You are on page 1of 6

Solar Energy Vol. 22, pp. 113-118 0038--092XH9/0201-0113/$02.

00/0
© Pergamon Press Ltd., 1979. Printed in Great Britain

DESIGN CONSIDERATIONS FOR RESIDENTIAL


SOLAR HEATING AND COOLING SYSTEMS
UTILIZING EVACUATED TUBE SOLAR COLLECTORS

DAN S. WARD? and JOHN C. WARD:[:


Solar Energy ApplicationsLaboratory, Colorado State University, Fort Collins,CO 80523, U.S.A.

(Received 14 May 1977; revisionaccepted 7 July 1978)


hlmtraet--As solar heating systems become a commercial reality, greater efforts are now being employed to
incorporate solar coolingcomponents in order to obtain a complete solar heating and coolingsystem and thus take
advantage of the cost-effectiveness of year-round use of the solar equipment. Because of the exceptional
performance and high efficiency of evacuated tube solar collectors, these advanced collectors are receiving
considerable attention for use in solar heating and cooling systems. While improved performance is readily
obtained with these sophisticatedsolar collectors,there are also numerous difficultiesand problemsassociated with
their use in a solar system. This paper addresses many of the design considerationswhich must be included in any
realistic solar system design. Most of the considerationspresented here are based on the experience gained in the
design and performance of the solar heating and cooling systems for CSU Solar Houses I-IV.

INTI~DDOCTION under good solar conditions) than does snow or ice on


The addition of a solar cooling capability to a solar space flat-plate collectors. This is due to the much lower heat
a n d domestic hot water (DHW) heating system allows losses from the absorber of the evacuated tube collector
for a substantially improved usage of the solar collector and the corresponding lower temperature of the glass
array and the associated components of the solar sYstem. cover.
Year-round usage gives greater cost-effectiveness of the In addition, the greater strength and durability of a
solar equipment because of greater cost savings on con- cylindrical glass tube over a sheet of flat glass means that
ventional fuels in return for a relatively small additional wind and hail would be much less of a threat to the
initial capital investment. An integrated solar heating and structural integrity of an evacuated glass tube. And,
cooling system (including DHW heating) is expected to because of the lower cover temperature of the evacuated
achieve a much lower cost per unit energy than a solar tube, the wind will have less effect on the efficiency of
space and DHW heating system in most areas of the the collector.
continental United States[l]. A solar heating and cooling system design must,
Ward [2] has shown that solar cooling would typically therefore, be capable of utilizing the inherent advantages
provide a nearly constant per cent of the summer cooling of evacuated tubes and diminishing the effects of the
load on a daily basis (with auxiliary providing the inherent disadvantages of these advanced collectors.
balance each day), whereas heating is usually 100 per
cent on most days (no auxiliary use), and largely auxili- EVACUATEDTUBESOLARCOLLECTORS
ary on 20--30 days during the heating season. The use of Evacuated tube solar collectors permit the use of a
evacuated tubular solar collectors permits the collection vacuum of sufficient magnitude to virtually eliminate
of solar energy at lower solar radiation levels (about convection and conduction heat transfer losses. In ad-
0.14 kW/m2 vs 0.25-0.30 kW/m2 for flat-plate collectors-- dition, these collectors generally require a minimum
see Ref.[3]), and thus provides solar energy for heating amount of material per m 2 of collector and thus provide
and cooling earlier in the morning and later in the even- for the possibility of lower costs (under conditions of
ing. This increases the availability of solar radiation large scale manufacturing processes). Finally, the
during those periods of load demand. vacuum may help to protect a selective surface used on
The particular characteristics of the evacuated tube the absorber (for reduction of long-wave radiation heat
solar collectors also play an important part in overall losses) against performance degradation over the life of
system design. For example, because of the geometrical the collector.
shape of evacuated glass tube solar collectors, snow The performance of these evacuated glass tube solar
removal requires longer melting periods than conven- collectors can be represented (for steady-state condi-
tional flat-plate solar collectors because snow slide-off is tions) by the standard equation:
generally impeded by the tubular design. Observations at
CSU Solar Houses I and III have shown that snow and
, = F,~(¢a)- F,~UL( ~ ) (t)
ice remain on the evacuated tubes much longer (6-10 hr

tAssistant Professor of Civil Engineeringand Physics. where ~ is the solar collector efficiency (dimensionless),
~;Professor of Civil Engineering. FR(¢a) is solar collector efficiency when (T~- To) = 0,
113
114 D. S, WARDand J. C. WARD

UL is a function of the various heat transfer coefficients into eqn (2) gives
applicable to a particular collector (kJ/[hr][m2][°C]), T~ is
the inlet fluid temperature (°C), To is the outdoor air (2b)
T~(Tio - 273°K - To) = (ra)HR
3
C
temperature (°C), and (HR) is the solar radiation on the
collector (Ll/[hr][m2]).
For comparison purposes, values of FR(¢a) and FRUL The solution of eqn (2b) for Tea is by trial-and-error. For
are given in Table 1 for several different kinds of solar example, for the Owens-Illinois evacuated tube solar
collectors. Equation (1) can also be used to estimate the collector, if one assumes that the value of UL reported in
maximum temperature that may be reached during equil- Table 1 corresponds to 100°C, then from eqn (2a):
ibrium conditions and when there is no flow of coolant
fluid through the collector loop. Under these conditions, C= 6.92 x 10-9 kJ
= 0 and eqn (1) reduces to: (hr)(me)(°K4)

Ti HRO'a) " ,l - l ,,. for this particular solar collector. A stagnation tempera-
~ a (2)
" UL " ture of 555°K has been observed for this collector when
Ta = 21°C and HR = 3088 kJ/(hr)(m2). Substituting these
It will be noted that the values of F,O'a) (column 5 of values of T, and HR into eqn (2b) along with the value
Table 1) are higher and the values of FaUL (column 6 of of 0"a)=0.837 (F~ ---0.95), a trial-and-error solution
Table 1) are lower for the evacuated glass tube solar gives T~o= 536°K, a result that is within 4 per cent of the
collectors compared to the other more conventional observed value. For values of (T~-Ta)IHR>-O.033
(concentration = 1) flat-plate solar collectors listed, and (hr)(m2)(°C)lLl, both evacuated glass tube solar collec-
as a result, their equilibrium (no flow) temperatures are tors have a higher efficiency than the concentrating
also much higher. However it is important to realize that (concentration = 10) solar collector that tracks the sun.
heat losses from evacuated glass tube solar collectors are One evacuated glass tube solar collector design also
dominated by thermal radiation. In this case, UL in- has a significant heat capacity, (cW) [kJ/(°C)(m2)], when
creases with the third power of the absolute temperature used as a liquid heater. For a weight per unit area (W) of
of the absorber, and, because the equilibrium (no flow) 19.6 kg/m2 when dry and 34.2 kg/m 2 when filled with water
temperature of evacuated glass tube solar collectors are [specific heats (c) of water and glass are, respectively, 4.18
so high, substantial increases in the value of UL can be and 0.836 kJ/(hr)(°C)], the value of (cW) for the Owens-
expected. If we assume that: Illinois collector is 77.6 kJ/(°CXm2).
We may note the effects of a large heat capacity by the
uL CT~o
= (2a) following. Let Q, represent the heat delivered by the
collector in kJ/(me)(hr). Then:
where C = a constant, kJ/(hr)(m2)(°K4), and
Q'-F~(Ta)
T,o = T~+ 273°K = absolute inlet fluid temperature, °K.
- , ~. .u , /T,-To~ . /ATdAt\
) (3)

Substituting eqn (2a) and the above expression for T~ where AT~ is the change in collector inlet fluid tempera-

Table 1. Typical values of FR(¢a)and FRULfor several different kinds of collectors

FRUL
Type of Solar Concen- FR(.~a) kJ
Manufacturer Collector Fl ui d tration
(hr) ( m ~
(1) (2) (~) II (4) (s} (6)
Fresnel lens 10 0.845
(tracking mode) Liquid 6.16
Northrup
Fresnel lens
{non-trackinq mode) Liquid 4 0. 859 9.67
General Electric 2 Lexan cover plates 1 O. 751
(selective surface) Liquid 13.10
'T
CSU Observed ** Liquid 1 0.660 17.30
(Solar House I)
Theoretical Liquid 1 0.730 12.00
Sol aron Observed Air 1 0.637 13.20
(Solar Houses II
and IV) Theoretical Air 1 O. 700 "14.60
Ametek Selective surface, ? Liquid
1 O. 770 12.90
qlass cover plates
Corning
olar House I) Evacuated glass tube!Liquid
1 0.810 5.10
i|l
ens-lllinois
(Solar House I I I ) Evacuated glass tube Liquid 1 0. 791 3.59
**Based on an ex )erimental test module whose sides were not insulated
Design considerations for residential solar heating 115
ture (°C) during the time interval At, and At is the time water-glycol in evacuated tube solar collectors are the
interval (hr). potential for freezing and boiling. The freezing problem
For the Owens-Illinois collector, eqn (3) becomes: is relatively easy to avoid by using a liquid with a
sufficiently low freezing point. If an ethylene glycol
( A T.JAt'~ water mixture is used, sufficient ethylene glycol must be
ZH R = 0"791- 3"59 ( ~ ) - 77"6 \ - - H - R ] ' (4, added to permit flow under all conditions. It is possible
to use lower concentrations of ethylene glycol than that
The effect of this large heat capacity can be seen if we specified by the manufacturer to prevent damage to the
consider the conditions of T~ = 500C; T~ = -10*C; and T~ collector, but flow will not be possible. This, however,
(T~ at a time At = l hr before)=-10*C. Then eqn (4) leads to the extremely dangerous situation where the
becomes: liquid in the collector reaches the boiling point, but the
lines leading to the collector are still frozen sufficiently to
Q, = 0.791 H R - 215.4 kJ/(m2)(hr) - 4656 kJ/(m2)(hr). prevent flow. Experience dictates that solar collector
systems should not be used in a freezing climate with
A study of the second and third terms on the right side any liquid whose freezing point is above any air
of this equation demonstrates the significance of the temperatures that might be encountered.
energy required to heat the evacuated tube collector to While the use of ethylene glycol or other non-freezing
operating conditions in relation to the steadystate heat liquid may solve the freezing problem, the potential for
losses, i.e. heat losses from the collector constitute less power failures over the life of the system virtually assure
than five per cent of the energy required to "warm up" numerous opportunities for boil-off of the collector
the collector. Of equal significance is the fact that most liquid. In many cases the violent boiling conditions may
of the heat stored in the solar collector when it ends its damage or destroy the solar collector (thermal shock,
daily operation will be lost overnight. excessive vibration of the absorber within the glass tube,
There are several variations in the design of evacuated etc.), but in all cases the liquid must be replaced. If
tube solar collectors; in addition to the Coming and provisions are not made to recover the boiling liquid, this
Owens-Illinois collectors, which are utilized in CSU recurring cost penalty can be an additional disadvantage
Solar Houses I and III, respectively, both General Elec- of liquid-heating evacuated tube solar collectors.
tric and Philips (Germany) have done considerable Finally, the equilibrium (no flow) temperatures of al-
research into particular designs. While the differences in most any reasonably well designed solar collector will
design are significant, there are also several noteworthy exceed the boiling point of water and water-ethylene
similarities. All utilize a liquid (usually water or water- glycol mixtures. In addition, the equilibrium (no flow)
ethylene glycol) as a coolant liquid, with the inlet and temperatures of evacuated glass tube solar collectors will
outlet of the liquid at the same end of the tube (this latter exceed the boiling points of almost any other heat trans-
aspect simplifies the problem of differences in the ther- fer liquid presently being utilized in solar systems, so
mal expansion of the outer glass tube and the absorber provision for boiling must be provided, regardless of the
surface). In addition, numerous tubes (6-24 per module) heat transfer liquid used. One of the potential disad-
are piped in series to ensure sufficient flow through each vantages of evacuated tube solar collectors is that they'
collector tube (modules are usually in parallel). This may not be able to withstand the high equilibrium (no
provides for the possibility of substantial pressure drop flow) temperatures they develop either during installation
through the collector modules and, consequently, of later during electrical power failures, etc.
significant pumping power. The evacuated tube solar The use of a non-aqueous liquid (to eliminate cor-
collector designs utilized in CSU Solar Houses I and III rosion problems) permits the use of materials consider-
have required more pumping power than is acceptable. If ably less expensive than copper (even copper is not
parasitic power requirements are to be reduced to prac- immune to corrosion in an aqueous environment). But
tical levels, these large pressure drops must be reduced. because the only practical liquid for heat storage is
In general, arranging the collector modules in parallel water, the use of non-aqueous liquids requires a heat
flow patterns (rather than series flow patterns) reduces exchanger between the collector liquid circuit and the
the total pressure drop through the collector array. hot water storage tank, a factor that reduces the overall
However, these parallel flow patterns do require careful solar system efficiency. However, many non-aqueous
design if uniform flow distribution is to be achieved. liquids have boiling points well above those of water or
Experience indicates that attempting to obtain uniform water-ethylene glycol mixtures. This is an important
flow distribution by trial-and-error adjustments of either consideration in the case of evacuated tube solar collec-
valves or dampers is essentially impossible in solar tors because of the possibility of unusually high
collector arrays and, consequently, uniform flow dis- temperatures.
tribution must be designed into the array from the outset. An obvious conclusion to the foregoing is the ad-
And, for evacuated tubes, slight variations in the flow vantages associated with using air as the collector fluid.
through a tube in parallel may easily result in boiling (and Freezing, boiling, and corrosion difficulties are
thus the loss of the usefulness of the tube) because of eliminated. In addition, maintenance costs of air type
the exceptionally low heat loss coefficient of these solar systems are of the order of 1 per cent per yr of the
collectors. initial installed cost[4]. The annual maintenance costs of
Other difficulties associated with the use of water and liquid type solar systems are not likely to be any lower
116 D. S. WARDand J. C. WARD

and, in fact, boil-off, periodic replacement of anti-freeze, Tab~ 2.


corrosion, etc. may indicate higher maintenance costs Auto Valves Coil Circ DHW Fan
'V4 V5 V6'V7 Pump Pum~ Pump
than for air systems. Failure to perform any required
I. Solar c o l l e c t o r On
maintenance may result in a solar system performance storing heat
decline substantially greater than 1 per cent per yr. 2. Space heating A A A A -- On * On
from storage
3. Space heating B A, A B -- On Off On
SOLARHEATINGANDCOOIANGSYSTEMDESIGN from a u x i l i a r y
(LIQUID SYSTEM) 4. DHW heating ....... B A -- On On Off
from storage
Figure 1 is a design schematic for an integrated solar 5. Storage to A B A A -- On * --
chiller
heating and cooling system. It incorporates evacuated 16. A u x i l i a r y to B B A B -- On Off --
tubular solar collectors, a thermal storage unit, an auxil- chiller
iary boiler (for providing conventional heat to the heating • May provide DHW heating in addition to space
coils or to the absorption chiller), heating coils, cooling heating and cooling in these modes
subsystem (see below), automatically actuated 3-way
valves, and a DHW preheat system. The various operat-
ing modes of the system are shown in Table 2. and a slightly lower temperature then reaches the DHW
Part of the design rationale of the system shown in double-walled heat exchanger (approximately 80"C). The
Fig. 1 is minimizing the number of pumps, e.g. the use of utilization of several automatically actuated 3-way valves
a single pump to operate the chiller and at the same time can be easily incorporated into solid-state control
provide heat to the DHW system. Note that the higher schemes and constitute less of a capital investment than
temperature water is delivered to the chiller (e.g. 850C) a multitude of pumps.

.. , -..-- ,
froOOOl
½
J~Check
l]'vo,v.
I Thermal
IS~r~'
]
I ~ .... ,,v,

Circ.
Pump

WoV" lj v....
. 11 L__~.

i II I ~,.,,,.r I , I"o".r ,
"- ' I I " ' J

U A
Supply
Air
Fig. 1. Schematicof solar heating and coolingsystem with evacuated tube solar collector.
Design considerations for residential solar heating 117

COOLING SUBSYSTEMD~IGN The ability of the thermal storage to provide heat to


The design of the cooling subsystem must consider not operate the absorption cooling unit is, as mentioned
only the operating characteristics of the absorption cool- previously, heavily dependent on temperature. Ward[7]
ing unit, but the other components of the solar system as has shown, for example, that an inlet temperature of the
well. For example, if the thermal storage unit is located generator of the absorption unit of 88°C may provide for
within the conditioned space of the building, then any a COP of 0.6 (for cooling water temperatures of 30°C). If
heat losses from the storage will add to the cooling load the inlet temperature is reduced to 80°C, the COP may be
and thus degrade the performance of the total system. reduced to 0.5. On the other hand, if the inlet tempera-
Heat losses from a liquid thermal storage unit can be ture is increased to 96°C, the COP will again be reduced
very substantial and can, in fact, mean the difference because there is no additional cooling with additional
between a successful and an inadequate solar cooling input heat to the generator. In this latter case, the COP
design. Not only do heat losses from storage add to the might be only 0.45. This example emphasizes the im-
cooling load, but they also detract from the ability of the portance of careful design for the operation of the ab-
solar storage to provide heat at sufficiently high sorption cooling unit. Departures from design conditions
temperatures to operate the cooling unit. Jacobsen[5] can significantly reduce the performance of the cooling
and San Martin[6], for example, have described un- unit.
expectedly high energy loss rates from the thermal Such penalties can also be caused by the inlet
storage subsystem. temperatures of the fluid to be cooled, i.e. the building air
While the additional cooling load caused by heat losses (or in the case of an absorption water chiller, the cool
from storage can be eliminated by relocating the thermal water). For a typical lithium bromide absorption water
storage unit exterior to the conditioned space, such chiller, the inlet temperature of the water to be chilled is
losses still reduce the availability of solar heat to operate 14°C and the outlet temperature is 9°C, yielding a COP
the absorption unit. Another difficulty of an exterior of 0.65. However, if the inlet temperature is I I°C, the
installation during the winter heating season is the COP drops to 0.53.
possibility of freezing, the fact that heat losses to the A cooling subsystem design that incorporates these
ambient will be higher because of higher temperature considerations is shown in Fig. 2. This design utilizes two
differences, and the fact that the heat losses will not identically-sized water storage tanks (designated as
contribute to the building's heating load. Because of "warm storage" and "cool storage"), with the total
these considerations, the choice of interior or exterior volume of water in the cooling subsystem equal to the
installations can profoundly affect the overall perfor- volume of one tank. Each of the storage tanks acts as a
mance of the solar heating and cooling system. variable level tank. Operation of the chiller lowers the

[ _ ~ ---~ CT
" ~ Pump
Circulating
Loop

t
i (Generator)

!coo inq I Iv2 I


Coils L-~,

,I A Cool
i-
L___J
i Pump
v3
Fig. 2. Solar cooling subsystem schematic.

SE Vol.22. No. 2--B


118 D. S. WARDand J. C. WARD

water level in the warm storage tank. During the delivery meeting the heating load and summer heat gains would
of cool water to the cooling coils (load), the reverse aid in meeting the cooling load. The heat losses of the
occurs. When both the chiller is operating and cool water exterior tank in summer would be less (due to a lower
is delivered to the cooling load, the levels in the storage temperature difference, i.e. higher ambient temperature)
units remain constant. and would not add to the cooling load.
The use of two variable-level cool storage tanks in-
sures the all-important temperature stratification between CONCLUSIONS
the inlet and outlet sides of the water chiller. In addition, Evacuated tube solar collectors have the same in-
the chiller can he run in a continuous fashion to avoid herent problems associated with conventional liquid-
cycling of the absorption unit under conditions of inter- heating solar collectors: freezing, boiling, corrosion, etc.
mittent load. Finally, the proper use of automatically However, for the evacuated tube collectors, the prob-
actuated 3-way valves allows the use of a single pump lems are usually more severe; it is painfully easy to
for the chiller and cooling load loops. The position of cause boiling in an evacuated tube collector which util-
these valves and status of the cooling subsystem pumps izes aqueous collector liquids. It would appear that an
are detailed in Table 3. air-heating evacuated tube solar collector design could be
Cool storage will undergo some heat gains, and if the of substantially greater value. With the utilization of
cool storage units are located within the conditioned pebble-bed storage at higher temperature levels (e.g.
space, this will constitute a heat removal method and 60°-90°C instead of 20°-60°C), airheating evacuated tube
contribute toward meeting the cooling load. In this solar collector systems could perform better than liquid
respect it is similar to the concept of heat losses from a systems. At these higher temperatures, absorption chiller
thermal hot storage unit reducing the winter heating load. units could utilize solar heated air via an air-to-liquid
In order to take advantage of these two aspects, a heat exchanger.
storage system could be comprised of three water storage
tanks. One tank would be located exterior to the condi- R~C~
tioned space and would be twice the volume of the other
1. G. O. G. Ltf and R. A, Tybout, The design and cost of
two, identically-sized tanks, both of which would be optimized systems for residential heating and coolingby solar
located within the conditioned space. During the winter energy. Proc. ISES Conf., Paris (1973).
heating season, the exterior tank would be empty and the 2. D. S. Ward, T. Weiss and G. O. G. 1.3f, Preliminary per-
two interior tanks would provide a stratified thermal formance of CSU solar house I heating and cooling system.
storage unit for the solar heating system. During the Solar Energy 18(6),541-548 (1976),
3. D. C. Beeldey and G. R. Mather, Analysis and Experimental
summer cooling season, the exterior tank would be used Test of High PerformanceTubular Solar Collectors. Presented
in the cooling subsystem (as described in Fig. 2). Thus at the 1SES Congress, Los Angeles(1975).
winter heat losses of the interior tanks would aid in 4. J. C, Ward and G. O. G. Ltf, Maintenance costs of solar air
heating systems. Proc. 1977 Annual Meeting, Am. Sec. of
Table 3. ISES, pp. 10--2to 10--8(1977).
5. A. S. Jacobsen, Solar heating and coolingof mobile home test
3-way valve results. Proc. ISES Conf., Orlando, Florida (1977).
Mode portions Pumps
6. R. L. San Martin, D. LaPante, C. Parkard and H. Shaw,
V1 V2 #3 Cool CT Twenty months of operating experience with a solar heated
i l l e r operating, storing A B A On On and cooled officebuilding. Proc. 1SES Conf., Orlando, Florida
ool (1977).
i l l e r operating, water to A A A On On
ooling coils 7. D. S. Ward, T. Uesaki and G. O. G. Ltf, Coolingsubsystem
ol storage providing water B A B On Off design in CSU solar house III. Solar Energy 20, 119-126
(1978).

You might also like