 6,474 ft3

Exhaust Fan Capacity = (V x ACH)/ 60


= (6,474 x 10)/60
= 1,079 cfm
≈ 1,100 cfm

Fresh Air Fan Capacity = 60% x 1,100


= 660 cfm
≈ 700 cfm

Summary of Fan Selection

Area Exhaust Fan Fresh Air Fan


Capacity (cfm) Qty. Capacity (cfm) Qty.
Passage - First floor 1,100 1 no. 700 1 no.

Passage - Second floor 1,100 1 no. 700 1 no.