OHE/ PSI DEPOT

GAD NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS.


2. THIS DRAWING IS BASED ON CEE/CORES APPROVAL ON 25-12-92 VIDE PP NO 3 OF FILE NO CORE
/EL/SER - BLDG - 109.
3. THE FLOOR OF TOILET SHOULD BE 25MM LOWER THAN MAIN FLOOR.
4. ONE WATER STORAGE TANK (CAPACIY 1000LIT) TO BE PROVIDED OVER THE ROOF OF TOILET WHERE
WATER SUPPLY IS AVAILABLE& A SEPTIC TANKSHOULD ALSO BE PROVIDED AS PER TYPE PLAN OF
ZONAL RAILWAYS WHERE SEWER LINE IS NOT AVAILABLE.
5. WHERE WATER SUPPLY IS NOT AVAILABLE AQUIA PRIVY TO BE PROVIDEDAS PER TYPE PLAN OF ZONAL
RAILWAYS – NA
6. PRESSED STEEL FRAME FOR DOORS TO BE PROVIDED AS PER DRG NO RE / CIVIL /S-129 / 2001R2.
7. GLAZED STEEL WINDOW TO BE PROVIDED.
8. PVC DOORS TO BE PROVIDED IN TOILET.
9. FOR DETAILS OF ROOF TRUSS REFFER DRG NO RE / CIVIL / 27/ 81.
10. ALL INTERNAL & EXTERNAL WALLS SHALL BE 13TH CEMENT PLASTERED (1:6)
11. INTERIOR SURFACE OF WALLS SHALL BE WHITE WASHED & EXTERNAL SURFACEOF WALLS SHALL
BEPROVIDED WITH SNOWCEM.
12. THE FOUNDATION HAS BEEN DESIGNED FOR …T/M² SAFE BEARING CAPACITY WHICH MAY BE
ALTERED BY ENGINEER IN CHARGE AS PER SITE CONDITION.

FOUNDATIONS:

13. CEMENT CONCRETE M7.5 IN FOUNDATION WITH 40mm GRADED STONE AGGREGATE TO
BEPROVIDED
14. IN EXPANSIVE SOIL WHERE PILE FOYUNDATION IS DESIRABLE, THE CASE MAY BE REFERRED TO
HEAD QUARTERS OFFICE FOR PROPER DESIGN MENTIONING THENATURE, STRATA AND LOAD
BEARAING CAPACITY OF SOIL.
15. ALL STEEL WORKSHOP SHALL BE PAINTED WITH TWO COATS OF REDY MIXED PAINT OF APPROVED
QUALITY AND, SHADE WITH RED OXIDE PRIMER.
16. ALL R.C.C. WORK SHALL BE DONE IN I.S 456-2000 FOR PLAIN & R.C.C. IN GRADE M-15 & M-20.
17. MANSORY: SUPPERSTRUCTURE SHALL BE IN CEMENT MORTAR 1:6 WITH WELL BURNT BRICKS EXCEPT
115Th WALL WHICH SHALL BE IN CEMENT MORTAR 1:4 WITH WELL BURNT BRICKS. –
18. D.P.C.:40mm Th C.C. M-15 WITH GRADED STONE CHIPS MIXED WITH WATER PROOFING
COMPOUND OF APPROVED QUALITY & MAKE AND 2 COATS OF COAL TARRING ON TOP.
19. FLOORING: 100 mm Th .BASE CONCRETE M-15 TO BE PROVIDED IN ALL ROOM & VERANDAH EXCEPT
WORKSHOP OVER WELL CONSOLIDATED EARTH INCLUDING WATERING & RAMMING IN150mm
LAYERS.
I. 40 mm Th. I P S FLOOR FINISHING TO BE PROVIDED OVER BASE CONCRETE IN ALL ROOMS
EXCEPT WORKSHOP & 200 HIGH 19Th SKIRTING TO BE PROVIDED TO ALL WALLS EXCEPT
TOILETS WHERE DADO TO BE PROVIDED TO A HEIGHT OF 1200 FROM FLOOR LEVEL WITH
6mm Th WHITE GLAZED TILES AND 20 TH MSAIC TILES FLOORING OVER 80 Th CC M7.5.
II. IN WORKSHOP HEAVY DUTY FLOORING TO BE PROVIDED WITH 15Th HARDONATE
TOPPING OVER 50mm Th CC GRADE M-15 OVER 100mm Th BASE CONCRETE M-10.
20. ROOF WATER PROOFING - SHALL BE PAINTED WITH TWO COATS OF BITUMEN AND ABOVE SCREED
CONCRETING IN 12 MM DOWN AGGREGATES - 25 MM THICK AND ADDED WITH NECESSARY WATER
PROOFING COMPOUND.
21. STAIRCASE STEPS SHALL BE SURFACE OF 2.5 CMTHICK I.P STONE 1:1:3 MIX AND MS HANDRAILS SHALL
BE PAINTED WITH RED OXIDE AND ENAMEL

RCC NOTES IN12 MM DOWN AGGREGATES AND

1. ALL DIMENSIONS ARE IN MILLIMETERS AND ALL LEVELS ARE IN METERS UNLESS OTHERWISE
MENTIONED.
2. N.G.L OF THE PROPOSED STRUCTURE CORESPONDS TO +0.00
3. ALL RCC WORKS TO BE DONE AS PER IS: 456-2000, IS:13920.
4. REINFORCED CONCRETE IS OF GRADE M-20 AND SHOULD CONFORM TO I.S. 456-2000.IT SHOULD
BE ENSURED THAT ONLY DESIGN MIX IS USED.
5. COARSE AGGREGATE FOR CONCRETE SHALL CONSIST OF HARD CRUSHED GRANITE STONE OF
MAXIMUM SIZE 20mm AND SHALL BE PERFECTLY CLEANED AND WELL GRADED CONFORMING TO
IS:383 AND IS : 2386.
6. REINFORCEMENTBARSSHALL BE TOR STEEL (Fe-500D GRADE) CONFORMING TOIS:1786.
REINFORCEMENT SHALL BE CLEAN AND FREE FROM OIL, MILL SCALE ETC, SHALL BE BENT COLD
TO THE SHAPES AND DIMENSIONS INDICATED AND SHALL BE PLACED EXACTLY AS SHOWN.
7. ALL INTERSECTIONS OF BARS SHALL BE SECURELY BOND WITH N0.16 GAUGE PLIABLE WIRE.
8. THE LAP LENGTH OF BARS SHALL NOT BE LESS THAN 48Ø.
9. NOT MORE THAN 50 % OF BARS SHALL BE LAPPED AT SAME LOCATION.
10. THE CLEAR DISTANCE BETWEEN LAP AND ANOTHER PAIR OF LAP BARS SHALL NOT BE LESS THAN
1.3Ld
11. ANCHORAGE LENGTH OF BARS SHALL NOT BE LESS THAN 48Ø.
12. CLEAR COVER TO REINFORCEMENT SHALL BE
I) COLUMN =50mm
II) FOOTING = 50mm
III) PLINTH BEAM = 40mm, OTHER BEAMS = 25mm.
IV) SLAB & SUN SHADE = 25mm
13. THE CONCRETE SHALL INVARIABLY BE VIBRATED BY MECHANICAL MEANS
14. THE LEVELING COURSE SHALL BE OF CEMENT CONCRETE OF GRACE M10 USING40MM MAX. SIZE
OF COARSE AGGREGATE OF APPROVED QUALITY.
15. BUILDING FOUNDATION DESIGNED FOR (G+1) ONLY.
16. NET SAFE BEARING CAPACITY OF SOIL AT FOUNDATION LEVEL ASSUMED AS .. T/SQM THE
SAMESHALL VERIFIED AT SITE BEFORE EXECUTION.
17. STIRRUPS SHALL BE ENCLOSED BY STANDARD 135° HOOK WITH EXTENSION OF 10D OR 75 WHICH
EVER IS MAXIMUM.
18. SPACER BARS DIAMETER SHOULD BE MAXIMUM OF THE DIAMETER OF THE BARS BETWEEN
WHICH IT IS PLACED.THEY SHOULD BE PLACED AT 1000mm C/C.