Professional Documents
Culture Documents
Optimal power flow considering fault current level constraints and fault
current limiters
Amirhossein Khazali, Mohsen Kalantar ⇑,1
Center of Excellence for Power System Automation and Operation, Iran University of Science and Technology, Iran
a r t i c l e i n f o a b s t r a c t
Article history: The aim of this paper is to present a novel method to dispatch the active generation power properly in the
Received 1 January 2013 power system while incorporating fault current levels as constraints for the optimization problem. Due to
Received in revised form 9 December 2013 the limited capacity of protective devices such as circuit breakers, allocating active power without con-
Accepted 18 February 2014
sidering fault current levels can probably lead to fault currents exceeding the rating of these devices.
Available online 22 March 2014
Hence restricting the fault current levels to an allowable amount while minimizing a specified objective
function seems to be necessary. In a number of cases even the appropriate allocation of active power is
Keywords:
not able to reduce the fault current levels to the permitted amount therefore using fault current limiters
Optimal power flow
Fault current level constrained
(FCL) is unavoidable. In this paper also a planning scheme is presented for the location and sizing of fault
Fault current limiter (FCL) current limiters and the effect of fault current limiters on the objective functions is investigated.
Optimal location Ó 2014 Elsevier Ltd. All rights reserved.
Fault current
http://dx.doi.org/10.1016/j.ijepes.2014.02.012
0142-0615/Ó 2014 Elsevier Ltd. All rights reserved.
A. Khazali, M. Kalantar / Electrical Power and Energy Systems 59 (2014) 204–213 205
minimizing protection costs. In [17] in addition to the limitation of is implemented to the New England 39-bus system and the results
fault currents the FCL is used for preventing voltage sags. In the exhibit the effectiveness of the proposed method.
presence of distributed generation the settings of over current re-
lays have to be readjusted. However in [18] fault current limiters 2. Fault current calculation and fault current limiters
are used for restoring the coordination of over current relays.
Utilizing fault current limiters can facilitate the connection of The majority of faults in power systems are unsymmetrical
independent power producers (IPP) to the system. It can also in- however the three phase fault is the most intensive type of faults
crease the capacity of lines and totally increase the security and and is used for specifying the rating of circuit breakers. In the
reliability of the system. However, the impedance and installa- following the calculation of fault current at each bus and the effect
tion location of fault current limiters have an important effect of three phase faults on the currents flowing in the lines are
on the improvement of the system, therefore developing a meth- described:
od that can determine the sufficient number of FCLs, there loca-
tion and impedance seems to be necessary. In radial systems the 2.1. Fault current at bus
appropriate place for installing fault currant limiters can be spec-
ified simply. But in loop systems this problem is complicated and For a symmetrical fault at bus i the fault current can be obtained
requires a suitable method to determine the location, number by (1):
and impedance of FCLs considering the system specifications
[19,20]. ISC
i ¼ ðEi =Z ii Þ I b ð1Þ
In [20] a micro genetic algorithm approach has been used for where ISC
is the fault current at bus i and Ei is the voltage before the
i
solving the optimization problem considering superconducting fault at bus i which is usually assumed to be 1 p.u. Zii is the diagonal
fault current limiters. Also [21] utilizes a genetic algorithm and members of the impedance matrix. Finally Ib is the base current
sensitivity factor calculation method. In [22] a rectifier type super- [21].
conducting fault current limiter is placed in a large scale power By adding the impedance Zb between buses j and k each ele-
system. In this work a method is implemented for determining ment of the impedance bus is modified as [21]:
the optimal placement and location of fault current limiters.
In this paper initially the OPF problem is solved regarding the Z new new
xy ¼ Z xy ðZ xj Z xk Þ ðZ jy Z ky Þ=ðZ jj þ Z kk 2Z jk þ Z b Þ ð2Þ
fault current levels. It is indicated that for a number of specified where Z new
is the modified element of the impedance matrix. There-
xy
cases the proper allocation of power is capable of suppressing fore the effect of inserting the impedance Zb series with the trans-
the fault current levels to under the rated amount of protection de- mission line is equivalent to inserting the impedance Zp parallel
vices such as circuit breakers. But in other cases even the appropri- with the transmission line which can be obtained by the following
ate settings of control devices are not adequate and using fault relation:
current limiters are inevitable. In the next stage an optimal FCL
programming is represented for specifying the optimal location
Z p ¼ ðZ b ÞjjðZ b þ Z FCL Þ ¼ Z b ðZ b þ Z FCL Þ=Z FCL ð3Þ
and amount of fault current limiters. Also the impacts of using FCLs Fig. 1 shows the Thevenin equivalent from the bus under study
in the system for suppressing the fault current levels to under the when impedance Zb is added between two buses. Finally Zp is used
permitted amount is investigated on total generation cost, power to modify the elements of the impedance matrix by the below
loss of the system and voltage deviations. The proposed method relation:
Fig. 3. Resistive fault current limiters under the normal and fault condition.
X
Q Gi Q Di ¼ V i V j ðBij cos hij Gij sin hij Þ ð15Þ
Fig. 4. Structure of magnetic shield SFCL. j2N B
where PGi and QGi are the active and reactive powers generated at
bus i. PDi and QDi are the active and reactive loads at bus i. Vi and
buses [28–31]. The function is optimized while satisfying equality
Vj are the voltages at buses i and j. Gij and Bij are the conductivity
and inequality constraints. The first objective is to minimize the
and susceptance of the line between buses i and j. Finally hij = hi hj
generation fuel cost:
is the difference between bus angles.
Ng
X The inequality constraints are as follows. These constraints in-
F1 ¼ ai P2Gi þ bi PGi þ ci ð9Þ clude the bus voltages and also the line limits.
i¼1
T min
l 6 T l 6 T max
l l ¼ 1; 2; . . . Nl ð21Þ However as including fault current level constraints in the opti-
mization problem this leads to exacerbate the operation of the sys-
tem including the increase of total generation cost, power loss and
4. Optimal power flow incorporating fault current levels and also voltage deviations. Therefore to prevent the replacement of
fault current limiters protection devices and improving the quality of power system
operation utilizing fault current limiters are suggested. Also for a
In this section the optimal power flow problem is solved regard- number of lines the appropriate allocation of active power is not
ing the fault current levels in the system. The fault current level adequate for suppressing the fault currents to beyond the desired
constraints are added to the OPF problem as the following: levels and therefore using replacing circuit breakers or using fault
current limiters become inevitable. Fig. 7 demonstrates the men-
Isc max
k;j;f 6 Ik;j ð22Þ tioned two states. In case (a) the fault current for a specified line
decreases to under the desired level by a proper setting of control
where Isck;j;f indicates the maximum fault current at line k–j for a fault variables while in case (b) using fault current limiters is necessary
at bus f. Also Imax
k;j is the maximum permitted fault current according and the OPF problem is not able to decrease the fault currents to
to the capacity of protection devices such as circuit breakers at a under the permitted amount and is unfeasible. Fig. 6 shows this
specified line. However computing all of the fault current levels is stage that leads to the solving the FCL optimal sizing and place-
time consuming regarding the combination of bus numbers, line ment problem and then the solving the conventional OPF problem.
numbers and circuit breakers that are installed at the end of lines
[10]. Hence to reduce the computational burdens for large systems 5. FCL optimal placement and sizing formulation
initially a fault current level study is done at each line for a fault at
each bus. According to the ratings of circuit breakers which are in- In this paper the goal is to reduce the fault current at each bus
stalled at each line if the fault current level for a specific line vio- and the fault current flowing in lines to a specified amount. This
lates the rating of installed CBs for a fault at any bus the line will goal is obtained by the installation of adequate fault current limit-
enter a fault current level list. This list specifies the lines which ers in the system. However the total impedance used for the fault
there maximum fault current levels should be involved as con- current limiters should be minimized to reduce the financial costs.
straints such as relation (22) for the OPF problem. After determining Hence the problem can be formulated as following:
the initial fault current level list the OPF problem is solved consid-
ering this list. After solving the OPF problem a fault current level X
N FCL
minJ 1 ¼ Z i;FCL ð23Þ
analysis is done on the system considering the new amounts of con-
i¼1
trol variables obtained by the OPF problem. For any line if the fault
current level amount exceeds the rating of the installed circuit
Z min max
i;FCL 6 Z i;FCL 6 Z i;FCL i ¼ 1; 2; . . . NFCL ð24Þ
breakers for that line for a fault at any bus the line enters the fault
current level list and the OPF problem is solved again. Fig. 6 illus-
Isc sc;max
f 6 If f ¼ 1; 2; . . . ; Nb ð25Þ
trates the algorithm for making the fault current level list.
Yes
No Solve the FCL
Is the OPF problem optimal sizing and
feasible? location problem
Yes
Decreasing
Fault current level by fault current
placing and activating level by OPF
fault current limiter
Desired fault
current level
Neglecting fault
current levels in the
OPF problem
Case a
Decreasing
Fault current level by Desired fault fault current
placing and activating current level level by OPF
fault current limiter
Neglecting fault
current levels in the
OPF problem
Case b
Fig. 7. Two states for limiting fault currents using OPF and FCL.
Table 3 Table 4
Control variables for different objective functions regarding fault current levels. Buses with fault currents more than the permitted amount for a symmetrical fault at
the specified bus.
Total fuel Power loss Voltage deviation
cost ($) (MW) (p.u.) Bus number 31 32 33 34 36 38
Bus fault current 21.8 20.53 23.07 38.14 25.02 26.61
T1 0.9790 0.95 1.05
T2 0.95 1.05 0.9687
T3 0.9893 1.05 1.05
T4 0.9503 1.05 0.9955
T5 1.05 1.0498 1.0361
T6 0.95 1.0061 1.05
levels of the specified lines are suppressed to under the rating
T7 1.0405 1.0013 1.0468 amounts of circuit breakers while minimizing the total fuel cost.
T8 1.05 1.05 1.0482 Also the results for system power loss and also voltage deviations
T9 0.95 0.9838 1.0135 are illustrated in Table 3. Fig. 8 shows a comparison between the
T10 1.05 1.05 1.027
maximum fault currents of the studied lines before and after opti-
T11 0.9715 0.9956 0.9869
T12 1.0036 1.0275 0.9818 mization. It is obvious that the fault currents are limited to under
V1 0.9211 0.9254 0.9736 the allowed amount.
V2 0.9 0.9 1.0425
V3 1.1 1.0960 1.1
6.2. FCL optimal sizing and placement
V4 1.0659 1.1 1.0982
V5 0.9 0.9003 0.9008
V6 1.1 1.1 1.0571 In this section the placement of fault current limiters are pro-
V7 1.0983 0.9694 1.1 grammed to suppress the fault currents obtained by (1) and (7)
V8 0.9233 0.9747 0.9677
at buses and lines that have critical fault currents exceeding the
V9 0.9 1.0081 1.0158
V10 1.1 1.0263 1.0096 rating of protective devices. To start the optimization procedure
P1 200 200.8270 200 initially fault currents have been calculated at each bus (assuming
P2 872.5906 737.1923 56.9804 a symmetrical fault). Also the fault currents flowing through the
P3 355.8121 709.4084 1088.5 lines caused by faults at other buses that are not permitted were
P4 846.8513 678.4576 407.2304
mentioned in the previous section. For this system the fault cur-
P5 342.8564 697.9022 313.4271
P6 200 553.5478 1186 rents generated by symmetrical faults exceed the determined limit
P7 1200 653.5292 1200 (20 p.u.) for the following buses illustrated at Table 4. Six buses ex-
P8 288.1815 200 586.8395 ist that according to the impedance of the system exceed the deter-
P9 714.0144 577.1717 774.7046
mined limit of fault currents. Also in the cases noticed in Table 2
P10 1200 1170.2 439.3149
Amount of objective 167390 49.5326 0.2879
the fault current flowing in lines is more than the specified limit.
function So the fault current limiters should be sized and placed to have
the minimum impedance (for economic concerns) in addition of
limiting the fault current to the allowed limit. The fault currents
flowing in lines caused by faults at other buses are dependent on
the voltages of the system and therefore affect the optimization
problem. But the fault currents at buses caused by symmetrical
faults only depend on the impedance matrix and do not affect
the OPF problem. For the fault currents at lines the FCL optimiza-
tion problem is solved considering the initial state of the system.
Also it is assumed that inductive fault current limiters are used
in this work.
The optimization problem is solved in three cases. In the first
case only the fault current of the buses are reduced to the allow-
able limit by placing fault current limiters. In the second case the
amount and location of fault current limiters are determined in
the way to restrict the fault current flowing in lines to the permit-
ted limit. Finally in the third case the programming of fault current
limiters is implemented to the system considering both types of
fault currents.
For the first case the results are obtained and illustrated in
Table 5 by solving the optimization problem at (23)–(25). The
Fig. 8. Fault currents before and after solving the OPF problem.
results are obtained for solving the optimization problem with
three and four fault current limiters. By using two FCLs in the
system it is not possible to satisfy the constraints of (23)–(25). It
to use the minimal number of fault currents. In other worlds the is observed that in the case of using four fault current limiters
least number of fault current limiters are desired to cover the en- the total reactance that should be installed in the system is
tire system and suppressing the fault current at any location of 0.0455 p.u. while using three fault current limiters in the system
the system to under the allowed amount. In this paper for the first requires a total 0.1404 p.u. reactance. Fig. 9 shows the bus fault
case using one or two FCLs was not adequate to suppress the fault currents for three states before and after installing three and four
currents in all of the system. Therefore for the first and second case fault current limiters in the system for buses in Table 4.
of the optimal placement and sizing problem three FCLs were cho- In the second case the fault current limiters are used to restrict
sen. However in the third case even using three FCLs is not ade- the fault current flowing in the lines to an acceptable level. The
quate and using four FCLs is proposed. results in Table 6 are acquired after solving the optimization
The results for solving the optimization problem for each of problem assuming using three and four fault current limiters
these objective functions are demonstrated at Table 3. The fault (for this case it is assumed that programming the FCLs amount
A. Khazali, M. Kalantar / Electrical Power and Energy Systems 59 (2014) 204–213 211
Table 5
Optimal location and amount of fault current limiters for limiting bus fault currents.
Fig. 9. Bus Fault currents before and after installing fault current limiters for case 3.
Table 6
Optimal location and amount of fault current limiters for limiting branch fault currents.
Fig. 10. Bus Fault currents before and after installing fault current limiters for case 3.
and placement is done regarding the base case of the system). In A fault current limiter with an impedance 0.0105 p.u. should
case of using four fault current limiters the total impedance that be placed at line 19.
should be installed in the system is 0.11703 p.u., also using three A fault current limiter with an impedance 0.4194 p.u. is
FCLs increases the total used reactance to 0.2351 p.u. Similar to placed at line 1.
the previous case using two FCLs is not enough for the entire A fault current limiter with an impedance 0.020 p.u. is
system. placed at line 41.
In the last case both type of fault currents are restricted. For this A fault current limiter with an impedance 0.0034 p.u. is
case at least four fault current limiters should be used to decrease placed at line 30.
the fault current at each bus to less than 20 p.u. and the fault cur-
rent flowing in lines to under 2.2 p.u. The results attained for this Figs. 10 and 11 indicate the line and bus fault currents before
case are: and after placing the fault current limiters.
212 A. Khazali, M. Kalantar / Electrical Power and Energy Systems 59 (2014) 204–213
Fig. 11. Line fault currents before and after installing fault current limiters for case 3.
Table 7
Control variables obtained from the conventional OPF.
according to rating of Circuit breakers in the system and if the fault [9] Khazali A, Kalantar M. Optimal reactive power dispatch by a harmony search
algorithm. Electr Power Energy Syst 2011;33:684–92.
currents exceed the rating of these switching devices they are re-
[10] Vovos P, Harrison G, Wallace A, Bialek J. Optimal power flow as a tool for fault
garded in the OPF problem as additional constraints. The solution level-constrained network capacity analysis. IEEE Trans Power Syst
of the OPF problem has to suppress the levels of fault current to be- 2005;20(2).
neath the allowed amount. However there is a probability that the [11] Vovos P, Bialek J. Direct incorporation of fault level constraints in optimal
power flow as a tool for network capacity analysis. IEEE Trans Power Syst
OPF problem considering fault current limits can become infeasi- November 2005;20(4).
ble. In this case utilizing fault current limiters is proposed as a [12] Neumann C. Superconducting fault current limiter (SFCL) in the medium and
solution of decreasing fault current levels. In this work a method high voltage grid. Power Eng Soc Gen Meet 2006(2):1423–5.
[13] Noe M, Oswald B. Technical and economical benefits of superconducting fault
is presented to find the optimal placement and values of fault cur- current limiters in power systems. IEEE Trans Appl Supercond June
rent limiters and the optimal placement and sizing problem for 1999;9(2):1347–50.
FCLs is solved for three different cases. [14] Elmitwally A. Proposed hybrid superconducting fault current limiter for
distribution systems. Int J Electr Power Energy Syst 2009;31(10).
The fault current limiters are placed with the goal to restrict the [15] Javadi H. Fault current limiter using a series impedance combined with bus
fault currents at buses and the fault currents flowing through lines sectionalizing circuit breaker. Int J Electr Power Energy Syst
caused by faults at other buses. In this paper the optimization 2011;33(3):731–6.
[16] Shahriyari S, Yazdani A, Haghifam M. Cost reduction of distribution network
problem is defined in order to minimize the used impedance while protection in presence of distributed generation using optimized fault current
satisfying the defined constraints. The proposed method is imple- limiter allocation. Int J Electr Power Energy Syst 2012;43(1):1453–9.
mented to the 39 bus IEEE system. The results show that the fault [17] Firouzi M, Gharehpetian G, Pishvaei M. A dual-functional bridge type FCL to
restore PCC voltage. Int J Electr Power Energy Syst 2013;46:49–55.
currents are suppressed to the admissible levels using the least
[18] Javadi H, Mousavi S, Khederzadeh M. A novel approach to increase FCL
impedance. application in preservation of over-current relays coordination in presence of
Finally the OPF problem is solved neglecting the fault current asynchronous DGs. Int J Electr Power Energy Syst 2013;44(1):810–5.
level constraints (due to the FCL placements in the system). Com- [19] Fault Current Limiter Technical Committee, Technical Report of the IEE of
Japan, vol. 709, 1999.
paring the results for two cases indicates that placing fault current [20] Hongesombut K, Furusawa K, Mitani Y, Tsuji K. Allocation and circuit
limiters in the system can have a salient impact on the economical parameter design of superconducting fault current limiters in loop power
and secure operation of the system. system by a genetic algorithm. Trans Inst Electr Eng Jpn 2003;123(9):1054–63.
[21] Teng J, Lu C. Optimum fault current limiter placement with search space
reduction technique. IET Gener Transm Distrib 2010;4(4):485–94.
References [22] Nagata M, Tanaka K, Taniguchi H. FCL location selection in large scale power
system. IEEE Trans Appl Supercond 2001;11(1):2489–94.
[1] Lee K, Park Y, Ortiz J. A united approach to optimal real and reactive power [23] Cointe Y, Tixador P, Villard C. FCL: a solution to fault current problems in DC
dispatch. IEEE Trans Power Ap Syst 1985:1147–53. networks. J Phys: Conf Ser 2008;97.
[2] Momoh JA, El-Hawary ME, Adapa R. A review of selected optimal power flow [24] Kozak S, Janowski T. Physical and numerical models of superconducting fault
literature to 1993. I. Nonlinear and quadratic programming approaches. IEEE current limiters. IEEE Trans Appl Supercond 2003;13(2):2068–71.
Trans Power Syst 1999;14(1):96–104. [25] Osorio M, Cabo L, Veira J, Vidal F. Inductive fault current limiter based on
[3] Momoh JA, El-Hawary ME, Adapa R. A review of selected optimal power flow multiple superconducting rings of small diameter. Supercond Sci Technol
literature to 1993. II. Newton, linear programming and interior point methods. 2004;17:98–102.
IEEE Trans Power Syst 1999;14(1):105–11. [26] Guk-Hyun M, Wi Y, Lee K, Joo S. Fault current constrained decentralized
[4] AlRashidi M, El-Hawary M. Applications of computational intelligence optimal power flow incorporating superconducting fault current limiter
techniques for solving the revived optimal power flow problem. Electric (SFCL). IEEE Trans Appl Supercond June 2011;21(3).
Power Syst Res 2009;79(4):694–702. [27] Xie Y, Tekletsadik K, Hazelton D, Selvamanickam V. Second generation high-
[5] Abido M. Optimal power flow using particle swarm optimization. Int J Electr temperature superconducting wires for fault current limiter applications. IEEE
Power Energy Syst 2002;24:563–71. Trans Appl Supercond 2007;17(2):1981–5.
[6] Lai L, Ma J, Yokohoma R, Zhao M. Improved genetic algorithm for optimal [28] Abido M. Optimal power flow using particle swarm optimization. Int J Electr
power flow under both normal and contingent operation states. Electr Power Power Energy Syst 2002;24(October (7)):563–71.
Energy Syst 1997;19:287–91. [29] Osman M, Abo-Sinna M. A solution to the optimal power flow using genetic
[7] Abou E AA, Abido MA, Spea SR. Optimal power flow using differential evolution algorithm. Elsevier Inc.; 2003.
algorithm. Electr Power Syst Res 2010;80(7):878–85. [30] Sivasubramani S, Swarup K. Multi-objective harmony search algorithm for
[8] Kumari MS, Maheswarapu S. Enhanced genetic algorithm based computation optimal power flow problem. Electr Power Energy Syst 2011;33:745–52.
technique for multi-objective optimal power flow solution. Int J Electr Power [31] Vaisakh K, Srinivas L. Evolving ant direction differential evolution for OPF with
Energy Syst 2010;32(6):736–42. non-smooth cost functions. Eng Appl Artif Intell 2011;24:426–36.