You are on page 1of 8

Project Construction of Sewage Treatmeny Plant of Capacity 37 MLD on DBO Basis for UGSS in Tiruchirappalli City Corporation

Document Number 19-EPE-TCC-STP-PTU-STR-001 Prepared Checked Approved Rev


Title Structural Design Calculation of Pre Treatment Unit RKK VJ PS 0

Column CORNER STIRRUPS STIRRUPS


MIDDLE REIN. Prov.
REIN. Ast Prov. REQUIRED PROVIDED
Grid Col. Member DEPTH WIDTH 2 Req Steel
S.No Ast req (mm ) % Pt 2 Steel % Ratio CHECK CHECK
Mark Mark No. (D) (B) req (mm )
Dia Dia Dia Ptprov
(STAAD) Nos Nos Nos DIA. SPACING DIA. SPACING
(mm) (mm) (mm)

C1(Inlet Column) +68.50-73.00

1 C1 161 450 450 412.62 0.20 6 25 4 20 4202 2.08 0.098 SAFE 8 190 8 175 SAFE

2 C1 181 450 450 3089.15 1.53 6 25 4 20 4202 2.08 0.735 SAFE 8 190 8 175 SAFE

3 C1 163 450 450 1620.00 0.80 6 25 4 20 4202 2.08 0.386 SAFE 8 190 8 175 SAFE

4 C1 182 450 450 3932.37 1.94 6 25 4 20 4202 2.08 0.936 SAFE 8 255 8 175 SAFE

5 C1 162 450 450 423.66 0.21 6 25 4 20 4202 2.08 0.101 SAFE 8 190 8 175 SAFE

6 C1 184 450 450 3783.19 1.87 6 25 4 20 4202 2.08 0.900 SAFE 8 300 8 175 SAFE

7 C1 164 450 450 1620.00 0.80 6 25 4 20 4202 2.08 0.386 SAFE 8 190 8 175 SAFE

8 C1 183 450 450 3974.32 1.96 6 25 4 20 4202 2.08 0.946 SAFE 8 255 8 175 SAFE

C2(Screen Column) +68.40-74.60

9 C2 167 300 300 720.00 0.80 4 16 2 12 1030 1.14 0.699 SAFE 8 255 8 175 SAFE

10 C2 185 300 300 720.00 0.80 4 16 2 12 1030 1.14 0.699 SAFE 8 255 8 175 SAFE

11 C2 168 300 300 304.09 0.34 4 16 2 12 1030 1.14 0.295 SAFE 8 190 8 175 SAFE

11 C2 186 300 300 276.62 0.31 4 16 2 12 1030 1.14 0.268 SAFE 8 190 8 175 SAFE

C3(Screen Column) +68.45-74.6

12 C3 171 300 300 451.62 0.50 6 16 1206 1.34 0.374 SAFE 8 190 8 175 SAFE

12 C3 189 300 300 553.05 0.61 6 16 1206 1.34 0.458 SAFE 8 255 8 175 SAFE
Project Construction of Sewage Treatmeny Plant of Capacity 37 MLD on DBO Basis for UGSS in Tiruchirappalli City Corporation

Document Number 19-EPE-TCC-STP-PTU-STR-001 Prepared Checked Approved Rev


Title Structural Design Calculation of Pre Treatment Unit RKK VJ PS 0

Column CORNER STIRRUPS STIRRUPS


MIDDLE REIN. Prov.
REIN. Ast Prov. REQUIRED PROVIDED
Grid Col. Member DEPTH WIDTH 2 Req Steel
S.No Ast req (mm ) % Pt 2 Steel % Ratio CHECK CHECK
Mark Mark No. (D) (B) req (mm )
Dia Dia Dia Ptprov
(STAAD) Nos Nos Nos DIA. SPACING DIA. SPACING
(mm) (mm) (mm)

13 C3 172 300 300 475.33 0.53 6 16 1206 1.34 0.394 SAFE 8 255 8 175 SAFE

14 C3 191 300 300 1085.46 1.21 6 16 1206 1.34 0.900 SAFE 8 300 8 175 SAFE

Detritor Tank(68.45-74.2)

15 C4 133 400 400 1280.00 0.80 4 20 4 16 2061 1.29 0.621 SAFE 8 190 8 175 SAFE

16 C4 104 400 400 1684.72 1.05 4 20 4 16 2061 1.29 0.817 SAFE 8 190 8 175 SAFE

16 C4 255 400 400 789.66 0.49 4 20 4 16 2061 1.29 0.383 SAFE 8 190 8 175 SAFE

16 C4 248 400 400 758.68 0.47 4 20 4 16 2061 1.29 0.368 SAFE 8 190 8 175 SAFE

16 C4 135 400 400 1280.00 0.80 4 20 4 16 2061 1.29 0.621 SAFE 8 190 8 175 SAFE

16 C4 106 400 400 1280.00 0.80 4 20 4 16 2061 1.29 0.621 SAFE 8 190 8 175 SAFE

17 C5 139 350 350 579.81 0.47 4 16 4 16 1608 1.31 0.360 SAFE 8 255 8 175 SAFE

19 C5 110 350 350 553.74 0.45 4 16 4 16 1608 1.31 0.344 SAFE 8 255 8 175 SAFE

18 C5 257 350 350 536.29 0.44 4 16 4 16 1608 1.31 0.333 SAFE 8 255 8 175 SAFE

19 C5 250 350 350 502.79 0.41 4 16 4 16 1608 1.31 0.313 SAFE 8 255 8 175 SAFE

20 C5 141 350 350 980.00 0.80 4 16 4 16 1608 1.31 0.609 SAFE 8 300 8 175 SAFE

21 C5 112 350 350 980.00 0.80 4 16 4 16 1608 1.31 0.609 SAFE 8 300 8 175 SAFE

22 C5 138 350 350 577.69 0.47 4 16 4 16 1608 1.31 0.359 SAFE 8 255 8 175 SAFE
Project Construction of Sewage Treatmeny Plant of Capacity 37 MLD on DBO Basis for UGSS in Tiruchirappalli City Corporation

Document Number 19-EPE-TCC-STP-PTU-STR-001 Prepared Checked Approved Rev


Title Structural Design Calculation of Pre Treatment Unit RKK VJ PS 0

Column CORNER STIRRUPS STIRRUPS


MIDDLE REIN. Prov.
REIN. Ast Prov. REQUIRED PROVIDED
Grid Col. Member DEPTH WIDTH 2 Req Steel
S.No Ast req (mm ) % Pt 2 Steel % Ratio CHECK CHECK
Mark Mark No. (D) (B) req (mm )
Dia Dia Dia Ptprov
(STAAD) Nos Nos Nos DIA. SPACING DIA. SPACING
(mm) (mm) (mm)

23 C5 109 350 350 1156.40 0.94 4 16 4 16 1608 1.31 0.719 SAFE 8 300 8 175 SAFE

24 C5 256 350 350 537.16 0.44 4 16 4 16 1608 1.31 0.334 SAFE 8 255 8 175 SAFE

25 C5 249 350 350 503.55 0.41 4 16 4 16 1608 1.31 0.313 SAFE 8 255 8 175 SAFE

26 C5 140 350 350 980.00 0.80 4 16 4 16 1608 1.31 0.609 SAFE 8 300 8 175 SAFE

27 C5 111 350 350 980.00 0.80 4 16 4 16 1608 1.31 0.609 SAFE 8 300 8 175 SAFE

29 C5 146 350 350 980.00 0.80 4 16 4 16 1608 1.31 0.609 SAFE 8 300 8 175 SAFE

30 C5 117 350 350 980.00 0.80 4 16 4 16 1608 1.31 0.609 SAFE 8 300 8 175 SAFE

31 C5 369 350 350 980.00 0.80 4 16 4 16 1608 1.31 0.609 SAFE 8 300 8 175 SAFE

32 C5 259 350 350 397.63 0.32 4 16 4 16 1608 1.31 0.247 SAFE 8 190 8 175 SAFE

33 C5 252 350 350 350.09 0.29 4 16 4 16 1608 1.31 0.218 SAFE 8 190 8 175 SAFE

34 C5 278 350 350 545.93 0.45 4 16 4 16 1608 1.31 0.339 SAFE 8 255 8 175 SAFE

35 C5 147 350 350 245.48 0.20 4 16 4 16 1608 1.31 0.153 SAFE 8 190 8 175 SAFE

36 C5 118 350 350 587.86 0.48 4 16 4 16 1608 1.31 0.365 SAFE 8 255 8 175 SAFE

38 C5 143 350 350 980.00 0.80 4 16 4 16 1608 1.31 0.609 SAFE 8 300 8 175 SAFE

39 C5 114 350 350 980.00 0.80 4 16 4 16 1608 1.31 0.609 SAFE 8 300 8 175 SAFE

40 C5 371 350 350 980.00 0.80 4 16 4 16 1608 1.31 0.609 SAFE 8 300 8 175 SAFE
Project Construction of Sewage Treatmeny Plant of Capacity 37 MLD on DBO Basis for UGSS in Tiruchirappalli City Corporation

Document Number 19-EPE-TCC-STP-PTU-STR-001 Prepared Checked Approved Rev


Title Structural Design Calculation of Pre Treatment Unit RKK VJ PS 0

Column CORNER STIRRUPS STIRRUPS


MIDDLE REIN. Prov.
REIN. Ast Prov. REQUIRED PROVIDED
Grid Col. Member DEPTH WIDTH 2 Req Steel
S.No Ast req (mm ) % Pt 2 Steel % Ratio CHECK CHECK
Mark Mark No. (D) (B) req (mm )
Dia Dia Dia Ptprov
(STAAD) Nos Nos Nos DIA. SPACING DIA. SPACING
(mm) (mm) (mm)

41 C5 258 350 350 369.27 0.30 4 16 4 16 1608 1.31 0.230 SAFE 8 190 8 175 SAFE

42 C5 251 350 350 764.17 0.62 4 16 4 16 1608 1.31 0.475 SAFE 8 255 8 175 SAFE

43 C5 281 350 350 976.55 0.80 4 16 4 16 1608 1.31 0.607 SAFE 8 300 8 175 SAFE

44 C5 144 350 350 252.04 0.21 4 16 4 16 1608 1.31 0.157 SAFE 8 190 8 175 SAFE

45 C5 115 350 350 1052.37 0.86 4 16 4 16 1608 1.31 0.654 SAFE 8 300 8 175 SAFE

SBR OUTLET (74.10-68.5)

47 C6 395 300 300 155.10 0.17 4 16 804 0.89 0.193 SAFE 8 190 8 175 SAFE

48 C6 391 300 300 259.96 0.29 4 16 804 0.89 0.323 SAFE 8 190 8 175 SAFE

49 C6 396 300 300 152.01 0.17 4 16 804 0.89 0.189 SAFE 8 190 8 175 SAFE

50 C6 394 300 300 367.92 0.41 4 16 804 0.89 0.457 SAFE 8 190 8 175 SAFE

51 C6 155 300 300 102.51 0.11 4 16 804 0.89 0.127 SAFE 8 190 8 175 SAFE

52 C6 125 300 300 535.48 0.59 4 16 804 0.89 0.666 SAFE 8 255 8 175 SAFE

53 C6 156 300 300 720.00 0.80 4 16 804 0.89 0.895 SAFE 8 255 8 175 SAFE

54 C6 126 300 300 778.42 0.86 4 16 804 0.89 0.968 SAFE 8 255 8 175 SAFE

55 C7 158 300 300 247.04 0.27 6 16 2 12 1433 1.59 0.172 SAFE 8 190 8 175 SAFE

56 C7 128 300 300 230.06 0.26 6 16 2 12 1433 1.59 0.161 SAFE 8 190 8 175 SAFE
Project Construction of Sewage Treatmeny Plant of Capacity 37 MLD on DBO Basis for UGSS in Tiruchirappalli City Corporation

Document Number 19-EPE-TCC-STP-PTU-STR-001 Prepared Checked Approved Rev


Title Structural Design Calculation of Pre Treatment Unit RKK VJ PS 0

Column CORNER STIRRUPS STIRRUPS


MIDDLE REIN. Prov.
REIN. Ast Prov. REQUIRED PROVIDED
Grid Col. Member DEPTH WIDTH 2 Req Steel
S.No Ast req (mm ) % Pt 2 Steel % Ratio CHECK CHECK
Mark Mark No. (D) (B) req (mm )
Dia Dia Dia Ptprov
(STAAD) Nos Nos Nos DIA. SPACING DIA. SPACING
(mm) (mm) (mm)

57 C7 159 300 300 720.00 0.80 6 16 2 12 1433 1.59 0.503 SAFE 8 255 8 175 SAFE

58 C7 129 300 300 1127.61 1.25 6 16 2 12 1433 1.59 0.787 SAFE 8 300 8 175 SAFE

59 C7 160 300 300 978.19 1.09 6 16 2 12 1433 1.59 0.683 SAFE 8 300 8 175 SAFE

60 C7 130 300 300 720.00 0.80 6 16 2 12 1433 1.59 0.503 SAFE 8 255 8 175 SAFE

Clasifier (Differs)

60 C8 268 300 300 720.00 0.80 4 20 1257 1.40 0.573 SAFE 8 255 8 175 SAFE

61 C8 260 300 300 720.00 0.80 4 20 1257 1.40 0.573 SAFE 8 255 8 175 SAFE

62 C8 269 300 300 413.46 0.46 4 20 1257 1.40 0.329 SAFE 8 190 8 175 SAFE

63 C8 261 300 300 1230.61 1.37 4 20 1257 1.40 0.979 SAFE 8 300 8 175 SAFE

Clasifier Platform

63 C9 218 300 300 720.00 0.80 4 16 804 0.89 0.895 SAFE 8 255 8 175 SAFE

64 C9 217 300 300 720.00 0.80 4 16 804 0.89 0.895 SAFE 8 255 8 175 SAFE

63 C9 220 300 300 473.29 0.53 4 16 804 0.89 0.588 SAFE 8 255 8 175 SAFE

64 C9 372 300 300 418.50 0.47 4 16 804 0.89 0.520 SAFE 8 190 8 175 SAFE

65 SC1 387 300 300 720.00 0.80 6 16 2 12 1433 1.59 0.503 SAFE 8 255 8 175 SAFE

66 SC1 382 300 300 720.00 0.80 6 16 2 12 1433 1.59 0.503 SAFE 8 255 8 175 SAFE
Project Construction of Sewage Treatmeny Plant of Capacity 37 MLD on DBO Basis for UGSS in Tiruchirappalli City Corporation

Document Number 19-EPE-TCC-STP-PTU-STR-001 Prepared Checked Approved Rev


Title Structural Design Calculation of Pre Treatment Unit RKK VJ PS 0

Column CORNER STIRRUPS STIRRUPS


MIDDLE REIN. Prov.
REIN. Ast Prov. REQUIRED PROVIDED
Grid Col. Member DEPTH WIDTH 2 Req Steel
S.No Ast req (mm ) % Pt 2 Steel % Ratio CHECK CHECK
Mark Mark No. (D) (B) req (mm )
Dia Dia Dia Ptprov
(STAAD) Nos Nos Nos DIA. SPACING DIA. SPACING
(mm) (mm) (mm)

61 SC2 228 300 300 720.00 0.80 6 16 1206 1.34 0.597 SAFE 8 255 8 175 SAFE

62 SC2 370 300 300 720.00 0.80 6 16 1206 1.34 0.597 SAFE 8 255 8 175 SAFE
Inlet to Detritor

Detritor Tank
SBR Outlet

Clasifier