Project:
Customer:
Consultant:
SUTEK
Unrestricted
______________________________________________________________________________________________________________________________________
We reserve the rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly
forbidden. © SIEMENS Ltd.
2 of 18 62OP42338_U1_625040018 Rev.-
Ø CONSULTANT: SUTEK
Ø GEARBOX: TRIVENI
OPERATING CONDITIONS:
_________________________________________________________________________________________________________________________________
_____
Format No.: IP-Q-F-3009/C
Rev.Date : 30.03.2010
Page: Document No. Rev.No.
3 of 18 62OP42338_U1_625040018 Rev.-
OPERATION PHILOSOPHY:
Motor driven main & auxiliary oil pumps are provided for the use during starting or shutting
down or barring operation or when the oil header pressure is low. It is directly driven by an
electric motor and the combined unit is mounted on the lube oil skid.
Start Permissive
Ø Drive remote selected
Manual Start
Ø Through soft PB when drive is in Manual mode
Manual Stop
Ø Through soft PB when drive is in Manual mode
Auto Start
Ø Lube/Control oil header pressure low OR
Ø Standby drive Feeder Fault OR
Ø Standby drive not running
Auto trip
Ø Feeder Fault [Overload, Switchgear fault etc]
_________________________________________________________________________________________________________________________________
_____
Format No.: IP-Q-F-3009/C
Rev.Date : 30.03.2010
Page: Document No. Rev.No.
4 of 18 62OP42338_U1_625040018 Rev.-
OPERATION PHILOSOPHY:
An Emergency Oil Pump driven by DC Motor is provided. When all sources of oil supply fail, the
emergency oil pump ensures supply of oil to bearings during coasting down period. This is the
reason why this pump is connected to the bearing oil circuit without passing through the oil cooler
and filter in order to ensure positive supply of oil to the bearings.
Manual Start
Ø Through soft PB when drive is in Manual mode
Manual Stop
Ø Through soft PB when drive is in Manual mode AND
Ø Lube oil header pressure not low low (NORMAL) OR
Ø Turbine speed =<20rpm (STAND-STILL)
Auto Start
Ø Lube oil header pressure low low OR
Ø Lube oil header pressure low low AND Turbine speed =>20rpm
Auto trip
Ø Not provided
EOP can be stopped by pressing any one of the stop push buttons provided on the DCS or DC
Starter Panel near the drive irrespective of the mode of selection.
Ø In case of Speed is >20rpm and Lube oil pressure is low low irrespective of mode selection
in DCS, EOP will automatically start and cannot be stopped until the pressure becomes
normal or turbine speed come to standstill.
Ø Lube oil pressure low low – <1.8kg/cm2 (switch) is directly connected to DC starter panel
start
_________________________________________________________________________________________________________________________________
_____
Format No.: IP-Q-F-3009/C
Rev.Date : 30.03.2010
Page: Document No. Rev.No.
5 of 18 62OP42338_U1_625040018 Rev.-
Operation Philosophy:
During Turbine operation when either of the MOP, AOP or EOP is supplying lube oil to all the
bearings. Due to the oil circulation and heat taken away by the oil from the bearing, vapour
formation occurs inside the lube oil tank. This creates a positive pressure above the oil level,
which may cause restrictions for the proper oil circulation. As it is necessary to remove the vapour
from the tank and to create slight negative pressure, oil vapour extractor fans are provided. This
also prevents leakages from the bearings baffle rings.
Start Permissive
Ø Drive remote selected
Manual Start
Ø Through soft PB when drive is in Manual mode
Manual Stop
Ø Through soft PB when drive is in Manual mode
Auto Start
Ø Any of the oil pump is running (MOP, AOP, EOP) AND
Auto trip
Ø Feeder Fault [Overload, Switchgear fault etc]
Protection OFF
Ø MOT level high high (93.61 %)
_________________________________________________________________________________________________________________________________
_____
Format No.: IP-Q-F-3009/C
Rev.Date : 30.03.2010
Page: Document No. Rev.No.
6 of 18 62OP42338_U1_625040018 Rev.-
OPERATION PHILOSOPHY:
Continuous rotation of the shaft with the barring gear prevent the development of temperature
gradients and thus deformation of rotor and the turbine casing and also prevents over heating
of white metal of bearings.
The Barring Gear motor is mounted on the Gearbox with integral gearbox. The shaft can be
rotated manually if required.
Start Permissive
Ø Lube oil pressure >1.95kg/cm2 of the lube oil header pressure
Ø Turbine speed is <20rpm or between 250rpm AND 300rpm
Ø EOP ready OR
Ø Overhead lube oil tank level NORMAL
Manual Start
Ø Through soft PB [if start permissive is available]
Ø Through Local PB [if start permissive is available]
Manual Stop
Ø Through Local PB if Turbine parting flange centre temperature >100deg C OR
Ø Cooling down time >96 hours
Auto trip
Ø Feeder fault [Overload, Switchgear fault etc]
If Barring Gear ON command persists AND barring gear is not started (detected <250rpm OR
>20rpm) then ON condition will be withdrawn after 15sec.
_________________________________________________________________________________________________________________________________
_____
Format No.: IP-Q-F-3009/C
Rev.Date : 30.03.2010
Page: Document No. Rev.No.
7 of 18 62OP42338_U1_625040018 Rev.-
Operation Philosophy:
The GSC system is used for collecting the leakage steam from turbine front and rears glands and
further it condenses the steam with the help of CW passing through it. The condensate shall be
recovered to the hotwell and further to Deaerator or drained to the external drain system
continuously during normal operation.
In order to suck the low-pressure leak steam from Turbine glands, a slight negative pressure that
is around– 0.05kg/cm2 [g] is being created with the help of Vacuum pumps [blowers] which is a
part of GSC system.
Start Permissive
Ø Drive remote selected
Manual Start
Ø Through soft PB when drive is in Manual mode
Manual Stop
Ø Through soft PB when drive is in Manual mode
Auto Start
Ø Turbine speed >200 rpm AND
Auto trip
Ø Feeder Fault [Overload, Switchgear fault etc]
_________________________________________________________________________________________________________________________________
_____
Format No.: IP-Q-F-3009/C
Rev.Date : 30.03.2010
Page: Document No. Rev.No.
8 of 18 62OP42338_U1_625040018 Rev.-
Operation Philosophy:
Lube oil tank is provided with heaters to maintain the lube oil in the recommended temperature to
achieve the best property of oil.
Start Permissive
Ø Drive remote selected
Manual Start
Ø Through soft PB when drive is in Manual mode
Manual Stop
Ø Through soft PB when drive is in Manual mode
Auto Start
Ø Main oil tank temperature <30degC
Auto trip
Ø Main oil tank temperature >35degC
Ø Feeder Fault [Overload, Switchgear fault etc]
Protection OFF
Ø Main oil tank temperature >65degC
_________________________________________________________________________________________________________________________________
_____
Format No.: IP-Q-F-3009/C
Rev.Date : 30.03.2010
Page: Document No. Rev.No.
9 of 18 62OP42338_U1_625040018 Rev.-
Ø PF mode ON
Ø PF mode OFF
Ø Excitation ON
Conditions: Turbine speed >95% of rated
Ø Excitation OFF
Ø Excitation MANUAL mode enabled
Ø Excitation AUTO mode enabled
_________________________________________________________________________________________________________________________________
_____
Format No.: IP-Q-F-3009/C
Rev.Date : 30.03.2010
Page: Document No. Rev.No.
10 of 18 62OP42338_U1_625040018 Rev.-
Reference documents : P&ID, TG Logics, I/O List, Schematics of Turbo Supervisory Panel &
Generator Protection Panel
The Turbine will trip due to any of following fault conditions as listed below
11 of 18 62OP42338_U1_625040018 Rev.-
_________________________________________________________________________________________________________________________________
_____
Format No.: IP-Q-F-3009/C
Rev.Date : 30.03.2010
Page: Document No. Rev.No.
12 of 18 62OP42338_U1_625040018 Rev.-
The function of the turbine safety system is first to trigger an alarm, then in a second step to trip
the STG unit automatically when the safety limits are reached. The Control System is based on
the Fail Safe philosophy. All the field parameter for Turbine Trip Logic is taken in Healthy condition
[Logic=1]. The List of Signals is mentioned above. The Power Contactors will be in Energised
condition for continuous operation of the Turbine. During Emergency condition, Emergency Trip
Push Button is provided in Turbo Supervisory Panel for tripping the Turbine. Apart from this a Soft
emergency PB is also provided in Control System HMI to trip the turbine in case of emergency.
Trip Solenoids can be operated through Turbo Supervisory Panel one at a time and functional test
can be accomplished. If any of the Above Parameter reached to respective set points [refer I/O list
for details], the Turbine is tripped, i.e. Power contactors of solenoids get de-energised, which
finally trips the Turbine, Excitation and Generator Breaker.
The Turbine [ESV through safety block] & Governor [Emergency shut down signal] can be reset
after clearing all fault condition from Control System if the following conditions are fulfilled.
_________________________________________________________________________________________________________________________________
_____
Format No.: IP-Q-F-3009/C
Rev.Date : 30.03.2010
Page: Document No. Rev.No.
13 of 18 62OP42338_U1_625040018 Rev.-
This tripping shall come in to operation 10min after the generator breaker is closed.
The main steam temperature value is monitored for its rate of change with respect to time. If this
rate of change is more than 3degC/min, an alarm is generated in DCS.
If the rate of change is more than 5degC/min then the turbine should trip if the rate of change
continues for a rise of 50degC.
Refer curve 0-20410-E41472A-10 for main steam temperature low low trip.
The set point for turbine trip will be as per the given curve.
Refer curve 0-20410-E41472A-18 for turbine exhaust pressure high high trip.
Note: The considered altitude above Mean Sea Level is 0 meter.
Turbine live steam pressure should not exceed the 120% of rated pressure, if it exceeds 120% of
rated pressure, immediately tripping is required.
Also accidental swings 105% to 120% of rated inlet steam pressure are permitted, provided that
the duration of such swings over a period of any 365days of turbine operation does not exceed 12
Hrs.
Also, in conditions of average pressure exceeding the permitted pressure for more than 12 hours,
turbine trip is will switch to 105% of rated pressure from 120% of rated pressure.
As per IEC 45-1, Turbine live steam temperature should not exceed the Trated+ 28 Deg’C , if it
exceeds immediately tripping is required.
Also, accidental swings of Trated+ 8 Deg’C to Trated+14 DegC are permitted provided that the
duration of such swings over a period of any 365 days of turbine operation does not exceed
400hrs.
Also, accidental swings of Trated+ 14 Deg’C to Trated+ 28 DegC are permitted provided that this
swing should not exceed for more than 15 min in a single swing/ operation and the duration of
such swing over a period of any 365 days of turbine operation does not exceed 80 hrs.
If any accidential swing mentioned above crossed the time limit, the tripping limit of turbine switch
from Trated+ 28 Deg’C to Trated+ 8 Deg’C
Note: For more details please refer O&M Manuals of respective equipment or system.