Professional Documents
Culture Documents
Marriott Fire Protection PDF
Marriott Fire Protection PDF
A. General Requirements............................................................. 1
B. Definitions ................................................................................ 1
C. Codes, References and Standards.......................................... 2
D. Systems Testing ...................................................................... 3
E. Submittals ................................................................................ 4
F. Automatic Sprinkler / Standpipe System.................................. 4
G. Fire Alarm ................................................................................ 8
H. Mechanical Smoke Control ................................................... 10
I. Kitchen Hood and Duct Fire Suppression.............................. 11
J. Emergency Electrical Systems ............................................. 11
K. Central Control Station (Fire Command Room) ..................... 12
L. Means of Egress .................................................................... 12
M. Special Considerations .......................................................... 13
N. Example Diagrams................................................................. 13
Module Organization
• This Module is a part of an integrated series of Modules.
• Coordination with information from other Modules is required.
• The reference symbol <XX> is used to indicate a Module reference that
includes additional information.
D. Systems Testing
1. Application: Before a property is opened to the public, the
fire protection and life safety systems shall be fully
operational, contractor tested and approval obtained from
Marriott's Fire Protection Department.
In order to obtain Marriott's approval, the fire protection and
life safety systems shall be operated by the contractor under
simulated emergency conditions in the presence of Marriott
Fire Protection personnel and the contractor shall
demonstrate compliance with Marriott's standards.
2. Automatic Sprinkler / Standpipe System (Section F.):
• Contractor shall flush and pressure test system prior to
Marriott's observation of the test of water flow and
tamper switches.
• Fire pump shall be tested and certified by the
manufacturer.
• Underground mains flushed and tested.
3. Fire Alarm (Section G.):
• Contractor shall pretest and operate system without
trouble lights exhibited.
• Contractor shall demonstrate compliance by activating all
devices to set-off alarms and verifying that proper point
address or zone indications and supervision appear on
alarm panel.
4. Mechanical Smoke Control (Section H.):
• Prior to testing smoke control systems, HVAC systems
shall be contractor tested and balanced.
• Public area, atrium and guestroom corridor smoke
exhaust, and stairwell pressurization systems shall be
operational and tested to clear "cold smoke" so that exit
signs are visible within 10 minutes of activation without
smoke migration to other areas.
5. Kitchen Hood and Duct Fire Suppression (Section I.):
• Contractor shall pretest all coordinated components by
activation of kitchen hood and duct flow switch or control
unit.
• Contractor shall demonstrate compliance by operating
initiating devices, activating coordinated alarms, gas,
electric and hood supply air fan shut-downs.
6. Emergency Electrical Systems (Section J.):
• Generator shall be operational and tested to
automatically activate upon loss of normal incoming
power and to provide standby and emergency service to
operate emergency lighting and specified systems.
• Battery standby power and UPS systems providing
emergency power and lighting shall be fully operational.
E. Submittals
1. General: Prior to installation of systems, submit the
following for review and approval to:
Marriott Corporate Fire Protection:
• Floor plans with exiting and occupant load diagrams,
and fire resistance ratings.
• Fire alarm system diagrams, shop drawings,
equipment product sheets, voltage drop and battery
calculations and sequence of operation matrix.
• Automatic sprinkler / standpipe system shop drawings,
hydraulic calculations and equipment product sheets.
• Plans for emergency lighting and exit signs, and
information on the emergency power provided.
• Smoke control system shop drawings, riser diagrams
and calculations (space volumes, air changes, fan /
equipment flow capacities and locations).
Zurich Services Corporation:
• Automatic sprinkler / standpipe system shop drawings,
hydraulic calculations and equipment product sheets.
• Set of construction (contract) drawings.
2. Mailing Addresses:
• Marriott International, Inc.; Marriott Corporate Fire
Protection, Dept. 52/924.36; 10400 Fernwood Road;
Bethesda, MD 20817
• Zurich Services Corporation; Risk Engineering
Department; 1818 Market Street, 21ST Floor;
Philadelphia, PA 19103; Attn: Mr. Richard Gallagher,
Sr. Risk Engineering Consultant
F. Automatic Sprinkler / Standpipe System
1. Design Requirements:
• Standards: NFPA 13 (not NFPA 13R), 14, 1142 & 20.
• Water Source: Perform flow-test(s) and document.
Provide dependable source of water quantity and
pressure from municipal water main or from on-site
cistern or tank(s) if municipal water is not available.
• Safety Factor: Provide a 10% hydraulic safety factor
up to a maximum of 10 psi.
• Pressure Reducing Valves: In order to minimize
adjustment and maintenance, design system within
maximum pressure of 175 psi without use of pressure
reducing valves. If pressure reducing valves are
required, consult with Marriott Fire Protection.
G. Fire Alarm
1. Requirements: Equip entire building with a central fire
alarm system. See the Fire Alarm System Sequence
Matrix in this Module. Coordinate with <15C>.
• Standard: NFPA 72.
• System: Provide fully point addressable system (all
alarm initiating and supervisory devices individually
addressable) in all buildings.
• Campus Style Sites: Provide point addressable
networking that reports to the continuously attended
property location.
• Testing: Provide the following at the Fire Alarm
Control Panel (FACP).
+ Disconnect switches to disable notification, audible
appliances, visual strobes, and auxiliary function
points for testing purposes.
+ Alarm sensitivity testing at FACP.
• Unconditioned areas: Provide corrosion resistant
(weatherproof) devices listed for exterior use.
2. System Smoke Sensors (Detectors):
• Guestrooms, Suite Rooms and other Sleeping Units:
Provide system smoke sensors with sounder bases to
meet the following:
+ Photoelectric type sensor.
+ Sounder Base: Provide minimum audible alarm of
85 dBA at 3 m (10 ft.); minimum of 75 dBA “at the
pillow”.
+ Activation of room system smoke sensor to
immediately and automatically sound an alarm
within the room of incident.
+ System smoke sensor normal and emergency
power is provided by the FACP.
+ In suites and other mixed sleeping spaces, provide
system smoke sensors in each separate sleeping
room, living rooms convertible to sleeping and
areas providing access to the corridor doorway.
Multiple sensor sounder bases located within the
same suite or unit shall activate at the same time.
+ To minimize false alarms, avoid locating smoke
sensors near the kitchen.
• Public Areas, Corridor and Back of House Areas:
Provide system smoke sensors where:
+ Required by governing code.
+ Smoke exhaust is required in compliance with the
other requirements of this Module.
• Duct System Smoke Sensors: Provide duct system
smoke sensors as required by the NFPA 101 Life
Safety Code. Provide remote test switch and indicator
light accessible from floor level.
Guestroom System
Smoke Sensors (3)
Pressure Switches
Generator Signals
Carbon Monoxide
Notes: Reference numbers are shown in parenthesis (1) for notes /
Tamper Switches
Supply Switches
Kitchen Hood &
Sprinkler Valve
Elevator shaft /
System Smoke
notations indicated below and in headings to the right.
Suppression
System Heat
Duct Smoke
Manual Pull
Sensors (1)
Emergency
Waterflow
detectors
Switches
Duct Fire
Stations
Sensors
(2) & (7)
Signals
(8)
(9)
FACP: Display an audible / visual alarm. X X X X X X X X X X X X X X
Remote Annunciator: Display an audible / visual alarm. X X X X X X X X X X X X X X
Audible / Visual Alarms: Activate audible / visual strobe appliances on X X X X X X
affected floor. (5)
Fire Door: Release magnetic door holders on affected floor. X X X X
Stairwell Pressurization: Activate pressurization. X X X X X
Smoke Exhaust: Activate exhaust system in affected zones. X X (4) (4)
Guestroom Audible Alarms: Activate alarms in rooms on affected X X X X X X
floor. (5)
ADA Guestrooms Audible / Visual Signals: Activate both signals in X X X X X X
ADA and hearing-impaired guestrooms on affected floor. (5)
Guestroom Local Audible Alarms: Activate audible alarms only in X __ (6)
rooms containing alarm.
ADA Guestroom Local Audible / Visual Signals: Activate both signals X __ (6)
only in hearing-impaired and ADA guestroom containing alarm.
Air Handlers: Shut down associated air handlers. X
Kitchen Gas / Electric: Shut down associated kitchen gas & electric X
and make-up air handler.
(1) System smoke sensors not located in guestrooms.
General Notes: (2) Provide associated elevator recall and shunt trip functions in compliance with ASME A-17.1,
• All fire alarm system devices to be point addressable. Elevator Code.
• On campus style properties, provide point addressable networking (3) Guestroom Smoke Sensors: Provide photoelectric type, with sounder base (minimum ratings of 85
reporting to continuously attended property location. dBA, with 75 dBA "at the pillow"). At suites, multiple sensors shall activate at the same time.
• Sprinkler system water flow and tamper switch alarms are (4) Water flow alarms shall not activate smoke control exhaust fans where smoke control zones and
annunciated on the FACP. fire sprinkler zones do not correspond.
(5) Fire alarms shall activate only on floor of alarm. Governing authority may require additional zoning.
(6) Carbon Monoxide detectors in guestrooms shall activate an alarm in the guestroom of incident and
at the fire alarm control panel.
** End of Module ** (7) We recommend not using heat detectors since fire sprinklers are also activated by heat.
(8) Provide alarm and signal devices remote from controller in compliance with NFPA 20.
(9) Provide alarm and signal devices remote from generator in compliance with NFPA 110.