APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 1 : CIVIL – EXTERNAL

EXTERNAL (COMPOUND) INSPECTION CHECKLIST

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1 Access road
a) 8000mm ± 500mm (wide)
b) (Premix/Crusher Run*)
MJ
c) Catered for double axle trucks carrying
60 tons transformer c/w method
statement (as per sample)

2 Internal road
a) In front of transformer bay - 8000mm ±
500mm (wide)
b) In front of loading bay - 6000mm ±
500mm (wide)
c) Others - 3000mm ± 500mm (wide)
MJ
d) (Premix/Reinforced Concrete)
e) Catered for double axle trucks carrying
60 tons transformer c/w method
statement (as per sample)
f) To conduct coring test min. 2 location (in
front of loading bay and transformer bay)

3 Main gate (Tolerance: ± 5%)


a) 8000mm (w) x 2400mm (h) double leaf
swing gate c/w cross bar support with
min. 4 nos heavy duty roller MJ
b) Hot dipped galvanised iron with anticlimb
anticut.
c) Mesh size: 12.5 x 75 x 4mm Ø

4 Fence (Tolerance: ± 5%)


a) 2100mm (h) hot dipped galvanised iron,
anticlimb anticut c/w 600mm high razor
blade concertina wire
MJ
b) Mesh size: 12.5 x 75 x 4mm Ø
c) 38 – 50mm stone chipping at the base
150 mm depth (1000mm inward and
1000mm outward)

5 Perimeter drainage system MJ

Page 1 of 6
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 1 : CIVIL – EXTERNAL

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

a) Culverts & sump (standalone PPU)**


b) Heavy Duty FRP Grating at all crossings

6 Sewerage system
a) (Centralize/Individual)**
MJ
b) Culverts & sump (standalone PPU)**
c) Heavy Duty FRP Grating at all crossings

7 Water supply
(Domestic connection/ Rain water harvesting MJ
system/Tube well)**

8 Compound Surfacing – (Premix/Crusher run*) MN

9 Compound lighting for standalone PPU


a) 8 nos 4m (high), 150W HPSV galvanised
pole c/w timer and photocell MJ
b) Sub DB (external lighting) shall be located
at guard house

10 Oil Water Separator System MJ

11 a) Heavy Duty Reinforced


MJ
Concrete earthing chamber
Commissioning) constructed as per
Earthing system (incl. Testing &

b) 50mm x 6mm copper tape


Tolerance:
Tebal: ± 0.055mm MJ
specification

Lebar: ± 1.0mm
Panjang: ± 10mm

c) Copper connection (crossby


MJ
clip/cadweld/clamp)

d) Link Earth Resistance


< 3 ohms
MJ
e) Tested and certified by
service engineer

Page 2 of 6
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 1 : CIVIL – EXTERNAL

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

f) Proof of calibrated testing


equipment (min. every 3
years)
g) Testing method shall comply
with IEEE STANDARD 81

12 a) Main signboard MN

b) TNB Careline
 Location: at PPU wall facing MN
the main road

c) Danger sign
 Location: at all four (4) sides MN
Signage

of perimeter fencing

d) No entry sign
 Location: at all four (4) sides MN
of perimeter fencing

e) Safety Excellence
Management System (SEMS) MN
symbol

13 Meter board (backup building supply) MJ

14 Site Clearing MN
* Developer shall provide an undertaking letter for provision of premix upon the completion of the development
**As per local authorities’ approval

Page 3 of 6
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 1 : CIVIL – EXTERNAL

EXTERNAL (BUILDING) INSPECTION CHECKLIST

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1 Structural failure – crack, settlement as per


MJ
professional Civil & Structural engineer

2 Painting works (visual defects) MN

3 a) Floor finish – power float MJ

b) Removable handrail –
900mm high 75mmØ stainless MJ
steel

c) Staircase anti-slip c/w anti-slip


Loading bay

MJ
nosing tiles

d) Finish floor level shall be lower


MN
than internal floor level by 50mm

4 a) Apron
 Visual inspection - no cracks
 Cement render finishes
b) Ramp MN
 Visual inspection - no cracks
 V-shaped Groove line
 Yellow and black demarcation lines

5 Cable entry 33kV


a) 24 Nos of ducting HDPE PN10 150mm Ø
b) 1000mm extended beyond perimeter MJ
fencing c/w endcap
c) 1000mm cable landing before ramp

6 Cable entry 11 kV
a) 24 Nos of ducting HDPE PN10 200mm Ø
b) 1000mm extended beyond perimeter MJ
fencing c/w endcap
c) 1000mm cable landing before ramp

Page 4 of 6
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 1 : CIVIL – EXTERNAL

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

7 Air terminal rod (for lightning) to be


connected with main grid 25 x 3mm copper
MJ
strip concealed in concrete, test point at 4
corners at 2.1m height

8 Rain water down pipe –


MJ
Min. 5 nos of 150 mmØ exposed PVC pipe

Page 5 of 6
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 1 : CIVIL – EXTERNAL

RESULT

DISTRIBUTION FACILITY: PMU/PPU/SSU

DATE:

CONCLUSION:

 PASS  FAIL NO. OF NON-COMPLIANCE :


(If minor non-compliance/s) (If any major non-compliance)

COMMENT :

AUDITED BY
NAME : SIGNATURE :

 ALL DEFECT/S CLEARANCE VERIFIED (IF APPLICABLE)

VERIFIED BY
NAME : SIGNATURE & DATE :

Note : Project Manager is required to scan & email this page to Project Design, Asset Development Unit within 5 days of SCA
completion date.

Page 6 of 6
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

TRANSFORMER BAY - ROOM 1 INSPECTION CHECKLIST

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1. Blast wall - structural & finishes


a) 4800mm high 2 hours fire-rated double
clay brick blast wall MJ
b) Structural failure (if any) *
c) Painting works (visual defects)

2. Transformer plinth – structural & finishes


a) Floor finishes - Power float
b) 4200mm (l) x 2000mm (w) x
MJ
150mm(h) ± 10mm
c) Design load – 60 tonne
d) Structural failure (if any)*

3. a) Room signage MN
Signage

b) Danger sign MN

c) No entry sign MN

4. a) 5000 x 2500mm(h) ± 5%
Removable fencing hot
dipped galvanised iron frame
Outdoor type

MJ
with hot dipped galvanised
anti-climb, anti-cut mesh
Mesh size: 12.5 x 75 x 4mm Ø

b) Fittings - latch & hasp c/w


MJ
lock protector

5. a) 5000 x 6000 (h) ± 5% Solid


G.I. both auto & manual
Attached building

roller shutter door linked


with firefighting system with
closing time less than 30 MJ
seconds
b) Side door: 900 x 2100mm (h)
± 5% single leaf mild steel
door

Page 1 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

c) Fitting – latch & hasp c/w lock


MJ
protector

d) Ventilation system
Mechanical ventilation connected MJ
to fire alarm panel

6. Cable trench & slot - structural & finishes


a) Structural failure (if any)*
MJ
b) 900mm (wide) x 900mm(depth)** ±
10mm

7. Trench/ slot cover


a) 6mm thick reinforced chequered plate MJ
c/w lifting hook***

8. . 150mm (thick) Granite chipping ± 10mm


MJ
Size: 25mm - 38mmØ (if at ground level)

9. Water discharge outlet pipe


MJ
1 nos 150mmØ PVC pipe/Submersible pump

10. Lighting -
Electrical fittings (incl. Testing &

a) 5000mm (h) affl 2 nos


Floodlight 250W– 300W
MJ
(Attached)
Commissioning)

b) 4800mm affl 3 nos Lantern


HPSV 150W (Standalone only)

Switches
a) 1 Nos Weatherproof switches
b) 1 Nos 20 Amps power point MJ
c) 1 Nos 3 phase 20 Amps
power point

11. 2 points of 50mm x 6mm x


Earthi

Syste
ng

300mm (l) copper tape MJ


12. Location: Transformer plinth

Page 2 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

13. 2 nos. earthing chamber MJ

14. 2 Nos of 9kg ABC portable fire extinguisher


MJ
c/w weatherproof compartment
*Major crack or settlement shall be verified by professional Civil & Structural engineer
** Trench depth clearance from ground beam – 600mm
***Reinforced with 25 x 25mm mild steel angle iron stopper welded at the underside of chequered plate

Page 3 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

TRANSFORMER BAY - ROOM 2 INSPECTION CHECKLIST

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1. Blast wall - structural & finishes


a) 4800mm high 2 hours fire-rated double
clay brick blast wall MJ
b) Structural failure (if any) *
c) Painting works (visual defects)

2. Transformer plinth – structural & finishes


a) Floor finishes - Power float
b) 4200mm (l) x 2000mm (w) x 150mm(h)
MJ
± 10mm
c) Design load – 60 tonne
d) Structural failure (if any)*

3. a) Room signage MN
Signage

b) Danger sign MN

c) No entry sign MN

4. a) 5000 x 2500mm(h) ± 5%
Removable fencing hot
dipped galvanised iron frame
Outdoor type

MJ
with hot dipped galvanised
anti-climb, anti-cut mesh
Mesh size: 12.5 x 75 x 4mm Ø

b) Fittings - latch & hasp c/w


MJ
lock protector

5. a) 5000 x 6000 (h) ± 5% Solid


G.I. both auto & manual
Attached building

roller shutter door linked


with firefighting system with
closing time less than 30 MJ
seconds
b) Side door: 900 x 2100mm (h)
± 5% single leaf mild steel
door

Page 4 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

c) Fitting – latch & hasp c/w lock


MJ
protector

d) Ventilation system
Mechanical ventilation connected MJ
to fire alarm panel

6. Cable trench & slot - structural & finishes


a) Structural failure (if any)*
MJ
b) 900mm (wide) x 900mm(depth)** ±
10mm

7. Trench/ slot cover


b) 6mm thick reinforced chequered plate MJ
c/w lifting hook***

8. . 150mm (thick) Granite chipping ± 10mm


MJ
Size: 25mm - 38mmØ (if at ground level)

9. Water discharge outlet pipe


MJ
1 nos 150mmØ PVC pipe/Submersible pump

10. Lighting -
Electrical fittings (incl. Testing

a) 2 Nos Floodlight 250 – 300W


(Attached) MJ
& Commissioning)

b) 3 Nos Lantern HPSV 150W


(Standalone)

Switches
a) 1 Nos Weatherproof switches
b) 1 Nos 20 Amps power point MJ
c) 1 Nos 3 phase 20 Amps
power point

11. 2 points of 50mm x 6mm x


Earthing

500mm (l) copper tape MJ


System

12. Location: Transformer plinth

13. 2 Nos. earthing chamber MJ

Page 5 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

14. 2 Nos of 9kg ABC portable fire extinguisher


MJ
c/w weatherproof compartment
*Major crack or settlement shall be verified by professional Civil & Structural engineer
** Trench depth clearance from ground beam – 600mm
***Reinforced with 25 x 25mm mild steel angle iron stopper welded at the underside of chequered plate

Page 6 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

NER BAY / ROOM INSPECTION CHECKLIST

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1. Blast wall - structural & finishes


a) 4800mm high 2 hours fire-rated double
clay brick blast wall MJ
b) Structural failure (if any)*
c) Painting works (visual defects)

2. Transformer plinth – structural & finishes


a) Floor finishes - Power float
b) 1500mm (w) x 2100mm (l) x 150mm(h)
MJ
± 10mm
c) Design load – 5 tonne
d) Structural failure (if any)*

3. a) Room signage MN
Signage

b) Danger sign MN

c) No entry sign MN

4. a) 5000 x 2500mm(h) ± 5%
Removable fencing hot
dipped galvanised iron frame
Outdoor type

MJ
with hot dipped galvanised
anti-climb, anti-cut mesh
Mesh size: 12.5 x 75 x 4mm Ø

b) Fittings - latch & hasp c/w


MJ
lock protector

5. a) 2000 x 3000 (h) ± 5% Solid


G.I. both auto & manual
Attached building

roller shutter door linked


with firefighting system with
closing time less than 30 MJ
seconds
b) Side door: 900 x 2100mm (h)
± 5% single leaf mild steel
door

Page 7 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

c) Fitting – latch & hasp c/w lock


MJ
protector

d) Ventilation system
Mechanical ventilation connected MJ
to fire alarm panel

6. Cable trench & slot - structural & finishes


a) Structural failure (if any) *
MJ
b) 600mm (wide) x 900mm(depth)**
± 10mm

7. Trench/ slot cover


a) 6mm thick reinforced chequered plate MJ
c/w lifting hooks***

8. . 150mm (thick) Granite chipping ± 10mm


MJ
Size: 25mm - 38mmØ (if at ground level)

9. Water discharge outlet pipe


MJ
1 nos 150mmØ PVC pipe/Submersible pump

10. Lighting -
Electrical fittings (incl. Testing

a) 1 Nos Floodlight 250 – 300W


(Attached) MJ
& Commissioning)

b) 1 Nos Lantern HSPV 150W


(Standalone)

Switches
a) 1 Nos Weatherproof switches
b) 1 Nos 20 Amps power point MJ
c) 1 Nos 3 phase 20 Amps
power point

11. 1 point of 50mm x 6mm x 300mm


Earthing

(l) copper tape MJ


System

Location: NER plinth

12. 2 Nos. earthing chamber MJ

Page 8 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

13. 1 Nos of 9kg ABC portable fire extinguisher


MJ
c/w weatherproof compartment
*Major crack or settlement shall be verified by professional Civil & Structural engineer
** Trench depth clearance from ground beam – 600mm
***Reinforced with 25 x 25mm mild steel angle iron stopper welded at the underside of chequered plate

Page 9 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

CAPACITOR BANK BAY / ROOM

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1. Blast wall - structural & finishes


a) 4800mm high 2 hours fire-rated double
clay brick blast wall MJ
b) Structural failure (if any)*
c) Painting works (visual defects)

2. Transformer plinth – structural & finishes


a) Floor finishes - Power float
b) 1200mm (w) x 2100mm (l) x 150mm(h)
MJ
± 10mm
c) Design load – 5 tonne
d) Structural failure (if any)*

3. a) Room signage MN
Signage

b) Danger sign MN

c) No entry sign MN

4. a) 5000 x 2500mm(h) ± 5%
Removable fencing hot dipped
galvanised iron frame with hot
Outdoor type

MJ
dipped galvanised anti-climb,
anti-cut mesh
Mesh size: 12.5 x 75 x 4mm Ø

b) Fittings - latch & hasp c/w lock


MJ
protector

5. a) 2000 x 3000 (h) ± 5% Solid G.I.


Attached building

both auto & manual roller


shutter door linked with
firefighting system with
MJ
closing time less than 30
seconds
b) Side door: 900 x 2100mm (h) ±
5% single leaf mild steel door

Page 10 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

c) Fitting – latch & hasp c/w lock


MJ
protector

d) Ventilation system
Mechanical ventilation connected MJ
to fire alarm panel

6. Cable trench & slot - structural & finishes


a) Structural failure (if any) *
MJ
b) 600mm (wide) x 900mm(depth)**
± 10mm

7. Trench/ slot cover -


6mm thick reinforced chequered plate c/w MJ
lifting hooks***

8. . 150mm (thick) Granite chipping ± 10mm


MJ
Size: 25mm - 38mmØ (if at ground level)

9. Water discharge outlet pipe


MJ
1 nos 150mmØ PVC pipe/Submersible pump

10. Lighting -
Electrical fittings (incl. Testing

a) 1 Nos Floodlight 250 – 300W


(Attached) MJ
& Commissioning)

b) 1 Nos Lantern HSPV 150W


(Standalone)

Switches
a) 1 Nos Weatherproof switches
b) 1 Nos 20 Amps power point MJ
c) 1 Nos 3 phase 20 Amps
power point

11. 1 point of 50mm x 6mm x 300mm


Earthing

(l) copper tape MJ


System

Location: Capacitor bank plinth

12. 1 Nos. earthing chamber MJ

Page 11 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

13. 1 Nos of 9kg ABC portable fire extinguisher


MJ
c/w weatherproof compartment
*Major crack or settlement shall be verified by professional Civil & Structural engineer
** Trench depth clearance from ground beam – 600mm
***Reinforced with 25 x 25mm mild steel angle iron stopper welded at the underside of chequered plate

Page 12 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

LOCAL TRANSFORMER BAY / ROOM

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1. Blast wall - structural & finishes


a) 4800mm high 2 hours fire-rated double
clay brick blast wall MJ
b) Structural failure (if any)*
c) Painting works (visual defects)

2. Transformer plinth – structural & finishes


a) Floor finishes - Power float
b) 1000mm (w) x 1800mm (l) x 150mm(h)
MJ
± 10mm
c) Design load – 5 tonne
d) Structural failure (if any)*

3. a) Room signage MN
Signage

b) Danger sign MN

c) No entry sign MN

4. a) 5000 x 2500mm(h) ± 5%
Removable fencing hot dipped
galvanised iron frame with hot
Outdoor type

MJ
dipped galvanised anti-climb,
anti-cut mesh
Mesh size: 12.5 x 75 x 4mm Ø

b) Fittings - latch & hasp c/w lock


MJ
protector

5. a) 2000 x 3000 (h) ± 5% Solid G.I.


Attached building

both auto & manual roller


shutter door linked with
firefighting system with
MJ
closing time less than 30
seconds
b) Side door: 900 x 2100mm (h) ±
5% single leaf mild steel door

Page 13 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

c) Fitting – latch & hasp c/w lock


MJ
protector

d) Ventilation system
Mechanical ventilation MJ
connected to fire alarm panel

6. Cable trench & slot - structural & finishes


a) Structural failure (if any) *
MJ
b) 600mm (wide) x 900mm(depth)** ±
10mm

7. Trench/ slot cover


6mm thick reinforced chequered plate c/w MJ
lifting hooks***

8. . 150mm (thick) Granite chipping ± 10mm


MJ
Size: 25mm - 38mmØ (if at ground level)

9. Water discharge outlet pipe


MJ
1 nos 150mmØ PVC pipe/Submersible pump

10. Lighting -
Electrical fittings (incl. Testing

a) 1 Nos Floodlight 250 – 300W


(Attached and Standalone) MJ
& Commissioning)

b) 1 Nos Lantern 100W - 150W


(Standalone only)

Switches
a) 1 Nos Weatherproof switches
b) 1 Nos 20 Amps power point MJ
c) 1 Nos 3 phase 20 Amps power
point

11. 1 point of 50mm x 6mm x 500mm


Earthing

(L) copper tape MJ


System

Location: Local transformer plinth

12. 1 Nos. earthing chamber MJ

Page 14 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

13. 1 Nos of 9kg ABC portable fire extinguisher


MJ
c/w weatherproof compartment
*Major crack or settlement shall be verified by professional Civil & Structural engineer
** Trench depth clearance from ground beam – 600mm
***Reinforced with 25 x 25mm mild steel angle iron stopper welded at the underside of chequered plate

Page 15 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 2 : CIVIL – TRANSFORMER, NER & CAPACITOR BANK BAY

RESULT

DISTRIBUTION FACILITY: PMU/PPU/SSU

DATE:

CONCLUSION:

 PASS  FAIL NO. OF NON-COMPLIANCE :


(If minor non-compliance/s) (If any major non-compliance)

COMMENT :

AUDITED BY
NAME : SIGNATURE :

 ALL DEFECT/S CLEARANCE VERIFIED (IF APPLICABLE)

VERIFIED BY
NAME : SIGNATURE & DATE :

Note : Project Manager is required to scan & email this page to Project Design, Asset Development Unit within 5 days of SCA
completion date.

Page 16 of 16
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 3 : CIVIL – CABLE CELLAR

CABLE CELLAR INSPECTION CHECKLIST

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1 a) 1800 x 2100 mm (h) ± 5% double


leaf mild steel door c/w rubber MJ
Mild steel door (main door)

skirting

b) Fitting - latch & hasp c/w lock


MJ
protector

c) Danger signage MJ

d) No Entry signage MJ

e) Room signage MJ

2 a) 1800 x 2100 mm (h) ± 5% double


leaf mild steel door c/w rubber MJ
Mild steel door (exit door)

skirting

b) Fitting - latch & hasp c/w lock


MJ
protector

c) Danger signage MJ

d) No Entry signage MJ

e) Room signage MJ

3 a) Cable trench
 6mm thick reinforced chequered MJ
Structural & finishes

plate c/w lifting hook**

b) Cable entry 33 kV
 24 Nos of ducting HDPE PN10
150mm Ø c/w endcap
 1000mm cable landing before 30° MJ
inclination ramp with smooth
landing

Page 1 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 3 : CIVIL – CABLE CELLAR

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

c) Cable entry 11 kV
 24 Nos of ducting HDPE PN10
200mm Ø c/w endcap
MJ
 1000mm cable landing before 30°
inclination ramp with smooth
landing

d) Ventilation block c/w anti vermin


MJ
netting fixed on both sides

e) Floor finish - Green epoxy paint


MN
(Nippon EA-4 Evergreen 1461)

f) Wall finish – white emulsion paint MN

4 a) Main Fire Alarm Panel (MFAP)


(outside) - to include with
MJ
pictogram / mimic diagram inside
MFAP
Fire Fighting System (incl. Testing & Commissioning)

b) MFAP must be mark with the red


MJ
line at the floor

c) Name tag of installer contractor


MJ
(SGP) shall be placed at MFAP

d) Panel shall be earthed


MJ
independently

e) __nos of gas cylinder(s) c/w


MJ
demarcation lines

f) Laminated labelling at every gas


MJ
cylinder

g) __ nos of smoke detector(s) MJ

h) __nos 9 kg ABC Portable fire


MJ
extinguisher c/w demarcation lines

Page 2 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 3 : CIVIL – CABLE CELLAR

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

i) DB 3-phase for firefighting MJ

5 a) MSBψ (100A - PPU / 60A - SSU) with


changeover switch - must be mark MJ
Electrical Fittings (incl. Testing & Commissioning)

with the yellow line at the floor

b) Framed Schematic Diagram MSB


MJ
next to MSB

c) 1500mm (h) ± 10mm __ nos 13


Amp power point as per drawing -
tagging to follow schematic; test for MJ
each electrical socket using ELCB &
Socket Tester

d) 2 x 23W (min) T8 LED bare channel MJ

e) __ nos 13W emergency light MJ

f) "KELUAR" sign at every exit door MJ

g) Lux of lighting (min. 400 lux ) MJ

6 a) 50 x 6mm copper tape embedded


into concrete with 4 earth terminals MJ
in perimeter wall
Earthing System

b) 4 nos riser point MJ

c) 2 nos earthing points (copper bar


MJ
300 x 50 x 6mm) - 5 way)

d) Cadweld / brazed joints*** MJ

*Demarcation line– wall (Red & White – 50mm) & floor (Yellow - 100mm with 200mm spacing diagonals at 45°)
**Underside of chequered plate to be welded with 25 x 25mm mild steel angle iron stopper
***To be witnessed and verified by TNB during construction
ψ MSB shall be located at next to cable cellar main entrance

Page 3 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 3 : CIVIL – CABLE CELLAR

RESULT

DISTRIBUTION FACILITY: PMU/PPU/SSU

DATE:

CONCLUSION:

 PASS  FAIL NO. OF NON-COMPLIANCE :


(If minor non-compliance/s) (If any major non-compliance)

COMMENT :

AUDITED BY
NAME : SIGNATURE :

 ALL DEFECT/S CLEARANCE VERIFIED (IF APPLICABLE)

VERIFIED BY
NAME : SIGNATURE & DATE :

Note : Project Manager is required to scan & email this page to Project Design, Asset Development Unit within 5 days of SCA
completion date.

Page 4 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 4 : CIVIL – SWITCHGEAR ROOM

SWITCHGEAR ROOM INSPECTION CHECKLIST


Defect Clearance Category
Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1 a) 3000 x 3500mm (h) ± 5%


Solid galvanised iron/mild
steel, both auto & manual
roller shutter door linked MJ
with firefighting system with
Roller shutter

closing time less than 30


seconds

b) Ramp at entrance c/w black


MJ
& yellow demarcation line

c) Bottom level shall be at the


MJ
same level of loading bay

2 a) 1000 x 2100mm (h) ± 5% 1


hour fire-rated solid mild
steel door c/w rubber skirting
 Bottom level shall be at the MN
same level of loading bay
 Stripe colour (in front
entrance) black & yellow
Exit door

b) Fitting - latch & hasp c/w lock


MN
protector

c) Danger signage MN

d) No entry signage MN

e) Room signage MN

3 a) Floor hardener
MJ
Structural &

 Design load: 10kN/m


Finishes

b) Floor finish - Green epoxy


paint (Nippon EA-4 Evergreen MN
1461)

Page 1 of 5
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 4 : CIVIL – SWITCHGEAR ROOM

c) Wall finishes
 2100mm (h) TNB grey gloss
paints - ICI or equivalent
MN
 Above 2100mm (h), white
emulsion paint – ICI or
equivalent

d) 33kV switchgear slot opening


 1200mm x 11000mm ± 5%
 1500mm setback from the
wall to the opening
 Minimum 500mm
cantilevered slab from the
opening to the beam, MJ
 Opening and cantilevered
slab shall be free from cross
beams
 Slot covered with c/w 6mm
thick reinforced chequered
plate c/w lifting hooks**

e) 11kV switchgear slot opening


 1200mm x 16000mm ± 5%
 1500mm from the wall to the
opening
 Minimum 500mm
cantilevered slab from the
MJ
opening to the beam
 Opening shall be free from
cross beams
 Slot covered with c/w 6mm
thick reinforced chequered
plate c/w lifting hooks**

f) LVAC slot
 1000 (l) x 500 (w) ± 5%
 6mm thick reinforced
chequered plate c/w lifting MJ
hooks** and 6mm x 50mm
exposed copper tape at
opening

g) Top hung glass windows


MN
casement

Page 2 of 5
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 4 : CIVIL – SWITCHGEAR ROOM

 __ Nos 1800mm x 600mm to


conform with drawings

h) Ceiling – reinforced concrete


MN
roof slab

4 a) 1500mm (h) 13 Amp power


point - tagging to follow
schematic ( __ nos); test for MJ
Electrical fittings (incl. Testing & Commissioning)

each electrical socket using


ELCB & Socket Tester

b) 2 x 23W (min) ceiling mounted


LED T8 bare channel c/w
angle/mirror reflector (min.
1000mm away from slot
opening) MJ
c) 2400mm (h) ± 10mm 2 x 23W
(min) wall mounted LED T8
bare channel c/w angle/mirror
reflector

d) 13W emergency light


MJ
(__ nos)

e) "KELUAR" sign at every exit


MJ
door

5 a) __ nos min. 2.0 kg portable


Commissioning)
Testing &
Fire Fighting
System (incl.

carbon dioxide (CO2) fire


extinguishers c/w
MJ
demarcation line*,
labelling/tag & BOMBA
certificates

6 a) Air-Cond DB - marked with


Air Conditioning

Commissioning)

the yellow line at the floor


System (incl.

MN
Testing &

c/w Laminated Schematic


Diagram DB / Sub-DB

b) To provide remote control


MN
each room

Page 3 of 5
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 4 : CIVIL – SWITCHGEAR ROOM

c) Heavy duty wall mounted on


external wall type
(2.5HP/3.0HP/5.0HP) to reach
24°C internal temperature,
50% relative humidity
MJ
d) __ nos of air-conditioning
split unit designed for
alternate operation, 12 hours
interval
e) Aircond tray

f) Numbering Material for


Air-conditioning split unit
MN
 Indoor unit - signage number
 Outdoor unit - black paint

7 a) 50mm x 6mm copper tape MJ


Earthing System (incl.

Commissioning)

b) Min. 4 points exposed copper


MJ
Testing &

tape at 33 kV slot

c) Min. 3 points exposed copper


MJ
tape riser at 11 kV slot

d) Cadweld / brazed joints*** MJ

8 a) "UTAMAKAN KESELAMATAN"
sign – green colour (letter), MJ
Signage
Safety

white (background)

b) CPR signage - DRCAB MJ


*Demarcation line– wall (Red & White – 50mm) & floor (Yellow - 100mm with 200mm spacing diagonals at 45°)
**Reinforced with 25 x 25mm mild steel angle iron stopper welded at the underside of chequered plate
***To be witnessed and verified by TNB during construction

Page 4 of 5
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 4 : CIVIL – SWITCHGEAR ROOM

RESULT

DISTRIBUTION FACILITY: PMU/PPU/SSU

DATE:

CONCLUSION:

 PASS  FAIL NO. OF NON-COMPLIANCE :


(If minor non-compliance/s) (If any major non-compliance)

COMMENT :

AUDITED BY
NAME : SIGNATURE :

 ALL DEFECT/S CLEARANCE VERIFIED (IF APPLICABLE)

VERIFIED BY
NAME : SIGNATURE & DATE :

Note : Project Manager is required to scan & email this page to Project Design, Asset Development Unit within 5 days of SCA
completion date.

Page 5 of 5
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 4 : CIVIL – CONTROL ROOM

CONTROL ROOM INSPECTION CHECKLIST

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1. a) 2000 X 2700mm (h) double leaf


(Inside building)
Entrance Door

2 hours fire-rated door c/w


rubber skirting MN
b) BOMBA tag and certificates
c) Door closer

d) Room signage MN

2. a) 1000 x 2100mm (h) 1 hour fire-


rated solid mild steel door c/w MN
rubber skirting

b) Fitting - latch & hasp c/w lock


Exit door

MN
protector (outside the room)

c) Danger signage MN

d) No entry signage MN

e) Room signage MN

3. a) Floor hardener/
MJ
 Design load: 10kN/m

b) 600mm (h) Computer Flooring


 Design load: 10kN/m
Structural & Finishes

 (in the event when control MJ


room is located above
switchgear room)

c) Floor finish - Green epoxy paint


MN
(Nippon EA-4 Evergreen 1461)

d) Wall finishes
 2100mm (h) TNB grey gloss MN
paints - ICI or equivalent

Page 1 of 5
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 4 : CIVIL – CONTROL ROOM

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

 Above 2100mm (h), white


emulsion paint – ICI or
equivalent

e) 33kV slot opening


 600mm x 13000mm
 Slot covered with c/w 6mm MN
thick reinforced chequered
plate c/w lifting hooks**

f) 11kV slot opening


 600mm x 13000mm
 Slot covered with c/w 6mm MN
thick reinforced chequered
plate c/w lifting hooks**

g) Top hung glass windows


casement
MN
 ___ Nos 1800mm x 600mm to
conform with drawings

h) Ceiling
MN
 Reinforced concrete roof slab

4. a) 1500mm (h) 13 Amp power


point - tagging to follow
Electrical fittings (incl. Testing &

schematic ( Nos); test for each MJ


electrical socket using ELCB &
Socket Tester
Commissioning)

b) 2 x 23W (min) ceiling mounted


LED T8 bare channel c/w
angle/mirror reflector (min.
1000mm away from slot
MJ
opening)
c) 2400mm (h) 2 x 23W (min) wall
mounted LED T8 bare channel
c/w angle/mirror reflector

Page 2 of 5
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 4 : CIVIL – CONTROL ROOM

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

d) __ nos 13W emergency light MJ

e) "KELUAR" sign at every exit door MJ

5. a) __ nos min. 2.0 kg portable


Commission
Testing &
Fighting

carbon dioxide (CO2) fire


System
(incl.

ing)
Fire

extinguishers c/w demarcation MJ


line*, labelling/tag & BOMBA
certificates

6. a) Air-Cond DB - marked with the


yellow line at the floor c/w
Air Conditioning System (incl. Testing & Commissioning)

MN
Laminated Schematic Diagram
DB / Sub-DB

b) Wall mounted on external wall


type (2.5HP/3.0HP/5.0HP) to
reach 24°C internal
temperature, 50% relative
humidity
c) __ nos of air-conditioning split
unit designed for alternate
operation, 12 hours interval
d) Aircond tray

e) Numbering Material for


Air-conditioning split unit
MN
 Indoor unit - signage number
Outdoor unit - black paint

f) To provide remote control each


MN
room

7. a) 50mm x 6mm copper tape MJ


Earthing System

Commissioning)
(incl. Testing &

b) Min. 2 points exposed copper


MJ
tape at 33 kV slot

c) Min. 2 points exposed copper


MJ
tape at 11 kV slot

Page 3 of 5
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 4 : CIVIL – CONTROL ROOM

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

d) Cadweld / brazed joints*** MJ

8. a) "UTAMAKAN KESELAMATAN"
sign – green colour (lettering) white MN
Signage
Safety

(background)

b) CPR signage – DRABC MN


*Demarcation line– wall (Red & White – 50mm) & floor (Yellow - 100mm with 200mm spacing diagonals at 45°)
**Underside of chequered plate to be welded with 25 x 25mm mild steel angle iron stopper
***To be witnessed and verified by TNB during construction

Page 4 of 5
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 4 : CIVIL – CONTROL ROOM

RESULT

DISTRIBUTION FACILITY: PMU/PPU/SSU

DATE:

CONCLUSION:

 PASS  FAIL NO. OF NON-COMPLIANCE :


(If minor non-compliance/s) (If any major non-compliance)

COMMENT :

AUDITED BY
NAME : SIGNATURE :

 ALL DEFECT/S CLEARANCE VERIFIED (IF APPLICABLE)

VERIFIED BY
NAME : SIGNATURE & DATE :

Note : Project Manager is required to scan & email this page to Project Design, Asset Development Unit within 5 days of SCA
completion date.

Page 5 of 5
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 6 : CIVIL – BATTERY ROOM

BATTERY ROOM INSPECTION CHECKLIST

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1. a) 1000mm x 2100mm (h) ± 5% 2


(Inside building)
Entrance Door

hours fire rated single leaf door


c/w rubber skirting MN
b) BOMBA tag and certificates
c) Door closer

d) Room signage MN

2. a) 1000 x 2100mm (h) ± 5% 1 hour


fire-rated solid mild steel door MN
c/w rubber skirting

b) Fitting - latch & hasp c/w lock


Exit door

MN
protector

c) Danger signage MN

d) No entry signage MN

e) Room signage MN

3. a) Floor finish
MJ
 Acid resistant floor tiles

b) Wall finish
 2100mm (h) acid resistant tiles
Structural & Finishes

 Above 2100mm (h), white MJ


emulsion paint – ICI or
equivalent

c) 200mm x 500mm ± 5%
 Slot covered with c/w 6mm
MJ
thick reinforced chequered
plate c/w lifting hooks**

d) 400mm(16”) Ø exhaust fan c/w


suitable netting/ adjustable MJ
shutters

Page 1 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 6 : CIVIL – BATTERY ROOM

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

e) Aluminium louvres c/w anti-


vermin netting (both sides)

f) Ceiling
MJ
 Reinforced concrete roof slab

4. a) 560 x 360 x 235 mm ± 20mm


Ceramic lab type c/w MJ
gooseneck tap
Wash hand basin

b) 18” x 18” mirror c/w aluminium


MN
frame

c) Stop cock – nearby wash hand


MJ
basin

d) Direct water supply MJ

5. a) 13 Amp power point - tagging to


follow schematic ( Nos); test
MJ
for each electrical socket using
Electrical fittings (incl. Testing &

ELCB & Socket Tester

b) 2 x 23W ceiling mounted LED T8


Commissioning)

bare channel anti-corrosive type MJ

a) Switches for lamp and exhaust


MJ
fan – outside batt. room

b) __ nos 13W emergency light MJ

c) "KELUAR" sign at every exit


MJ
door

Page 2 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 6 : CIVIL – BATTERY ROOM

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

6. a) __ nos min. 2.0 kg portable


Fighting

carbon dioxide (CO2) fire


System
Fire

extinguishers c/w demarcation MJ


line*, labelling/tag & BOMBA
certificates

7. a) 50mm x 6mm copper tape MJ


System (incl.
Testing &
Earthing

b) Earth bar MJ

c) Cadweld / brazed joints*** MJ


*Demarcation line– wall (Red & White – 50mm) & floor (Yellow - 100mm with 200mm spacing diagonals at 45°)
**Underside of chequered plate to be welded with 25 x 25mm mild steel angle iron stopper
***To be witnessed and verified by TNB during construction

Page 3 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 6 : CIVIL – BATTERY ROOM

RESULT

DISTRIBUTION FACILITY: PMU/PPU/SSU

DATE:

CONCLUSION:

 PASS  FAIL NO. OF NON-COMPLIANCE :


(If minor non-compliance/s) (If any major non-compliance)

COMMENT :

AUDITED BY
NAME : SIGNATURE :

 ALL DEFECT/S CLEARANCE VERIFIED (IF APPLICABLE)

VERIFIED BY
NAME : SIGNATURE & DATE :

Note : Project Manager is required to scan & email this page to Project Design, Asset Development Unit within 5 days of SCA
completion date.

Page 4 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 7 : CIVIL – METER ROOM

METER ROOM INSPECTION CHECKLIST

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1. a) 1000 x 2100mm (h) ± 5% 1


hour fire-rated solid mild
MN
steel door c/w rubber
skirting
Entrance door

b) Fitting - latch & hasp c/w


lock protector (outside the MN
room)

c) Danger signage MN

d) No entry signage MN

e) Room signage MN

2. a) Ramp at entrance c/w black


MN
& yellow demarcation line

b) Floor hardener MN

c) Floor finish
 Green epoxy paint
MN
(Nippon EA-4 Evergreen
Structural & Finishes

1461)

d) Cable slot covered with c/w


6mm thick reinforced
MN
chequered plate c/w lifting
hooks**

e) Wall finishes
 2100mm (h) white
MN
emulsion paint – ICI or
equivalent

f) Ceiling – reinforced
MN
concrete roof slab

Page 1 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 7 : CIVIL – METER ROOM

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

g) (Ventilation
block/aluminium lourves)
c/w stainless steel anti- MJ
vermin netting fixed on
both sides

3. a) 1500mm (h) 13 Amp power


point - tagging to follow
schematic ( __ nos); test for MJ
each electrical socket using
ELCB & Socket Tester

b) 2 x 23W ceiling mounted


Electrical fittings (incl. Testing & Commissioning)

LED T8 bare channel c/w


angle/mirror reflector (min. MJ
1000mm away from slot
opening)

c) 400mm(16”) Ø exhaust fan


c/w suitable netting/ MJ
adjustable shutters

d) Aluminium louvres c/w


anti-vermin netting (both MJ
sides)

e) __ nos 13W emergency


MJ
light

f) "KELUAR" sign at every exit


MJ
door

g) Lux of lighting ( min. 400


MJ
lux )

Page 2 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 7 : CIVIL – METER ROOM

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

4. a) __ nos min. 2.0 kg portable


Fire Fighting

carbon dioxide (CO2) fire


System

extinguishers c/w
MJ
demarcation line*,
labelling/tag & BOMBA
certificates
*Demarcation line– wall (Red & White – 50mm) & floor (Yellow - 100mm with 200mm spacing diagonals at 45°)
**Underside of chequered plate to be welded with 25 x 25mm mild steel angle iron stopper

Page 3 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 7 : CIVIL – METER ROOM

RESULT

DISTRIBUTION FACILITY: PMU/PPU/SSU

DATE:

CONCLUSION:

 PASS  FAIL NO. OF NON-COMPLIANCE :


(If minor non-compliance/s) (If any major non-compliance)

COMMENT :

AUDITED BY
NAME : SIGNATURE :

 ALL DEFECT/S CLEARANCE VERIFIED (IF APPLICABLE)

VERIFIED BY
NAME : SIGNATURE & DATE :

Note : Project Manager is required to scan & email this page to Project Design, Asset Development Unit within 5 days of SCA
completion date.

Page 4 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 8 : CIVIL – TOILET, GUARD HOUSE, ROOFING & OTHERS

TOILET INSPECTION CHECKLIST

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1. Floor finishes - floor tiles MJ

2. Wall finishes - wall tiles full height MJ

3. Mild Steel Door - 900mm x 2100mm ± 5% MJ

4. Windows – 600mm x 300mm aluminium MJ


louvres

5. Room sign MJ

6. Sanitary fitting squat-type MJ

7. Ceiling – reinforced concrete roof slab MJ

8. Switches MJ

9. 2x23W ceiling and wall mounted LED T8 MJ

10. Wash hand basin MJ

11. Mirror 18” X 18” MJ

Page 1 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 8 : CIVIL – TOILET, GUARD HOUSE, ROOFING & OTHERS

GUARD HOUSE INSPECTION CHECKLIST

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1. Floor finishes - floor tiles MN

2. Wall finishes – white emulsion paints MN

3. Mild steel Door - 900mm x 2100mm(h) ± 5% MN

4. Table and chairs MN

5. Windows c/w awning MN

6. Room sign MN

7. Ceiling - Reinforced concrete MN

8. a) Switch for lamp and fan MN


Electrical fittings (incl. Testing

b) 2 nos 13 Amp power point MN


& Commissioning)

c) 2 x 23W ceiling LED T8 MN

d) 13W emergency light MN

e) Fan (wall) MN

f) DB for compound lighting MN

Page 2 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 8 : CIVIL – TOILET, GUARD HOUSE, ROOFING & OTHERS

ROOFING INSPECTION CHECKLIST

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1. Roof finishes –
MJ
0.48mm thick clip-lock metal decking

2. Roof truss – lightweight steel MJ

3. Roof slab – Reinforced Concrete MJ

4. Water proofing membrane with 5 years


MJ
warranty certificate

5. Gutter – Reinforced concrete MJ

OTHERS

Defect Clearance Category


Not
No. Description Pass Fail Verification MJ :Major
Applicable
(Sign. & Date) MN :Minor

1. Warranty of building/equipments in
MJ
condition construction work in progress

2. Lifting hook for chequer plate (if required) MN

3. Water Supply (including water meter) MN

4. Substation key – with labeling and spare MN

Page 3 of 4
APDV-5005-PSI PRECOMMISSIONING, INSPECTION AND TESTING (PIAT) CHECKLIST

ATTACHMENT 8 : CIVIL – TOILET, GUARD HOUSE, ROOFING & OTHERS

RESULT

DISTRIBUTION FACILITY: PMU/PPU/SSU

DATE:

CONCLUSION:

 PASS  FAIL NO. OF NON-COMPLIANCE :


(If minor non-compliance/s) (If any major non-compliance)

COMMENT :

AUDITED BY
NAME : SIGNATURE :

 ALL DEFECT/S CLEARANCE VERIFIED (IF APPLICABLE)

VERIFIED BY
NAME : SIGNATURE & DATE :

Note : Project Manager is required to scan & email this page to Project Design, Asset Development Unit within 5 days of SCA
completion date.

Page 4 of 4