Professional Documents
Culture Documents
PREPARED BY:
____________________________________
ARCH. WILLIAM TI JR.
PRC NO : 18161
PTR NO : 1128827
ISSUED AT : SAN JUAN
DATE ISSUED : Jan. 03, 2018
TIN NO. : 217-616-780
TABLE OF CONTENTS
DIVISION 1 GENERAL CONDITIONS
Sections 01000 General Conditions
01300 Contractor's Submittal
01350: Substitutions
DIVISION 2 SITEWORKS
Sections 02110 Earth work
02222 Soil Treatment
DIVISION 4 MASONRY
Section 04100 Masonry Units
DIVISION 5 METALS
Section 05010 Metal Materials
DIVISION 9 FINISHES
Sections 09000 Finishes
09200 Plastering
09300 Gypsum Board
09305 Homogenous Tiles
09500 Painting
09705 Epoxy Floor and Wall/ Ceiling Coatings
09706 Food Quality Epoxy Coatings
Part 1 General
1.01 SCOPE OF WORK: This includes furnishing of materials, labor & equipment, Transportation and other
facilities except where materials called for shall be supplied by others or the Owner.
1.02 PLANS & SPECIFICATIONS: Verify, examine and compare Plans and Specifications, if there is a
discrepancy, always submit matter to the Architect.
1.03 LAWS TO BE OBSERVED: Comply with all the laws, City-Municipal ordinances and all government
regulations.
A. The Contractor shall secure approval from authorities of all drawings relating to his work.
B. All construction permits and fees including drawings, specifications and other related documents
shall be obtained by and at the expense of the Contractor. The Contractor shall furnish the Owner
through the Architect, the final certificates of inspection and approval from the proper government
authorities upon completion of the work. The contractor shall prepare all as-built drawings and all
other paper work required by the approving authorities.
1.05 AUTHORIZED REPRESENTATIVE: The Contractor shall assume unit responsibility and shall provide the
full-time service of a qualified Representative to supervise the complete construction according to the
Drawings and Specifications.
In the event that the Contractor's Representative is found by either Owner or the Architect to be incompetent
in discharging his assigned responsibilities, Owner may request the Contractor at the Contractor's expense to
replace the engineer in question with a qualified and experienced architect/engineer acceptable to the Owner.
Part 2 Materials
2.01 MATERIALS: Shall be new, of best grade and quality; submit samples whenever asked for in the
Specifications and by the Architect. Failure to comply with this condition shall be at the Contractor’s
responsibility, materials not approved shall be at the risk of subsequent rejection.
2.02 SAMPLE & INFORMATION OF MATERIALS: When required by the Specifications or when called for by
the Architect, the Contractor shall furnish for approval full information and satisfactory evidences as to the
kind and quality of materials he contemplates on incorporating in the work. The Contractor shall furnish, for
Architect and Owner’s approval, all samples when so directed. The work shall be in accordance with approved
samples.
2.03 TEMPORARY FACILITIES: Provide weather-tight temporary facilities with water, light and toilet. Keep
facilities clean at all times.
Part 3 Execution
3.01 WORKMANSHIP: The work throughout shall be executed in the best and thorough manner to the
satisfaction of the Owner and the Architect, who will interpret the meaning of the Drawings and Specifications.
3.02 PROTECTION OF WORK & OWNER'S PROPERTY: Protect all work, materials and property of Owner
from damage, injury or loss.
3.3 INSPECTION OF WORK: Provide access and facilities to Owner and Architect during inspection.
3.4 DISPUTES: The Architect shall, within a reasonable time, make decisions on all claims of the Owner or
Contractor on all disputes concerning work and contract.
3.5 CLEAN-UP: The Contractor, prior to the turn-over of the work to the Owner, shall remove all rubbish,
tools, scaffolding, equipment and all materials not the property of the Owner.
Part 1 General
B. Throughout the contract documents, the minimum acceptable quality of workmanship and
materials is defined either by the manufacturer's name and catalog number, and or reference to
reputed industry standards.
2.01 SAMPLES:
A. Unless otherwise specifically directed by the Architect, every sample shall be of the precise item
proposed to be furnished.
B. Samples are subject to review of kind, color, pattern, and texture for final check and a comparison
of these characteristics between the final submittal and the component as delivered and installed.
Where variations are inherent in the product, submit multiple units that show limits of the variations.
C. All materials, finishes, and workmanship of specified items necessary to complete the work shall be
delivered on site, similar and equal to approved samples.
E. Where samples are for selection of characteristics from a range of choices, submit a full set of
choices for the product. Preliminary submittals shall be reviewed and returned with the
corresponding selection and other action to be taken. Unless range of choices submitted for each
product have identical costs, wearing capabilities, and suitability for the installation, completely
describe the relative costs and capabilities.
F. In addition to requirements of Article 3.02 of this Section, completely identify samples with the
following information:
1. Product Description;
2. Name of Manufacturer & Product;
3. Source;
4. Compliance with recognized standards; and,
5. Availability and delivery time.
A. Shop drawings shall be carefully prepared to show complete layout and details of all items: kind,
thickness, governing dimensions, finish of materials, methods of construction and anchorage,
adjoining supports and/or contiguous work. When required for correct fabrication of work, field
measurements shall be made and noted on the drawings before submittal.
B. Contract Documents or standard information are not to be reproduced as a basis of Shop Drawings.
C. Shop drawings shall completely bear the following information in addition to requirements of
Article 3.02 of this Section:
1. Dimensions;
2. Identification of products and materials included;
3. Notation of coordination requirements and deviations from Contract Documents; and,
4. Notation of dimensions established by field measurements.
D. Submit three (3) copies of Shop Drawings to the Architect for approval before fabrication of work.
Unapproved Shop Drawings are to be corrected and returned for final approval by the Architect. One
(1) copy of approved Shop Drawings shall be given to the Architect and to the owner. There should
always be, at least, one (1) copy of the updated and approved Shop Drawings on the site for
immediate reference. And they shall be kept inside the site office at all times.
E. Unless otherwise specifically directed by the Architect, prepare all shop drawings accurately to
scale, complete with all necessary text dimensions, sufficiently large, to show all pertinent features of
the item and its method of construction to the Work. Submit on sheets at least 279 mm. x 432 mm.
(11" x 17") but not larger than 762 mm. x 1016 mm. (30" x 40").
Let it be a general rule ,that in all Shop Drawings, text dimensions are considered correct and should
prevail over drawing scale. Should a discrepancy in the Shop Drawings arise, it is pertinent to advise
the Architect before any actions in connection with construction are taken. We will not allow anyone
to scale off from any Shop Drawing. Do not use Shop Drawings without a final stamp or approved
signature indicating actions taken in connection with construction.
H. Approval of shop drawings shall not be construed as authorized additional work or increased cost
to the Owner. Neither, will it relieve the Contractor from responsibility for errors, omissions, or work
required by the Contract, not indicated on the Shop Drawings. Errors or omissions discovered later
must be accordingly made good by the Contractor at their expense.
A. Submit to the Architect for reference Two (2) copies each of the CPM Schedule and Diagram as
early as possible. Whenever significant changes to the project such as added or deleted activities or
revised duration, they must be reflected in the revised CPM Schedule and Diagram and resubmitted
to the Architect in duplicate copies.
B. Coordinate CPM Schedule with Submittal Schedule. List of subcontracts, progress reports, payment
requests and other schedules. Secure commitment for performing critical construction operations
from parties involved.
D. Area Separation: Provide a separate diagram to identify each construction area by phase. Indicate
where each element must be sequenced with other activities.
A. Submit two (2) copies of Submittal Schedule to the Architect together with the Construction
Schedule. Coordinate the Submittal Schedule with the list of products and Construction Schedule.
B. Prepare the Submittal Schedule in chronological order and provide the following:
C. Distribute copies of Submittal Schedule to subcontractor and other parties required to comply with
scheduled dates. When revisions are made, distribute schedule to same parties.
Part 3 Execution
3.01 GENERAL
To ensure that the specified products are furnished and installed in accordance with design requirements,
provisions have been established for the review, and approval or rejection of submittals by the Architect.
B. Coordinate submittal preparation with performance of construction activities, and with purchasing
or fabrication, delivery, and other related activities.
C. Transmit different submittals of related activities in sufficient time before scheduled dates of work
to provide ample time for reviews, securing approvals, possible revisions and re submittals, placing
orders and securing deliveries. The Architect reserves the right to withhold action on submittal
requiring coordination until related submittals are received.
D. Allow at least three (3) days reckoned from receipt of submittal for the Architect's initial review.
Allow more time if processing must be delayed for coordination with other submittals. The Architect
shall advise the Contractor when a submittal shall be delayed for coordination. Allow two(2) weeks
for reprocessing each submittal.
Completely identify each submittal and re submittal by indicating at least the following information together
with attached transmittal:
B. Title of Project
C. Date of Submittal
Part 1 General
1. Substitutions requested during the bidding/negotiation period, and accepted prior to Award of
Contract.
2. Revisions to Contract Documents requested by the Owner or Architect.
3. Specified options of products and construction methods included in Contract Documents.
4. Compliance with governing regulations and orders issued by governing authorities.
1.02 SUBMITTAL:
A. Requests for Substitution shall be considered if received within fifteen (15) calendar days after
commencement of the Work. Requests received more than fifteen (15) calendar days after
commencement of the Work may be considered or rejected at the discretion of the Architect.
B. Submit three (3) copies of each Request for Substitution in accordance with procedures for Change
Order proposals. Include the following information’s:
2. Product data including drawings and description of product, fabrication and installation
procedures;
WTA Architecture And Design Studio Page 7 of 68
TECHNICAL SPECIFICATIONS
5. A list of changes or modifications needed due to the proposed substitution to other parts of
the work and to the construction performed by other separate Contractors;
6. A statement indicating the substitution's effect on the Construction Schedule compared to the
Schedule without approval of the substitution. Indicate the effect of the substitution on overall
Contract Time;
7. Cost information, including a proposal of the net change, if any in the Contract Sum; and,
8. Certification that the substitution is "equal to" or even better in every respect to that required
by the Contract Documents and that it shall perform adequately in application indicated. Include
Contractor's waiver of rights to additional payment or time, that may be necessary because of
the substitution's failure to perform adequately.
Part 2 Specifics
The Contractor's substitution request shall be received and considered by the Owner on the following
conditions, as determined by the Architect.
Documents;
D. The request is directly related to an "or approved equal" clause or similar language in the Contract
Documents;
E. The specified product or method of construction cannot be provided within the Contract Time but
which the proposed substitution can be promptly provided;
F. The specified product or method of construction cannot receive necessary approval by a governing
authority but which the requested substitution can be approved;
G. The proposed substitution offers a substantial advantage to the Owner, in terms of cost, time,
energy conservation or other considerations of merit, after deducting responsibilities that the
substitution may incur to the Owner. These additional responsibilities to the Owner may include
additional compensation to the Architect for redesign and evaluation services, increased cost of other
construction by separate contractors and similar considerations;
I. The specified product or method of construction cannot be coordinated with other materials but
which the proposed substitution can be coordinated, as certified by the Contractor;
J. The specified product or method of construction cannot provide a warranty required by the
Contract Documents but which the proposed substitution can provide the required warranty, as
certified by the Contractor or manufacturer of the requested product;
Part 3 Execution
3.01 ACCEPTANCE/REJECTION:
A. Within One (1) week of receipt of the Request for Substitution, the Architect shall notify the
Contractor of acceptance or rejection of proposed substitution. Acceptance shall be in the form of a
Change Order.
B. The Contractor's submittal and Architect's acceptance of Shop Drawings, Product Data or Samples
that relate to construction activities not complying with the Contract Documents does not constitute
a valid request for substitution, nor does it constitute approval for substitution.
PART 1 GENERAL
1.01 WORK INCLUDED: Work in this section includes the complete clearing of site, general site grading,
excavating, filling and backfilling.
Required compaction is expressed as a percentage of the maximum density obtained by test procedure of
ASTM D1557.
2.01 EXCAVATION. The contractor shall perform excavation of every type of material encountered within
the limits of the project to the lines, grades, and elevations indicated and as specified herein. Grading shall be
in conformity with the typical sections shown and shall be finished within a tolerance of 25/100 foot of the
grades indicated. Satisfactory excavated materials shall be transported to and placed in fill areas within work
limits. Unsatisfactory materials encountered below the established sub-grade shown under building or paved
areas shall be excavated 300 mm or 31 cm below grade and replaced with satisfactory materials as directed.
In the event that it is required to remove unsatisfactory material to a greater depth than specified, an
adjustment in the contract price will be made in accordance with the contract. Surplus satisfactory excavated
material not required for fill or embankment shall be disposed of to the designated waste or spoil areas.
Unsatisfactory excavated material shall be disposed of in designated wastes or spoil areas. Excavation and
filling shall be performed in manner and sequence that will provide proper drainage at all times.
2.02 CUTTING, FILLING AND GRADING. Cutting, filling and grading will be done to bring all areas of the
respective surfacing as fixed by the finished grade.
2.03 COMPACTION. Compaction shall be by rolling with approved tamping rollers, vibratory rollers,
pneumatic-tired rollers, three-wheel power rollers, or other approved equipment well suited to the particular
soil being compacted. Material shall be moistened or aerated as necessary to provide the moisture content
that will facilitate obtaining the specified compaction with the equipment utilized.
A. CONSTRUCTION. Sub-grade shall be shaped to line, grade, and cross-section, and compacted as
specified. This shall be done by plowing, disking, and moistening or aerating. Low areas resulting
from removal of unsatisfactory material or excavation of rock shall be brought up to required grade
with satisfactory materials, and entire sub-grade shaped. Elevation of finish sub-grade shall conform
to elevations shown.
B. PROTECTION. During construction, any excavation shall be kept shaped and drained. Ditches and
drains shall be maintained in such manner as to drain effectively at all times. Graded areas shall be
protected against action of the elements prior to acceptance of the work. Settlement or washing that
may have occurred shall be repaired and grades shall be re-established to the required elevations and
slopes immediately prior to installation of paving.
B. EXCESS EXCAVATION. Excavations carried below indicated depths will not be permitted except to
remove unsatisfactory material. Unsatisfactory materials encountered below grades shown shall be
removed and replaced as directed with satisfactory materials. Unauthorized material removed below
depths indicated shall be replaced, at no additional cost to the owners, to the indicated excavation
grade with satisfactory materials placed and compacted to 100% maximum density except under
concrete footings.
C. DRAINAGE AND PUMPING. Excavate in such a manner that site and area immediately surrounding
will be continually drained. Water shall not be permitted to accumulate in excavations. Do all
necessary pumping required to keep excavations dry.
D. SHORING. During excavation shall be furnished and installed as necessary to protect workers,
banks, adjacent paving, structures, and utilities. Shoring, bracing, and sheeting shall be removed, as
excavations are backfilled in such a manner as to prevent injurious caving.
E. EXCAVATED MATERIALS. Satisfactory excavated materials required for fill or backfill shall be
separately stockpiled as directed. Unsatisfactory and surplus excavated materials not required for fill
and backfill shall be disposed of in designated waste area. Stockpiles and wasted materials shall be
graded and sloped for proper drainage.
F. BACKFILLING. Backfilling shall not begin until construction below finish grade has been approved,
underground utilities systems have been inspected, tested, and approved, formed removed, and the
excavation cleaned of trash and debris. Backfill shall be brought to indicated finish sub-grade. Backfill
materials shall be satisfactory materials, free from roots and other organic matter, trash, debris.
Place backfill in 23-cm maximum layers loose depth. Compaction shall be as in Paragraph 2A.5. Fill
shall be compacted by power-driven hand tampers suitable for the material being compacted.
Backfill shall not be placed against foundation walls prior to 7 days after placement of concrete or
masonry. As far as practicable, backfill shall be brought up evenly on each side of the wall and sloped
to drain away from the wall. Brace inside of the wall before backfill is placed on the outside of
basement.
G. PROTECTION. Settlement that occurs in backfill areas prior to acceptance of the work shall be
repaired and grades re-established to the required elevation and slope.
A. GENERAL. Perform all excavating of every description and of whatever substance encountered to
depths indicated or specified. Pile materials suitable for backfilling a sufficient distance from banks of
trenches to prevent slides or cave-ins. Excavated materials shall be piled to one side only of trenches
and in such a manner as to permit ready access to and use of existing utilities system. All excavated
materials not required or suitable for backfill shall be wasted as directed. Water shall be removed by
pumping or other approved method and shall be discharged at a safe distance from the excavation.
Sheeting and shoring shall be done as necessary for protection of work and for safety of personnel.
B. TRENCH EXCAVATION. Trenches shall be of necessary width for proper laying of pipe, while
concrete lining, duct, or cable, and banks shall be as nearly vertical as practicable. Trench excavation
shall be coordinated to avoid open trenches for prolonged periods. Bottoms of trenches shall be
accurately graded to provide uniform bearing and support for each section of pipe on undisturbed soil
at every point along its entire length, except for portions of pipe sections where it is necessary to
excavate for bell holes and for proper making of pipe joints.
C. BACKFILLING. Backfilling shall be coordinated with testing of utilities. Where damage is likely to
result from withdrawing sheeting, it shall be left in place and contract price will be adjusted
accordingly. Trenches shall be carefully backfilled with satisfactory materials, consisting of earth,
loam, sandy clay, sand and gravel, or soft shale, free from large clod of earth. Backfill shall be brought
up evenly on both sides of pipe for a cover of not less than 31 cm for storm drains. The remainder of
backfill material shall then be deposited in the trench in 31-cm maximum layers and compacted by
mechanical means. Trenches and excavation pits improperly backfilled, or where settlement occurs,
shall be reopened to the depth required for proper compaction, then refilled and compacted, with
the surface restored to the required grade and compaction.
Part 1 General
1.01 WORK INCLUDED: This section covers the furnishing of all materials, labor, & equipment necessary to
perform the completion of ground and soil treatment.
1.02 LAYING OF WORK: Lay all work to true lines and grade; establish staking fully.
1.03 EXCAVATION & FILLING: Extent and elevations of excavation as shown on Drawings; practice extra
care to protect adjoining properties and utility lines.
Part 2 Materials
2.01 FILL MATERIALS: Of approved materials placed in layers not exceeding 150 mm. each in thickness,
compacted to 95% standard density at optimum moisture.
Material shall be an organic phosphate insecticide which acts primarily by contact activity and as a stomach
poison. It shall be biologically active against many species of insects and other anthropoids that are plant,
animal and human health pests, including termites.
Part 3 Execution
3.01 APPLICATION: Pesticide application shall be done only by licensed and certified pesticide applicators.
Applicator shall be familiar with all the works involved and shall only hire skilled personnel familiar with soil
and ground treatment. The applicator shall give a certificate of guarantee for a minimum of 5 years to
maximum of 20 years.
PART 1 General
1.02 SUBMITTALS
B. Product Data: Manufacturer's data sheets, including product specifications, test data, preparation
instructions and recommendations, storage and handling requirements and recommendations, and
installation methods.
A. Deliver product in factory numbered and sealed drums, with numbers recorded for Owner's
records.
B. Store products in manufacturer's unopened drums until ready for installation.
WTA Architecture And Design Studio Page 12 of 68
TECHNICAL SPECIFICATIONS
A. No satisfactory procedures are available to remove petroleum or rust stains from concrete.
Prevention is therefore essential. Take precautions to prevent staining of concrete prior to application
of cure-seal-hardener and for minimum of three months after application:
B. Do not install products under environmental conditions outside manufacturer's absolute limits.
1.06 WARRANTY
A. Provide manufacturer's warranty that a structurally sound concrete surface prepared and treated
according to the manufacturer's directions will remain permanently dustproof, hardened and water
repellent. If after the specified sealing period the treated surface does not remain dustproof,
hardened and water repellent, provide, at manufacturer's expense, sufficient material to reseal
defective areas.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Acceptable Manufacturer: Ashford Formula or approved equivalent.
2.02 MATERIALS
PART 3 EXECUTION
3.01 GENERAL
A. Do not begin installation until substrates have been properly prepared and are suitable for
application of product.
3.02 PREPARATION
B. Prepare surfaces using the methods recommended by the manufacturer for achieving the best
result for the substrate under the project conditions.
3.03 INSTALLATION
B. If this is the applicator's first project using this product, provide the manufacturer's technical
representative on-site to familiarize installers with proper procedures.
D. New Concrete: Apply cure-seal-hardener to new concrete as soon as the concrete is firm enough to
work on after troweling, except on colored concrete wait minimum of 30 days.
2. Keep surfaces wet with cure-seal-hardener for minimum soak-in period of 30 minutes, without
allowing drying out or becoming slippery. In hot weather slipperiness may appear before the 30
minute time period has elapsed. If that occurs, apply more cure-seal-hardener as required to
keep entire surface in a non-slippery state for the first 15 minutes. For the remaining 15 minutes,
mist the surface as needed with water to keep the material in a non-slippery state.
3. After this period, when treated surface becomes slippery lightly mist with water until
slipperiness disappears.
4. Wait for surface to become slippery again and then flush entire surface with water removing
all residue of cure-seal-hardener.
5. Squeegee surface completely dry, flushing any remaining slippery areas until no residue
remains.
6. Wet vacuum or scrubbing machines may be used to remove residue, provided manufacturer's
instructions are followed.
2. Saturate surface with cure-seal-hardener; resprayor broom excess onto dry spots.
3. Keep surface wet with cure-seal-hardener for minimum soak-in period of 30 to 40 minutes.
4. If, after the 30 minute soak-in period, most of the material has been absorbed, remove all
excess material using broom or squeegee, especially from low spots.
5. If, after the 30 minute soak-in period, most of the material remains on the surface, wait until it
becomes slippery and then flush entire surface with water removing all residue of cure-seal-
hardener and squeegee completely dry, flushing any remaining slippery areas until no residue
remains.
3.04 PROTECTION
A. Protect installed floors until chemical reaction process is complete; at least three months.
2. Clean floor regularly in accordance with manufacturer's recommendations because water will
accelerate the sealing and scrubbing will impart a shine.
3. Clean up spills immediately and spot-treat stains with good degreaser or oil emulsifier.
B. Precautions and cleaning are the responsibility of the General Contractor until Substantial
Completion.
PART 1 General
1.02 SUBMITTALS
B. Product Data: Manufacturer's data sheets, including product specifications, test data, preparation
instructions and recommendations, storage and handling requirements and recommendations, and
installation methods.
A. Deliver product in factory numbered and sealed drums, with numbers recorded for Owner's
records.
A. No satisfactory procedures are available to remove petroleum or rust stains from concrete.
Prevention is therefore essential. Take precautions to prevent staining of concrete prior to
application of cure-seal-hardener and for minimum of three months after application:
3. If construction equipment must be used for application, diaper all components that might drip
oil, hydraulic fluid, or other liquids.
B. Do not install products under environmental conditions outside manufacturer's absolute limits.
1.06 WARRANTY
A. Provide manufacturer's warranty that a structurally sound concrete surface prepared and treated
according to the manufacturer's directions will remain permanently dustproof, hardened and water
repellent. If after the specified sealing period the treated surface does not remain dustproof,
hardened and water repellent, provide, at manufacturer's expense, sufficient material to reseal
defective areas.
PART 2 PRODUCTS
2.01 MANUFACTURERS
2.02 MATERIALS
PART 3 EXECUTION
3.01 GENERAL
A. Do not begin installation until substrates have been properly prepared and are suitable for
application of product.
B. If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory
preparation before proceeding.
3.02 PREPARATION
B. Prepare surfaces using the methods recommended by the manufacturer for achieving the best
result for the substrate under the project conditions.
3.03 INSTALLATION
B. If this is the applicator's first project using this product, provide the manufacturer's technical
representative on-site to familiarize installers with proper procedures.
D. New Concrete: Apply cure-seal-hardener to new concrete as soon as the concrete is firm enough to
work on after troweling, except on colored concrete wait minimum of 30 days.
2. Keep surfaces wet with cure-seal-hardener for minimum soak-in period of 30 minutes, without
allowing drying out or becoming slippery. In hot weather slipperiness may appear before the 30
minute time period has elapsed. If that occurs, apply more cure-seal-hardener as required to
keep entire surface in a non-slippery state for the first 15 minutes. For the remaining 15 minutes,
mist the surface as needed with water to keep the material in a non-slippery state.
3. After this period, when treated surface becomes slippery lightly mist with water until
slipperiness disappears.
4. Wait for surface to become slippery again and then flush entire surface with water removing all
residue of cure-seal-hardener.
5. Squeegee surface completely dry, flushing any remaining slippery areas until no residue remains.
WTA Architecture And Design Studio Page 17 of 68
TECHNICAL SPECIFICATIONS
6. Wet vacuum or scrubbing machines may be used to remove residue, provided manufacturer's
instructions are followed.
2. Saturate surface with cure-seal-hardener; re-spray or broom excess onto dry spots.
3. Keep surface wet with cure-seal-hardener for minimum soak-in period of 30 to 40 minutes.
4. If, after the 30 minute soak-in period, most of the material has been absorbed, remove all excess
material using broom or squeegee, especially from low spots.
5. If, after the 30 minute soak-in period, most of the material remains on the surface, wait until it
becomes slippery and then flush entire surface with water removing all residue of cure-seal-
hardener and squeegee completely dry, flushing any remaining slippery areas until no residue
remains.
3.04 PROTECTION
A. Protect installed floors until chemical reaction process is complete; at least three months.
2. Clean floor regularly in accordance with manufacturer's recommendations because water will
accelerate the sealing and scrubbing will impart a shine.
3. Clean up spills immediately and spot-treat stains with good degreaser or oil emulsifier.
B. Precautions and cleaning are the responsibility of the General Contractor until Substantial
Completion.
DIVISION 5.0 METALS
Part 1 General
1.01 SCOPE: Furnish material and equipment and perform labor & services required to complete
fabrication and erection of all metal works.
1.02 RESPONSIBILITY: Contractor shall be responsible for the accurate location of all metal work including
items used to attach material to the parts of the work.
Part 2 Materials
2.01 CAST IRON: Lowest grade acceptable for cast Iron shall be that of BS 321) Grade C. The casting shall be
sharp and of exact form and required shape to fit the parts truly and to hold full dimensions. The
product must be free from air holes, scratches, core nails, flaws and defects of any kind.
WTA Architecture And Design Studio Page 18 of 68
TECHNICAL SPECIFICATIONS
2.02 WROUGHT IRON: Shall be kept free from any crack, blister, flaw and any defect and comply with BS
51, Grade A.
2.04 STAINLESS STEEL SHEET: Shall be of high chromium, high nickel Or approved equal. It shall comply
generally with the requirements of BS 970 EN and be the type established for welding (58B).
2.05 STEEL: Shall be cold-rolled of high tensile strength with good surface finish. Refer to Structural Plans.
2.06 GALVANIZED STEEL: Shall be entirely and evenly coated with zinc and free from stains, bare spots and
other defects, such as blisters, pits, unplated areas, cloudy patches, cracks and stains.
2.07 ALUMINUM SECTIONS OF FITTINGS: Shall be anodized of a minimum thickness 0.02mm of natural
color or of anolok finish as specified. All screws shall be stainless steel or approved alloy, countersunk
flush whenever possible.
1.01 WORK INCLUDED. This section covers the furnishing of all materials, labor, equipment, and
everything listed or mentioned on the drawings and necessary in performing all operations
for the completion of all finish carpentry works in accordance with all applicable drawings
and subject to the terms and conditions of the contract.
A. QUALIFICATION OF WORKMEN
If required by the Architect, the Manufacturer of specified work shall show evidence of his
experience, including a list of projects for which he manufactured work similar in scope and quality to
the specified work.
For actual cutting and fitting of trim and finish materials, use only competent finish carpenters, who
have been thoroughly trained and experienced in the skills required, who are completely familiar with
the materials Involved and the manufacturers’ recommended methods of installation, and who are
thoroughly familiar with the requirements of this work.
B. REJECTION
In the acceptance or rejection of finish carpentry, no allowance will be made for lack of skill on the
part of the workmen.
A. PROTECTION
All means necessary must be utilized to protect the material of this section before, during, and after
installation and to protect the installed work and materials of all other trades. All finish materials
must be stored at 12-inch minimum above the floor.
B. REPLACEMENT
In the event of damage, all necessary repairs and replacements must be immediately made, subject to
the approval of the Architect and at no additional cost to the Owner.
A. INSPECTION
1. Prior to all work covered in this Section, the installed work of all other trades must be carefully
inspect to verify that all such work is completed to the point where this installation may properly
commence.
2. Verify that finish carpentry may be completed in strict accordance with the original design and
all pertinent Codes and Regulations.
B. DISCREPANCIES
2. Do not proceed with the installation in areas of discrepancy until all such discrepancies have
been fully resolved.
1.05 SUBMITTALS
A. SHOP DRAWINGS: Show materials, layouts, details of construction, dimensions and, where
necessary, installation details.
2.01 MATERIALS
A. FINISH WOOD AND WOOD FRAMES
1. All finish wood shall be of quality suitable for painting finish specified and shall be fire
retardant treated. Exterior finish wood shall also be water-repellent treated.
2. Lumber shall be of the best grade available of the respective kinds required for the various
parts of the work, well-seasoned, thoroughly dry, and free from loose or unsound knots, cup
shakes or other imperfections impairing its strength, durability or appearance. All exposed
surfaces shall be smooth unless otherwise specified.
3. Yakal or Guijo shall be used for wood plates, door jambs, head, stair framing, girders, girt, and
for all wood works in contact with masonry and all exposed woodworks where Indicated on
schedule.
4. Narra or Tanguile, kiln dried, shall be used for baseboards, cornices, door casings, and other
moldings, wood framing, paneling, cabinetry and all other woodworks specified in the drawings
to be Narra or Tanguile.
B. SPECIALTIES
1. BASEBOARDS & MOULDINGS: Narra or Tanguile, kiln dried, with size and finishes as indicated
in architecture plans.
2. MAIN STAIR HANDRAIL AND TREADS; Use Narra planks wood in stained finish for stair tread to
be supply by the Owner and to be installed by the Contractor. And use Yakal, Tanguile or Guijo
for Stair Handrail in stained wood finish in wrought iron supports as approved by the Architect.
C. TREATMENT
All wood used for finishing shall be kiln-dried with fire retardant, unless otherwise specified. All
exposed wood shall be kiln-dried to be applied with approved type of wood preservative,
Xyladecor or equal.
D. MISCELLANEOUS
1. ROUGH HARDWARE: Rough hardware shall be provide for all Items such as spikes, nails, bolts,
toggle bolts, anchor bolts, wood screws, straps, clips necessary for the installation of specified
work. Rough hardware items shall be of suitable type and of sufficient size and length to draw the
work firmly together. Anchor bolts for wood nailers shall be steel 1/2-inch diameter. All rough
hardware shall be hot-dip galvanized.
A. Work-in-place, on which specified work is in any way dependent, must first be carefully examined.
Any defect, which may influence satisfactory completion and performance of specified work, must
be report, in writing, to the Architect
C. Architectural woodwork, and other finished woodwork, shall be installed only when normal
temperature and humidity conditions approximate the interior conditions that will exist when the
building is occupied. The building should not be cold and damp, or hot and dry.
3.02 FABRICATION
A. Construction millwork to meet or exceed “ Quality Standards ", for custom grade for exposed
surfaces.
B. Finished work shall be square, plumb and true, and free from defects and blemishes.
C. When it is necessary to cut and fit work at job site, units and materials shall be made with ample
allowance for cutting.
D. All joints shall be formed and made, both in shop and at job site, in such manner as to securely join
members together and prevent warping, splitting and opening up of joined parts due to swelling and
shrinkage.
E. Whenever possible, fastening shall be concealed on surfaces exposed to view. Where not possible,
secure with finishing nails or screws and glue; set all nail heads, and countersink all screw heads and
cover with neatly fitted wood plugs to match grain. Fasten exterior work with non-corrosive
fasteners.
3.03 INSTALLATION
A. Install trim in as long lengths as possible, with tight joints, coped where possible.
B. Secure work with finishing nails or screw and waterproofing glue on surfaces exposed to view, set
all nail heads, and countersink all screw heads and cover with neatly fitted wood plugs to match grain.
C. Apply exterior materials with non-corrosive devices as detailed and as required to complete the
project.
A. Install all hardware listed in FINISH HARDWARE SECTION or required in completing the project.
B. Adjust moving parts to operate properly. (See notes on Hardware Schedule and refer to
architectural plans
PART 1 General
1.01 SUMMARY
A. This Section includes polyurethane buried waterproofing membrane system, fluid-applied, for the
following areas:
1. Trench drains.
2. Vehicular Ramps
3. Balconies and Terraces.
4. Water Features/ Ponds.
5. All Toilets
6. Genset Room and Day Tank Rooms
7. Transformer and Switch Gear Rooms
8. Garbage Rooms
9. Mechanical Equipment Rooms
10. Roof Deck and specified Deck Areas
11. Roof Deck Pump Room
1.03 SUBMITTALS
A. Complete technical product data for each type of fluid-applied waterproofing specified, including
data substantiating that materials comply with specified requirements.
B. Samples, 300mm by 400mm minimum size, of each fluid-applied waterproofing material specified
for project including splice or laps, at joints in substrate a typical penetration detail and termination
detail including protection course.
1. Submit fully and cured samples defining each required coat using different shades colors.
2. Elastomeric sheeting for flashings.
D. Prepare mock-ups for installations as required by the Architect; showing complete waterproofing
requirements. Approved mock-up shall be the basis for installations required for the project.
1.04 WARRANTY
B. Single Source Responsibility: Obtain primary waterproofing materials of each type required from a
single manufacturer. Provide secondary materials only as recommended by manufacturer of primary
materials.
C. Pre-Installation Conference: Review methods and procedures related to work, including but not
necessarily limited to the following:
1. Tour areas to be waterproofed. Inspect and discuss condition of substrate, drains, curbs,
penetrations and other preparatory work performed by other trades.
2. Review waterproofing requirements (drawings, specifications and other contract
documents).
3. Review and finalize construction schedule related to waterproofing work and verify availability
of materials, Installer’s personnel, equipment and facilities needed to make progress and avoid
delays.
4. Review required inspection, testing, and certifying procedures.
1. Product name.
2. Product description (generic product classification).
3. Batch number under which product was produced.
4. National standards with which the product complies.
5. Application instructions.
A. Proceed with waterproofing operations only after substrate construction and penetrating work
have been completed.
B. Proceed with waterproofing operations only when existing and forecast weather conditions will
permit work to be performed in accordance with manufacturer’s recommendations.
1.07 CERTIFICATION
A. Have the manufacturers representative submit certification letter indicating that the manufacturer
is satisfied that the installation and project conditions meet their recommended criteria for
application, type & installation method used.
PART 2 Products
B. Acceptable Products:
PART 3 Execution
A. Clean substrate of projections, irregularities, debris, and substances detrimental to work; comply
with instructions of prime materials manufacturer.
WTA Architecture And Design Studio Page 24 of 68
TECHNICAL SPECIFICATIONS
B. Install cant strips flashings, support, embedded items, drain fixtures, and similar accessories as
shown and as recommended by prime materials manufacturer and as necessary for field conditions.
C. Fill voids, seal joints, and apply bond breakers as recommended by prime materials manufacturer.
E. Mask off adjoining surfaces not to receive fluid-applied waterproofing to effectively prevent
spillage or over-spray of liquid materials outside membrane area.
3.02 INSTALLATION
B. Start installation of waterproofing membrane only in presence and with advice of manufacturer’s
technical representative and under weather conditions acceptable for installations.
C. Apply waterproofing membrane material to substrates and adjoining surfaces indicated to receive
membrane. Apply in accordance with manufacturer’s recommendations to obtain thickness specified
and using applicators and techniques best suited for slope and type of substrate to which applied.
1.If two-coat application is required to obtain membrane thickness specified below, apply second
coat only after initial cost has cured as recommended by manufacturer.
2.Apply 100 or 60 dry mil thickness on required areas as per Part 1 of this specs section.
D. Install sheet-type flashings and joint covers where indicated and as recommended by prime
materials manufacturer. Extend flashings onto perpendicular surfaces and other work penetrating
substrate to not less than 300mm beyond finished surface to be applied over waterproofing, unless
otherwise indicated on drawings.
E. Permit membrane to cure under conditions that will not contaminate or deteriorate waterproofing
material. Block off traffic and protect membrane from physical damage.
F. Install protection course on cured membrane after testing, without delay to minimize period of
membrane exposure.
G. Provide concrete wear slab covering over protection board where indicated. Refer to Section
03320-Concrete Topping.
H. In-Place Testing: Before completed membranes on horizontal surfaces are covered by protection
course or other work, test for leaks. Repair any leaks revealed by examination of substructure, and
repeat test until no leakage is observed.
PART 1 General
1.01 SUMMARY
WTA Architecture And Design Studio Page 25 of 68
TECHNICAL SPECIFICATIONS
A. Provide bentonite waterproofing strips as water stops at structural elements, and where indicated
on drawings:
A. Performance Requirements, General: Provide bentonite waterproofing strips that is watertight and
complies with performance requirements specified, as demonstrated by testing performed by
independent testing laboratory of manufacturer’s standard systems according to test methods
indicated.
1.03 SUBMITTALS
A. Complete technical product data for each type of bentonite waterproofing strips specified,
including data substantiating that materials comply with specified requirements.
B. Samples, 200mm long, of bentonite waterproofing strips material specified for project.
1.04 WARRANTY
B. Single Source Responsibility: Obtain bentonite waterproofing strips from a single manufacturer.
1. Product name.
2. Product description (generic product classification).
3. Batch number under which product was produced.
4. National standards with which the product complies.
5. Application instructions.
A. Proceed with waterproofing operations only after substrate construction and penetrating work
have been completed.
B. Proceed with waterproofing operations only when existing and forecast weather conditions will
permit work to be performed in accordance with manufacturer’s recommendations.
PART 2 Products
2.01 MANUFACTURERS
A. Acceptable Manufacturers:
1. American Colloid Co.
2. System 7 Corp.
3. Kunimine Industries.
4. Other approved equivalent by the Architect.
2.02 PRODUCTS
2.03 MATERIALS
A. Definition of Bentonite: Loose, dry high-swelling Wyoming –type granular bentonite clay, also
known as sodium bentonite, minimum 85% montmorillonite (hydrated aluminum silicate), 90%
minimum passing 20-mesh sieve and 10% maximum passing 200-mesh sieve.
PART 3 Execution
A. General: Proceed with waterproofing strips only after substrate work to receive bentonite strips
application is complete.
B. Clean substrate of projections, irregularities, debris, and substances detrimental to work; comply
with instructions of prime materials manufacturer.
3.02 INSTALLATION
B. Start installation of waterproofing strips only in presence and with advice of manufacturer’s
technical representative and under weather conditions acceptable for installations.
D. Where construction joints are indicated to be protected by bentonite waterstops, place concrete
directly over waterstops.
PART 1 General
A. This section includes Capillary/Crystalline Type Waterproofing Systems for the following areas.
1. Elevator, sump and sewage pits, holding tank, and all other pits at Basement Level.
2. Closed water retaining structures (Underground Reinforced Concrete Water Tanks and Fire
Water Tanks).
a. Interior waterproofing application (floors, walls and ceilings) prior to finishing coat with
food quality epoxy coating.
3. All Basement level perimeter retaining walls, including walls and floors of chases where these
chases will open to the upper level/exterior.
B. Obtain capillary type waterproofing materials of each type required from a single manufacturer.
Provide secondary materials only as recommended by manufacturer of primary materials.
C. Pre-Installation Conference: Review methods and procedures related to work, including but
not necessarily limited to the following:
1. Tour jobsite areas to be waterproofed. Inspect and discuss condition of substrate, drains,
curbs, penetrations and other preparatory work performed by other trades.
2. Review waterproofing requirements (drawings, specifications and other contract
documents).
3. Review and finalize construction schedule related to waterproofing work and verify
availability of materials, Installer's personnel, equipment and facilities needed to make
progress and avoid delays.
4. Review required inspection, testing, and certifying procedures.
1. Product name.
2. Product description (generic product classification).
3. Batch number under which product was produced.
4. National standards with which the product complies.
5. Application instructions.
A. Proceed w/ waterproofing operations only after substrate construction & penetrating work have
been completed.
WTA Architecture And Design Studio Page 28 of 68
TECHNICAL SPECIFICATIONS
PART 2 Products
A. Manufacturers: Subject to compliance with requirements, provide products of one of the following:
1. Vandex.
2. Xypex.
3. Penetron
4. Other equivalent acceptable products.
2.02 PRODUCTS
A. General: The required capillary waterproofing shall be complete systems based on manufacturer’s
specific recommendation for each application type required, and shall include, but not limited to,
mortars, grouts, sealants, bentonite strips, etc., to make a complete watertight system application.
1. Dry powder compounds composed of Portland cement, silica sand, and other active chemicals.
2. Applied as a slurry coat to concrete to cause catalytic reaction in the pores and capillary tracks
of the concrete.
3. This reaction generates non-fibrous crystalline growth that seals the concrete against the
penetration of water.
PART 3 Execution
3.02 MIXING
3.03 INSTALLATION
B. Start installation of capillary-type waterproofing membrane only in presence and with advice of
manufacturer's technical representative.
D. Permit waterproofing to cure under conditions that will not contaminate or deteriorate
waterproofing material. Block off traffic and protect membrane from physical damage.
Part 1 General
1.01 SCOPE: This section deals with all damp proofing works for walls and floors.
Part 2 Products
2.01 MATERIALS: For all concrete slabs to receive wood flooring, use 1.0mm thick polyethylene foam with
polyethylene sheet, E-wha foam by E-wha Foam Philippines, Inc or approved equal.
For all exterior CHB walls and walls to receive wood paneling or wallpaper finish, use Rebtite L as
manufactured by Rebtrade Int’l Corp. or Shelby Plastic Sealer by Century Chemical Corp.
PART 1 General
Drawings and general provisions of Contract, including General and Supplementary Conditions and
Division 1 Specifications Sections, apply to this section.
1.02 SUMMARY
A. Thermal Resistivity: Where thermal resistivity properties of insulation materials are designated by
R-values they represent the rate of heat flow through a homogenous material exactly 25mm thick,
measured by test method included in referenced material standard or otherwise indicated. They are
expressed by the temperature difference in ºF between the two exposed faces required to cause one
BTU to flow through 0.0929 square meter (one square foot) per hour at mean temperatures
indicated.
B. Fire Performance Characteristics: Provide insulation materials which are identical to those whose
fire performance characteristics, as listed for each material or assembly of which insulation is a
part, have been determined by testing, per methods indicated below, by UL or other testing and
inspecting agency acceptable to authorities having jurisdiction.
1. Surface Burning Characteristics: ASTM E 84.
2. Fire Resistance Ratings: ASTM E 119.
3. Combustion Characteristics: ASTM E 136.
1.04 SUBMITTALS
A. Product Data:
1. Submit manufacturer's product literature and installation instructions for each type of
insulation material required.
2. Submit manufacturer's product literature and installation instructions for fasteners and
adhesive and tapes required for the work.
3. Submit 300mm x 300mm samples for each type of insulation required.
General Protection: Protect insulation from physical damage and from becoming wet and
soiled. Comply with manufacturer's recommendations for handling, storage and protection
during installation.
PART 2 Products
A. General: Provide insulating materials which comply with requirements indicated for materials,
compliance with referenced standards, and other characteristics.
B. ROCKWOOL INSULATION
1. Acceptable Manufacturers:
a. Rockwool Denmark.
b. CSR Bradford Rockwool.
c. Lapinus Rockwool.
WTA Architecture And Design Studio Page 31 of 68
TECHNICAL SPECIFICATIONS
4. For Sound Insulation under Genset : Provide rigid type with one face with perforated aluminum
3
foil facing, 80kg/m , 50mm thick, “FIBERTEX-R80 with perforated Thermofoil facing”, CSR
Rockwool or approved equivalent.
A. Adhesive for Bonding Fiberglass Insulation: Type recommended by insulation manufacturer, and
complying with requirements for fire performance characteristics.
B. Mechanical Anchors: Type and size indicated or, if not indicated as recommended by Insulation
Manufacturer for type of application and condition of substrate, subject to Architect's approval.
1. Use mechanical pins with self-locking washers for underslab insulation.
PART 3 Execution
A. Require Installer to examine substrates and conditions under which insulation work is to be
performed. A satisfactory substrate is one that complies with requirements of the section in which
substrate and related work is specified. Obtain Installer’s written report listing conditions detrimental
to performance of work in this section. Do not proceed with installation of insulation until
unsatisfactory conditions have been corrected.
B. Clean substrates of substances harmful to insulation or aluminum foil including removal of
projections which might puncture insulation.
A. Comply with manufacturer's instructions for particular conditions of installation in each case. If
printed instructions are not available or do not apply to project conditions, consult
manufacturer's technical representative for specific recommendations before proceeding with
work.
B. Extend insulation full thickness as shown over entire area to be insulated. Cut and fit tightly around
obstructions, and fill voids with insulation. Remove projections which interfere with placement.
C. Apply a single layer of insulation of required thickness, unless otherwise shown or required to
make up total thickness.
D. On wall applications, provide expanded metal lath to hold insulation. Provide mechanical anchors
with washers to hold metal lath in place.
A. Fiberglass: Size Insulation to Cover Underside of Slab: Apply adhesive to slab and set fasteners as
recommended by the insulation manufacturer. After curing adhesive, or when condition for
adhesive installation set by the manufacturer is already achieved, install insulation over mechanical
pins and install self-locking washers flush with the insulation to secure. Butt all edges of insulation.
3.05 PROTECTION
General: Protect installed insulation from harmful weather exposures and from possible physical
abuses, where possible by non-delayed installation of concealing work or, where that is not
possible, by temporary covering or enclosure.
PART 1 General
A. Extent of fluid-applied traffic topping waterproofing is indicated on drawings and provisions of this
section.
1. Parking, Driveways and Curb areas above Ground Floor Leasable spaces.
A. Manufacturer’s Qualifications: Firm with not less than 5 years of successful experience in
producing materials of types required, for project applications equivalent to requirements for this
project. Provide secondary materials only as recommended by manufacturer of primary
waterproofing materials.
Architect and Owner. Record (Contractor) discussions of conference and decisions and agreements
(or disagreements) reached, and furnish copy of record to each party attending. Review foreseeable
methods and procedures related to waterproofing works, including but not necessarily limited to the
following:
1.04 SUBMITTALS
A. Product Data: Submit manufacturer's technical product data, installation and maintenance
instructions, and written recommendations for waterproofing work. Include data indicating that
materials comply with requirements.
1. Waterproofing system.
2. Sheet flashing material.
3. Sealant.
B. Samples: Submit 300mm square samples of fully cured fluid-applied traffic topping
waterproofing materials, in each color required for project, including reglet and flashing
construction of typical horizontal to vertical surfaces.
C. Shop drawing for approval by the Architect, showing waterproofing details for typical installations
and other details as requested by the Architect.
A. Deliver waterproofing materials in manufacturer's unopened, labeled containers, and comply with
manufacturer's instructions for storage and handling.
A. Submit a written warranty, executed by the Contractor, Installer and Waterproofing Manufacturer,
agreeing to repair or replace waterproofing which fail in materials or workmanship, within the
specified warranty period. Failures include failure due to normal waterproofing exposure, but
excluding failures due to unusual weather phenomena, failure of substrate, fire, or abuse by
traffic or other activities.
A. Weather Condition Limitations: Proceed with fluid-applied waterproofing and associated work
only when weather conditions will permit unrestricted use of materials and adequate quality
control of work being installed, in compliance with requirements and with recommendations of
primary waterproofing materials manufacturers.
1. Do not apply materials unless surface to receive coating is clean and dry, or if precipitation is
imminent.
PART 2 Products
A. Liquid elastomer coating , either one-component or two-component mixture for application in one
or more coats with color of top coat selected by the Architect from manufacturer's standard colors
and approved colors for heliport markings. Provide cured membrane complying with ASTM C 957.
B. Available Products: Subject to compliance with requirements, products that may be incorporated
in the work include, but are not limited to, the following:
1. SONOGUARD, Sonneborn.
2. AUTO-GARD II by TheNeogard Corp.
3. VULKEM 350/345/ 346 TRAFFIC DECK COATING; Tremco.
4. Other approved equal
C. Miscellaneous Products: Provide other required flashing, reglet, cant and sealing products,
including aggregates as recommended by manufacturer.
D. Wet Mill Thickness: 25 mils base coat, 40 mils total top coats with aggregate, minimum.
PART 3 Execution
3.01 PREPARATION
C. Fill voids, including nonmoving joints and rough areas of substrate, with high durometer
elastomeric sealant or feathered-out coating of membrane material, in manner recommended
by manufacturer. Form coves at corners and penetrations of substrate.
F. Mask off adjoining surfaces not to receive traffic topping, and close off deck drains, to
prevent spillage and migration of liquid materials outside membrane area.
3.02 INSTALLATION
A. General: Apply membrane liquids by spraying roller coating, or distributing with notched squeegee
to provide uniform thickness. Trowel heavy-bodied mixtures in place uniformly as recommended by
manufacturer.
B. Apply total thickness of traffic topping in number of coats recommended by manufacturer, using
special top coating to achieve wear resistance and weather resistance as required and to provide
color and texture required.
A. Apply base membrane of urethane elastomer and aggregate-bearing top course in accordance
with manufacturer's instructions.
A. It is required that traffic topping be watertight and not deteriorate excessively for normal weather
exposure and for normal traffic in applications indicated, nor for manufacturer-recommended
cleaning procedures, for period of warranty.
B. Test each near-level deck area for leaks immediately after nominal cure of completed coating.
Flood each area for period of 24 hours, and examine lower surfaces of coated decks for evidence of
leakage, repair work at any leaks, and repeat test until no leakage is observed.
3.05 PROTECTION
A. Provide protections to ensure that work will be without damage or deterioration at time of final
acceptance.
1. Procedure:
a. Waterproofed area shall be flood tested for 24 hours after system has cured (24 hours at
75 degree F and 50% relative humidity) and prior to installation of protection course.
b. Plug drains and place barriers to contain the water.
c. Flood deck to a depth of 50mm for the duration of the test.
d. Repair any leaks that may appear.
WTA Architecture And Design Studio Page 36 of 68
TECHNICAL SPECIFICATIONS
3.07 CLEANING
A. Remove debris resulting from completion of coating operation from the project site.
Part 1 General
1.01 SUBMITTALS: Submit Caulking and Sealant Manufacturer’s Instructions for application and Priming.
Samples shall be submitted upon request from the Architect.
B. Work adjacent to joints shall be cleaned free of smears of caulking or Sealant compound as work
progresses. Surfaces that are difficult to clean shall be protected with masking tape.
C. Damaged work, as determined by the Architect, shall be repaired to the Architect’s satisfaction.
Part 2 Products
A. CAULKING: Vegetable oil and/or resin base, gun grade, elastic compound, conforming to FS TT-
C598B, Type I, color as selected by Architect from the manufacturer’s Standard Color Range. Dow
Corning or equal.
B. PRIMER FOR POROUS SURFACES: Non-staining product of Caulking Manufacturer for use when
recommended.
C. JOINT BACKING: Back-up material to have outside diameter of thirty (30%) percent greater that
joint width and shall be one of the following: Oakum, picked dry and free of oil and tar; closed-cell
Neoprene, tubulator rod stock; or Polyethylene rod stock.
A. SEALANT for building construction perimeter joints such as windows, doors, panels, expansion
joints, control, coping, etc., shall be a two-component non-staining elastomeric sealing compound
based on liquid Polysulfide Polymer. Dow Corning or equal. Color to match adjacent materials as
closely as possible.
C. JOINT BACKING: Closed-cell Neoprene or polyethylene Rod E-wha foam with square cross section.
Width of materials shall be thirty (30%) percent greater than joint width.
E. PRE-FORMED COMPRESSIBLE JOINT FILLER (For other than Poured-in-Place concrete): Non-
Extruding and Non-Bituminous Type, ASTM D1752, Type I or II.
Part 3 Execution
3.01 LOCATION
A. Caulking compound shall be installed in interior joints, including joints around pipes, conduits and
ducts which penetrate interior walls and partitions and all other locations indicated in the drawings.
A. Do not apply exterior sealant in damp or rainy weather or until surfaces have thoroughly dried
from the effects of such weather.
B. Install materials only after preparatory work has been approved and when adjoining work is in
proper condition to receive it. Apply to masonry joints before they have been treated with a water-
repellent or masonry preservative.
3.03 INSTALLATION
A. Installation shall be performed in strict accordance with the Manufacturer’s latest printed
instructions. Caulking or sealant compound shall be forced into opening with hand or air-powered
caulking gun and tooled so as to fill void completely. Gun shall have nozzle of proper size to fit joint.
B. Take care not to smear adjoining surfaces with caulking or sealant compound. Finish exposed butt
joint surfaces slightly concave by tooling unless otherwise indicated or directed by the Architect.
Part 1 General
1.01 SCOPE: The work in this section shall include the furnishing of all items of finish hardware as herein
after specified, or necessary for completion of this project.
1.02 QUALITY: All specified materials furnished under this section shall be free from defects and
blemishes. The hardware supplier shall repair or replace any item of finish hardware which may
prove to be defective before final acceptance of work
Part 2 Products
2.01 HARDWARE: Refer to Schedule of Hardware. All other hardware items not indicated in the Schedule
of Hardware shall be approved by the Architect.
2.02 HINGES: For doors, use Stanley or Lawrence (or approved equal), 4” x 4 heavy Duty 4-Ball bearing
hinges, with removable pin in satin stainless finish or approved equivalent.” minimum size, non
ferrous hinge with stainless steel non-removable pin for doors opening outside; loose pin for average
doors and ball bearing for high frequency doors and doors equipped with door closers. Provide 3 pcs.
per leaf for doors 0.8m wide or less and 4 pcs. per leaf for doors wider than 0.8m.
2.03 LOCKSETS: All locksets and grip handles shall be I.D. or Architect-approved. Approved brands are
Baldwin, Schlage, Ives, Hettich, and Hafele or approved equal.
2.04 DEADBOLT: Bored cylindrical deadbolt ANSI grade 1, single cylinder with thumbturn US26D.
2.05 FLOOR HINGE: For double swing doors, Use Mckinney ‘Ajax’ floor hinges, or approved equal, in I.D.
or Architect approved finish
2.06 FLUSH BOLT: For inactive leaf of double wooden doors, provide 2 pcs. Ives #262 flush bolts, or
approved equal, in I.D./Architect approved finish.
2.07 CABINET HARDWARE: Cabinet hardware such as drawer guides, concealed hinges, and the like
shall be supplied and installed-by “Others”, Owner and Architect-approved.
2.08 DOOR CLOSERS: Provide LCN 1073H door closers where required by the Architect or Owner.
2.09 EXIT DEVICE: For fire exit doors, 1 set rim fire exit device with lever trim, US32D.
2.10 VINYL DOOR SHOE: For fire exit doors, mil finish aluminum, Pemko 234 AV
2.11 JAMB & HEAD and SEAL: For fire exit doors, adhesive backed silicone gasketing, PEMKO S88Tan
2.12 SADDLE THRESHOLD: For fire exit doors, 2.5” wide saddle threshold, mil finish aluminum, PEMKO
166A.
2.17 OTHERS: Other hardware not indicated herein shall be verified with the Architect and Interior
Designer, Contractor-installed.
Part 3 Execution
3.01 APPLICATION: All hardware shall be installed in a neat, workmanlike manner following the
manufacturer’s instruction. Fasteners supplied with the hardware shall be used to secure hardware
to wood surfaces. Appropriate and applicable fasteners used for hardware shall be protected from
paint, stains, blemishes and damage. All hardware shall be properly adjusted and checked in the
presence of the Architect or his representative to show that they operate properly. After the
hardware is checked, the keys shall be tagged, identified and delivered to the Owner.
A. The glass and aluminum contractor shall include all labour, materials, tools, equipment and services
required to manufacture, assemble, deliver (including all import documents), and install all items
necessary for the proper execution and completion of said items of work, as shown on the drawings,
as indicated in the specifications, and as required by job conditions to provide a complete installation.
B. All work required shall comply with the requirements of the contract, including general and
supplementary conditions, along with the drawings, specifications and all other contract documents.
C. The extent of work required for the supply and installation of the storefront/curtain walls,
windows, doors, and louvers; shall include but not limited to the following:
1. Entire Storefront/Curtain Walls, Entrances, Windows, as shown in schedules, and all required
and approved hardware.
2. Glass and glazing.
3. Sealant, flashing, and backer rods between glass and aluminum work, and adjacent
construction. Sealant, backer rods, shims, gaskets, etc., as necessary within the system.
4. Testing (Laboratory and Field).
5. Final Cleaning.
6. Coordination with other trades.
7. All protective materials during transportation, installation, and prior to completion of the glass
and aluminum work.
D. The work required is performance based, and shall be developed, documented, tested and
warranted to comply with the design intentions indicated on the Drawings, Specified Performance
Criteria, and relevant statutory and project requirements. Drawings indicate generic design principles
and intentions only. All anchors, plates and other items associated with fixing in-place the glass and
aluminum work shall be supplied and installed by the Glass and Aluminum Contractor. Allowance shall
be made for varied installation sequence due to required construction openings and interfacing
requirements with other trades. The whole of this system shall be to a high standard. Acceptance
criteria (as outlined in this Specification) for all finished work shall reflect this high standard.
Provision of staff responsible for keeping the Glass and Aluminum Contractor works area on site clean
at all times, for keeping safety railings in place and access equipment in a safe condition at all times,
for cleaning the glass and aluminium assemblies required and for carrying out service and
maintenance work during the Warranty Period. Programs for all activities which are consistent with
the Main Contractor’s working schedule, and which comply with the overall program for this project.
Co-ordination of all activities with all other subcontractors and trades working on this project.
A. The drawings and Specification are for the purpose of defining the design intent and performance
requirements. The drawings do not claim to solve movement or structural requirements, pressure
equalization, waterproofing, air sealing, glass movement, seismic performance.
B. Alternatives proposed by the Glass and Aluminum Contractor to the design nominated on the
drawings will be considered provided they satisfy all the aesthetic and performance requirements of
the specifications, drawings and schedules.
1.05 REFERENCES
The following sections outline International Codes, Standards and Regulations to which all work
outlined in the Documents must conform. The Sub-contractor is responsible to ensure that all works
are in complete compliance with these and other Codes, Standards and Regulation referred to within
this Specification.
1. No substitution for the following codes will be accepted without endorsement from the Architect.
2. The Glass and Aluminum Contractor shall be responsible for ensuring all work is carried out in
accordance with the code requirements outlined in this specification.
3. Wherever there is a conflict between different codes, the requirements of the more stringent code
shall apply.
Comply with current edition of required Standards and Codes of Practice, including:
1. British Standards.
2. AAMA Architectural Aluminium Manufacturers' Association Standards mentioned herein.
3. ANSI American National Standards Institute Standards mentioned herein.
4. AS/NZ Australian/New Zealand Standards mentioned herein.
5. ASTM Standards mentioned herein.
1.07 SUBMISSIONS
Submit (within 1 week of award) representative samples of products and materials, including finishes and representative f
The Glass and Aluminum Contractor shall submit 2 sets minimum of drawings and calculations that are
certified by a Professional Structural Engineer (representing the Glass and Aluminum Contractor) to the
Architect for notation and file:
Submit comprehensive, detailed and dimensioned shop drawings to indicate all set out and
construction details not indicated in the Contract Documents, adjacent work by others, and for all
proprietary products where required details are not indicated in the manufacturer's product data.
Manufacture should not commence until approval to use the relevant shop drawings has been obtained
from the Architect.
Erection tolerances.
Machined slots, keyholes and other methods for handling and connecting components.
Junctions and trim to base-structure and adjoining surfaces.
Fully dimensioned set out drawings and templates.
Glazing materials including sealants, gaskets, tapes, setting and spacer blocks.
Rebate depth, and edge restraint.
Clearances and tolerances.
Methods of in-service glass replacement.
Hardware, fittings and accessories.
WTA Architecture And Design Studio Page 42 of 68
TECHNICAL SPECIFICATIONS
Submit a comprehensive manual containing all installation procedures, equipment and personnel
required for acceptance prior to the commencement of installation works.
Submit a comprehensive manual containing recommendations for operating, and routine cleaning
and maintenance, and all information required to ensure the full service capability of the work,
including source of replacement components, and methods of replacement of damaged components,
for a period not less than the warranty period. This is to be completed prior to the completion of
work.
The method of cleaning and timetable are to be specified together with cleaning agents which can
and cannot be used.
Submit (within one (1) week of award) all manufacturer's product specification and test data,
manufacturer's quality assurance documentation, preparation and installation recommendations.
Prepare as-built drawings. Submit progress reports on monthly intervals and provide complete as-
built documentation at completion of work
1.18 WARRANTIES
Provide a warranty for materials and workmanship of the Glass and Aluminum Contract for a period
of 10 Years after the expiry of the one (1) year Defects Liability Period (the "warranty period").
Provide all manufacturers’ product warranties as required in detailed specificationssections attached
herewith. Also provide a warranty to cover all the costs of materials, labour and equipment to
remove any defective components of the glass and aluminium work and replace them. This warranty
shall also cover the costs associated with removing and replacing internal finishes trims and services
so that remedial works can be carried out. The content of each warranty is to be approved by the
Architect and the Owner.
A. Generally
Be responsible for the warranty period of all functional and performance design requirements of the complete glass and
Performance design shall comply with the current edition of the relevant Standards. The glass and
aluminium system shall be water proof and weather proof, able to support all dead loads, wind loads,
live loads and other loads imposed on the glass and aluminium systems, accommodate all movements
WTA Architecture And Design Studio Page 43 of 68
TECHNICAL SPECIFICATIONS
due to base structure movement and deflections, and retain its appearance for the service life of the
system without failure or breakdown of individual materials and components.
B. Dimensional Stability:
All work shall have adequate dimensional stability to function properly and prevent damage to
adjacent or applied work by others.
C. Identification:
Provide a complete numbering system and schedule for all glazing panel units. Each panel shall be
individually numbered in such a way that the manufactured history can be traced. Provide an
approved permanent concealed marking system. Submit details.
Identify the location of each individual panel on shop drawings and "as-built" drawings.
Before the panels are delivered to the Site, provide suitable marks or identification for each panel for
showing its correct location and orientation when installed.
Identification labels on glass shall be made on a non-marking adhesive tape fixed to the glass.
A. Profiles:
Design components so that sizes, profiles, dimensions and architectural style are as close as possible to
those indicated on the Tender Drawings. Indicate any variations on the shop drawings.
B. Applied finishes:
The design of the components, selection and application of finishes, and installation procedures shall
ensure a high standard of applied finish protection during construction. Develop and implement
procedures to eliminate scratches, marks and blemishes to finished surfaces. Indicate procedures on
shop drawings and in the installation procedures.
The design of the components, fabrication and installation procedures shall ensure a high standard of
flatness, joint and edge straightness, and alignment of mating surfaces of joinery. Close attention shall
be given to cutting and cut edge treatment procedures, stiffening and the tightening of fixings and
fastenings, which may cause distortion or warping.
D. Exposed sealants:
1.21 MATERIALS
Provide protective coatings to prevent corrosion of metal components, including concealed and
structural components.
Adjacent materials and products generally shall be chemically and electrolytically compatible with each
other and with relevant substrates, and shall be non-staining and non-bleeding.
Metals shall be isolated to prevent electrolytic action and corrosion from adjacent dissimilar metals and
absorptive substrates, by an approved coatings or spacers.
Submit details of coatings, spacers and other means of isolation between dissimilar or incompatible
materials to prevent corrosion, perforation of protective coatings, or other damage due to electrolytic
action, chemical attack, or to any other cause including bad practice, incorrect installation, or inefficient
fixing methods.
Where there is a known or anticipated incompatibility between materials proposed under this Section
and materials to be provided by others, submit details of proposed separation, coatings and spacers.
Submit certificates from relevant manufacturers confirming acceptance of the use of the selected
products in the manner and on the substrates proposed.
A. Air Infiltration and Water Penetration: Design and install the manufacturer's glazed curtain walls,
window and entrance systems to permanently resist leakage of air and water through the system in
accordance with the following:
1. Air Infiltration: Differential static test pressure shall be 150 Pa. Air leakage of test specimen of
fixed wall area shall not exceed 0.010 m3min-1 per square meter of exterior surface, exclusive of
any operating window and door areas.
2. Water Penetration: Refer to Item 160.
B. Structural Performance: Design, engineer, fabricate, and install the glazed curtain walls, windows,
and entrance systems to withstand effects of wind load as per NSCP.
1. Structural Test Pressure shall be equal to 150 percent of the inward and outward acting
design pressures.
2. Deflections: The systems shall be capable of withstanding building movements and
weather exposures including wind loading and of performing within the allowable
deflection governed by codes under the required design loads both positive and negative.
a. Net permanent deflection of framing members shall not exceed 1/1000 times span.
b. There shall be no failure or gross permanent distortion of framing members.
c. At connection points of framing members to anchors, combined movement of anchor
relative to building structure, and framing member relative to anchor, shall not exceed 3mm
in any direction.
d. Perpendicular deflection: Not to exceed 1/180 of the unsupported span or 20mm,
whichever is less.
e. Parallel Deflection: Not to exceed an amount that will reduce glass bite by less than 75
percent of the design dimension, and reduce edge clearance to less than 25 percent of
design dimension or 3mm, whichever is less.
3. Building Movements:
a. Movement joints shall be provided to accommodate the full range of tolerances, thermal
movement, lateral movement, floor and beam sags, live load deflection and column
settlement. In no case shall the computed and as-built glass bite relative to metal frame be
less than 10mm.
b. Lateral movements as specified and required by code, shall be accommodated.
Thermal Movements: The systems shall be capable of withstanding thermal movements
without causing buckling, stresses on glass, failure of sealants, damaging loads on
fasteners, or other detrimental effects, based upon a minimum material temperature
range of 70 deg. C; regardless of surface areas exposed to exterior and interior. damaging
WTA Architecture And Design Studio Page 45 of 68
TECHNICAL SPECIFICATIONS
loads on fasteners, or other detrimental effects, based upon a minimum material temperature range
of 70 deg. C; regardless of surface areas exposed to exterior and interior.
1.23 TESTING
PERFORMANCE TESTING
General:
The proposed testing programme and procedure shall be approved prior to the
commencement of testing.
Field Testing:
The testing shall include all actual job-site components, including all glazing configurations,
sealants, adhesives and gaskets.
Instruments and gauges shall be selected, tested and located by the testing officer-in-charge
in consultation with the Main Contractor and Architect.
Each test shall cover an area of not less than 30.00 sqm. and not less than 5 lineal m of work.
Conduct field water test in accordance with AAMA 501.3 “Field Check For Water Penetration
through Installed Exterior Windows, Curtain Walls And Doors By Uniform Static Pressure
Difference”.
Submissions:
Submissions shall include the following:
Part 1 General
1.01 DESCRIPTION: This section covers Glass and Glazing required for this work which includes, but is not
necessary limited to , tempered glass, float glass, and mirrors.
1.02 PRODUCT DELIVERY, HANDLING, & STORAGE: Deliver materials to the project site in their original
unopened containers bearing label clearly identifying manufacturer’s name, brand and grade. Store
under cover and protect from damage. Label shall be affixed to each pane of glass indicating
thickness and shall remain on glass until final cleaning.
1.04 PROTECTION & DAMAGED WORK: Protect specified work, adjacent work and materials against
damage during progress of the work. Glass damaged due to improper handling or setting shall be
replaced at no extra cost to the Owner.
1.05 GUARANTEE: the glass Manufacturer shall provide written material guarantee for a period of ten (10)
years, beginning at substantial completion of project, guaranteeing glass against all defects and loss of
hermetic seal. The General Contractor shall provide written guarantee for labor to replace defective
glass during Glass Manufacturer’s 10-Year Material Guarantee Period.
Part 2 Materials
2.01 GLASS
A. EXTERIOR/INTERIOR GLASS: Tempered Clear Glass, Reflective Tempered Glass, Tinted Tempered
Glass, Frameless Tempered Glass as recommended by Glass or Curtain Wall Manufacturer, per
approved finish unless otherwise specified. Refer to plans for locations.
B. INTERIOR GLASS/MIRROR: 6 mm. thick clear float glass, facial mirrors on 12mm marine plywood
backing. Verify plans for locations if necessary.
Part 3 Execution
3.01 INSTALLATION
A. Installation, including preparation by glaziers, glass positioning, and clearances and tolerances,
setting and application of glazing materials shall comply with recommendations of the Glass
Manufacturer.
The contents of this section apply to all section of this Division unless otherwise specified or
modified.
1.01 QUALIFICATIONS
A. Before specified material or system is installed, the manufacturer or his authorized agent shall
inform the Architect, in writing, that he has familiarized himself with the Contract Documents, the
environmental conditions and the intended occupancy for this specified project. Furthermore, he
shall ascertain that his material or system is appropriate to the conditions to be encountered therein.
B. Before specified material or system is installed, the manufacturer shall Inform the Architect, in
writing, that he is familiar with the quality of workmanship of the installer and approves him as the
installer of his material or system for this specified project.
WTA Architecture And Design Studio Page 47 of 68
TECHNICAL SPECIFICATIONS
A. Deliver materials to the project site with manufacturers’ labels intact and legible. Where materials
are factory-packaged, same shall be delivered in original sealed containers.
B. Handle specified Item and/or its components in such manner as to prevent damage or
deformation. Properly protect same from harmful elements or damage by other work prior to its
incorporation into the project.
C. Materials shall be stored in areas where products will not be subjected to moisture or to
temperature or humidity extremes.
1.03 PROTECTION
A. The installer shall protect any existing work subject to damage during installation of specified work.
B. The installer shall protect finished work that is readily subject to damage by subsequent work or
environmental conditions.
Fabricators of custom work shall take actual measurements in field to verify or supplement
the dimensions indicated and shall be responsible for accurate fit of specified work.
A. Facilities shall be provided by the Contractor as needed for the proper inspection of all
specified work.
Work-In-place, on which specified work is in any way dependent, shall be examined. Any
defect, which may influence satisfactory completion and performance of specified work, shall
be reported, in writing, to the Architect. The absence of such notification shall be construed
as acceptance of work-In-place.
All defective or damaged work shall be restored to initial condition. Defective or damaged
Items and/or components that cannot be repaired or restored to initial condition shall be
removed and replaced at no additional cost to the Owner.
1.08 CLEANING
A. At the end of each day, the installer shall remove from the project site all accumulated
trash generated by his work.
B. Upon completion of specified work, all surfaces shall be thoroughly cleaned of dirt or
other foreign materials in accordance with manufacturers latest printed directions.
The publications listed below form a part of this specification to the extent referenced. The
publications are referred to in the text by the basic designation only.
A. Federal Specification:
A. Term Usage: The term plastering for this work shall apply to both interior and exterior
works of walls and ceilings in smooth finish.
B. Exterior walls, where indicated shall have plain smooth painted finish.;
B. PROTECTION FROM SUN AND DRY WINDS: During the application of the finish coat, and
for a period of 48 hours following the completion of finish coat application for any given
area, the surface of the plaster and stucco shall be protected from direct sunlight and
direct winds. Use of tarpaulins or other temporary means may be acceptable.
2.01 MATERIALS: Provide materials conforming to specifications and the requirement specified.
A. PORTLAND CEMENT: ASTM C 150, gray Portland cement type 1,11 or Ill; white Portland
cement, Type I or Ill with 1/2-inch chopped alkali resistant fiberglass strands, minimum 1
1/2-pounds per sack cement
B. PLASTIC CEMENT: ASTM C 150, Type I or II, except for the limitations on insoluble
residue, air entrainment, and additions subsequent to calcination. Plasticizing agents may
be added to Portland cement Type I and II In the manufacturing process, but not In
excess of 12 percent of the total volume with 12.5 mm (112’) chopped alkali resistant
fiberglass strands, minimum I-1/2 pounds per sack of cement.
D. AGGREGATE
I. Sand for Portland Cement Plaster and Stucco: ASTM C 144, except gradation of sand shall
conform to the following requirements:
Sand for finish Coats: Sand for finish coat shall be white and shall be graded within the limit
shown above for basecoats, except that the sand shall pass the No. 8 sieve, and for smooth
the sand shall pass the No. 30 sieve.
E. WATER: Clean, fresh, suitable for domestic consumption, and free of mineral and organic
substances that affect the hardening or durability of the plaster or stucco.
F. LIME : Shall be hydrated lime with the requirement that the unhydrated Calcium Oxide
and Magnesium Oxide in the hydrated product shall not exceed 8% by weight, calculated
on the “as received” basis.
2.02 PROPORTIONING AND MIXING: Except where specified otherwise, materials are specified on
a volume basis and shall be measured in approved containers, which will ensure that the
specified proportions will be controlled and accurately maintained during the progress of the
work.
Measuring materials with shovels’ “shovel count" will not be permitted. Ready-mix plaster(s)
shall be prepared for use by the addition of water only.
A. BASECOAT PROPORTION:
1. Portland Cement Plaster Basecoats: Mix scratch coat In the proportion of one part by
volume of Portland cement to not less than 2 1/2 nor more than 4 parts by volume of
damp loose sand. Mix brown coat in the proportion of one part by volume of Portland
cement and not less than 3 nor more than 5 parts by volume of damp loose sand.
Workability shall govern the actual amount of lime and sand used in the scratch and
brown coats.
2. Masonry Cement Plaster Basecoat: Mix scratch coat in the proportion of one part by
volume of masonry cement to not less than 2 1/2 nor more than 4 parts by volume of
damp loose sand. Mix brown coat in the proportion of one part by volume of masonry
cement to not less than 3 nor more than 5 parts by volume of damp loose sand.
Brown coat shall have the same proportion of sand used in the scratch coat or a greater
proportion of sand than used in the scratch coat, within the limit specified.
3. Scratch Coat for Ceramic Tile Backing: Mix scratch coat in the proportion of one part by
volume of Portland cement to 3 parts by volume of damp loose sand.
A. PORTLAND CEMENT PLASTER FINISH COAT: Mix finish in the proportion of one part by
volume of Portland cement to not more than 2 parts by volume of damp loose sand.
Workability shall govern the actual amount of sand used in the finish coat, within the
limits specified herein. Portland Cement for plaster finish shall be white. Approved
coloring compounds shall be added to produce the required color. Where smooth
trowelled finish is indicated, allow plaster to set up to the extent that It does not flow
ahead or under the trowel, yet has not solidified, then trowel the face lightly to embed
the granules. Do not over-trowel or burnish the surface.
B. MASONRY CEMENT PLASTER AND FINISH COAT: Mix finish coat in the proportion of one
part by volume of masonry cement to not less than 2 parts by volume of damp loose
sand.
2.04 MIXING
A. Except where hand mixing of small patches is approved, mix materials in approved
mechanical mixers of the type in which the quality of water can be controlled accurately
and uniformly. While the mixer is in continuous operation, add approximately 90 percent
of the estimated quantity of water, half of the sand, and all of the cementitious
materials. Introduce the other one-half of the sand into the mixer in that sequence and
mix thoroughly with the remainder of the water until the mixture is uniform in color and
consistency. Avoid excessive mixing or agitation. Discard plaster and stucco, which has
begun to set before It is used; re-tempering will not be permitted. Do not use frozen,
caked, or lumped materials. Empty mixers and mixing boxes after each batch s mixed and
keep free of old plaster. Mix ready-mixed plaster in accordance with the manufacturers
printed instructions.
A. Clean surfaces to which plaster is to be applied of all projection, dust, loose particles,
grease, bond breakers, and foreign matter.
B. Do not apply plaster directly to: (1) surfaces of masonry or concrete that have been
coated with bituminous compound or other waterproofing agents, or (2) to surfaces that
have been painted or previously plastered.
C. Before plastering work is started, wet masonry and concrete surfaces thoroughly with a
fine fog spray of clean water to produce a uniformly moist condition. Check metal
WTA Architecture And Design Studio Page 51 of 68
TECHNICAL SPECIFICATIONS
grounds, corner beads, screeds, and other accessories carefully for alignment before the
work is started. Check expansion and control joints and supporting metal structures to
ensure that expansion and control joints can move unrestrained.
(2) While holding cone firmly against base plate, fill cone with plaster taken directly from
the hose or nozzle of the plastering machine, tamping with a metal road during filling
to release air bubbles.
(3) Screed off plaster level with top of cone. Remove cone by lighting it straight up with
a slow and smooth motion.
(4) Place cone in a vertical position adjacent to freed plaster sample, using care not to
jiggle base plate.
(5) Lay a straightedge across top of cone, again being careful not to vibrate cone.
Measure slump in inches from the bottom edge of the straightedge to the top of the
slumped plaster sample.
3.03 PORTLAND CEMENT PLASTER: Apply base coats with sufficient pressure to curl the keys
around the back of metal lath or wire fabric and to provide good bond on masonry or
concrete bases.
A. PLASTER EXCEPT SCRATCH COAT FOR CERAMIC TILE BACKING: Apply in three coats
to a thickness of not less than 7/8 Inch. Apply the scratch coat not less than 3/8-inch
thick, lightly score horizontally, and moist cure for not less than 24 hours. Apply the
brown coat after the scratch coat has been aged at least 24 hours in addition to the
moist curing period. Apply the brown coat to bring the base coat out to the screeds,
compact and straighten to a true surface with rod and darby, and float to receive
the finish coat. After the brown coat has been moist cured for not less than 24
hours and aged at least an additional 5 days, apply the finish coat to a thickness of
WTA Architecture And Design Studio Page 52 of 68
TECHNICAL SPECIFICATIONS
not less than 1/8 inch. Where any previous coat has become dry, dampen the
surface evenly with water, prior to the application of the next coat.
The finish coat for plaster shall have a trowelled finish. Finish coat for stucco shall be
of the color and texture selected. Moisten plaster and stucco for 24 hours using fine
fog spray of water and apply to the finish coat as frequently as required to prevent
dry-out of the plaster or stucco. Do not saturate the plaster and stucco to the point
where free water stands on the surface. Prevent staining of the finish coat. Provide
moist curing.
A. SCRATCH COAT FOR CERAMIC TILE BACKING: Apply scratch coat and keep
continuously damp for not less than 24 hours before tile is to be set. Scratch coat
shall be applied in the thickness indicated or as necessary to bring the face of the
tile to the required plane, but not less than 1/4 Inch from the face of the material it
is being applied to, and with a level surface within a tolerance of 1/4 Inch In 8 feet.
Apply scratch coat after substantial grounds, plugs, hangers, and other such
accessories have been installed for plumbing fixtures, electrical outlets, and other
fixtures and fittings have been installed that are to be secured to tiled surfaces.
Apply scratch coat with sufficient pressure to ensure a proper bond and key with
the base and a proper base for the setting bed. While the mortar is still plastic, cut
the scratch coat with a trowel at internal vertical angles to the depth of the coat for
the full height of the tile bed. Score horizontally or on one-inch centers for the
extent of the tile bed. Score horizontally or cross-scratch on coats within one hour
after mixing, and at no time shall the mortar be re-tempered. Protect scratch coat
and keep moist during curing period. A leveling coat of the same mix specified for
the scratch coat when the surface of the scratch coat is not level within the
specified tolerance or when a base coat thickness of more than 3.4 inch is required.
Scratch leveling coat and cure for not less than 24 hours.
Upon completion of the building and when directed, cut out and re-patch all loose, cracked, damaged or
defective plaster and stucco. Patching shall match existing work in texture, color and shall be finished flush
with plaster previously applied. All point-patching of plastered surfaces and stucco plaster work abutting or
adjoining any other finish work shall be done in a neat and workmanlike manner. Remove plaster droppings or
splattering from all surfaces. All exposed plastered surfaces shall be left clean, in a condition ready to receive
paint or other finish. Remove protective covering from floors and other surfaces, and rubbish and debris from
the building.
Part 1 General
1.01 GENERAL: The work includes provision and installation of gypsum board as ceiling and wallboard
requirements.
Part 2 Products
2.01 GYPSUM BOARD: ASTM C 38-76a, 12 mm. thickness and lengths as required to suit the applications,
with taped edge and paintable exposed face, Goldbond or Georgia Pacific Regular gypsum board for
typical areas and 12mm thick. Moisture-Resistant gypsum board for areas where there is a high
moisture content, as locally supplied by Union Pacific Ace Industrial or approved equal.
2.02 CEILING & WALLBOARD ACCESSORIES: All metal accessories shall be hot-dipped galvanized. Ceiling
installation shall be Furring M-Bar System unless otherwise specified. Submit samples for Architect’s
approval.
2.03 CONCEALMENT TREATMENT MATERIALS. : Joints between ceiling board panels shall be reinforced
with joint tape and embedding type joint compound concealed with at least two (2) applications of
finishing type joint compound. Screw depressions shall be filled with at least three (3) coatings of joint
compound. Flanges at corner beads shall be concealed with at least two (2) applications of joint
compound. All coats shall be sanded when dry as necessary after each application of joint compound.
The final coat and sanding shall leave Gypsum wallboard treated areas uniformly smooth and flush
with the paper face of the wallboard and ready for paint. Concealment treatment materials shall be
the products of a single manufacturer.
Part 3 Execution
3.01 INSTALLATION: Shall be in accordance with the manufacturer’s latest printed directions as approved
by the Architect and as drawn in the plans.
A. Space 6 mm. dia. hanger rods at 1200 mm o.c. along carrying channels and within 150 mm. of ends
of channel run.
B. Install carrying channels 1200 mm o.c. and within 150 mm. of walls. Position channels for proper
ceiling height, level and secure with hanger wire saddle-tied along channel. Provide 25 mm.
clearance between runners and abutting walls and partitions. At channel splices, interlock flanges,
overlap ends 300 mm & secure each end with a double stand 18-gauge tie wire.
C. Erect metal furring channels at right angles to 1-1/2” carrying channels or main support member.
Space furring 400 mmo.c. and within 150 mm. of walls. Provide 25 mm. clearance between furring
channels with clips or saddle-tie to supports with double-strand 18-gauge tie wire. At splices, nest
furring channels at least 20 mm. and securely wire-tie each end with double-stand 18-gauge tie wire.
D. At light troffers or any opening that interrupt the carrying channels, install additional cross
reinforcing and hangers as required to restore lateral stability of grille.
3.03 CONCEALMENT OF JOINTS & DEPRESSIONS: Joints between ceiling board panels and joints at metal
trim shall be reinforced with joint tape and embedding type joint compound concealed with at least
two (2) applications of finishing type joint compound. Screw depressions shall be filled with at least
three (3) coatings of joint compound. Flanges at corner beads shall be concealed with at least two (2)
applications of joint compound. All coats shall be sanded when dry as necessary after each
application of joint compound. The final coat and sanding shall leave Gypsum wallboard treated
areas uniformly smooth and flush with the paper face of the wallboard and ready for paint.
PART 1 General
1.01 SUMMARY
1.02 SUBMITTALS
B. Shop drawings indicating tile patterns and locations and widths of expansion, contraction, control
and isolation joints in tile substrates and finished tile surfaces.
C. Samples for initial selection purposes in form of manufacturer's color charts consisting of actual
tiles or sections of tile showing full range of colors, textures, and patterns available for each type and
composition of tile indicated. Include samples of grout and accessories involving color selection.
D. Samples for verification purposes of each item listed below, prepared on samples of size and
construction indicated, products involve color and texture variations in sets showing full range of
variations expected.
1. Each type and composition of tile and for each color and texture required.
2. Sample of grout.
3. Divider strips, 100mm long.
A. Single-Source Responsibility for Tile: Obtain each color, grade, finish, type, composition, and
variety of tile from a single source with resources to provide products of consistent quality in
appearance and physical properties without delaying progress of the work.
B. Single-Source Responsibility for Setting and Grouting Materials: Obtain ingredient of a uniform
quality from one manufacturer for each cementitious and admixture component and from one source
or producer for each aggregate.
C. Installer Qualifications: Engage an experienced installer who has successfully completed tile
installations similar in material, design, quality of workmanship and extent to that indicated for
Project.
D. Field-Constructed Mock-up: Before installing tile, erect mock-ups for each tile design to
demonstrate aesthetic effects as well as qualities of materials and execution. Build mock-ups to
comply with the following requirements, using materials indicated for final unit of work.
A. Deliver and store packaged materials in original containers with seals unbroken and labels intact
until time of use.
B. Prevent damage or contamination to materials by water, foreign matter, and other causes.
C. Handle tile with temporary protective coating on exposed surfaces to prevent coated surfaces from
contacting backs or edges of other units.If despite these precautions coating does contact bonding
surfaces of tile, remove coating from bonding surfaces before setting tile.
A. Maintain environmental conditions and protect work during and after installation to comply with
referenced standards and manufacturer's printed recommendations.
B. Provide adequate mechanical ventilation for areas to be installed with tiles, particularly rooms
without windows.
A. Deliver extra materials to Owner. Furnish extra materials that match products installed as
described below, packaged with protective covering for storage and identified with labels clearly
describing contents. Furnish quantity of full-size units equal to 2 percent of amount installed, for
each type, composition, color, pattern, and size.
PART 2 Products
2.01 MANUFACTURERS
A. Available Manufacturers:
Homogenous Tile:
1. GranitiFiandre.
2. Caesar Ceramiche.
3. Granitogres.
4. Other equivalent manufacturers approved by the Architect.
A. The required product is Homogenous (Porcelain) Tile, with the same material composition
throughout its thickness.
B. Colors, Textures, and Patterns: Where manufacturer's standard products are indicated for tile,
grout, and other products requiring selection of colors, surface, textures, patterns, and other
appearance characteristics, provide specific products or materials complying with the following
requirements. Provide selections made by the Architect from manufacturer's full range of standard
colors, textures, and patterns for products of type indicated.
Nominal Facial Dimensions (As per Schedule of Finishes): HT-1 and HT-1a.
Tile Face Texture: As indicated above.
Color: As selected by the Architect.
WTA Architecture And Design Studio Page 56 of 68
TECHNICAL SPECIFICATIONS
Edge: Square.
Thickness: 10mm thick minimum.
Manufactured in accordance with ANSI A-137.1 and other recognized international standards
(DIN, BS, EN).
2.04 MATERIALS
A. Portland Cement Mortar Installation materials: Provide materials complying with ANSI A108.1 and
as specified below:
B. Divider Strip: Satin stainless steel 6mm wide x 25mm deep, for embedment to floor and flush to
floor finish. AISI Type 304.
2.05 GROUT
A. Mix mortars and grouts to comply with requirements of referenced standards and manufacturers
including those for accurate proportioning of materials, water, or additive content; type of mixing
equipment, selection of mixer speeds, mixing containers, mixing time, and other procedures needed
to produce mortars and grouts of uniform quality with optimum performance characteristics for
application indicated.
PART 3 Execution
3.01 EXAMINATION
A. Examine substrates and areas where tile will be installed, with Installer present, for compliance
with requirements for installation tolerances and other conditions affecting performance of installed
tile.
1. Verify that substrates for setting tile are firm, dry, clean, and free from oil or waxy films
and curing compounds.
2. Verify that installation of grounds, anchors, recessed frames, electrical and mechanical
units of works, and similar items located in or behind tile has been completed before installing
tile.
B. Do not proceed with installation until unsatisfactory conditions have been corrected.
A. ANSI Tile Installation Standard: Comply with parts of ANSI 108 series of tile installation standards
included under "American National Standard Specifications for the Installation of Ceramic Tile" that
apply to type of setting and grouting materials and methods indicated.
B. Extend tile work into recesses and under or behind equipment and fixtures to form a complete
covering without interruptions except as otherwise show. Terminate work neatly at obstructions,
edges, and corners without disrupting pattern or joint alignments.
C. Accurately form intersections and returns. Perform cutting and drilling of tile without marring
visible surfaces. Carefully grind cut edges of tile abutting trim, finish or built-in items for straight
aligned joints. Fit tile closely to electrical outlets, piping, fixtures, and other penetrations so that
plates, collars or covers overlap tile.
D. Jointing Pattern: Unless otherwise shown, lay tile in grid pattern. Align joints when adjoining tiles
on floor, base, walls, and trim are same size. Layout tile work and center tile fields in both directions
in each space or on each wall area. Adjust to minimize tile cutting. Provide uniform joint widths unless
otherwise shown.
E. Expansion Joints: Locate expansion joints and other sealants-filled joints, including control
contraction, and isolation joints, where indicated during installation of setting materials, mortar beds,
and tile. Do not saw cut joints after installation of tiles.
F. Grout tile to comply with the requirements of the following installation standards: Dry-set, Non-
Sanded Grout: ANSI A 108.6.
A. Homogenous Tile: Install tile to comply with requirements indicated below for setting-bed
method:
A. Install tile to comply with requirements indicated below for setting-bed method:
A. Cleaning: Upon completion of placement and grouting, clean all ceramic tile surfaces so they are
free of foreign matter.
1. Remove grout residue from tile as soon as possible, in methods recommended by the
grout manufacturer.
2. Unglazed tile may be cleaned with acid solutions only when permitted by tile and grout
manufacturer's printed instructions, but no sooner than 14 days after installation. Protect metal
surfaces, cast iron, and vitreous plumbing fixtures from effects of acid cleaning. Flush surface
with clean water before and after cleaning. Protect plumbing system.
B. Finished Tile Work: Leave finished installation clean and free of cracked, chipped, broken,
unbounded and otherwise defective tile work.
C. Provide final protection and maintain conditions in a manner acceptable to manufacturer and
installer that ensures that tile is without damage or deterioration at time of Substantial Completion.
Prohibit foot and wheel traffic from tile floors for at least 7 days after grouting is completed.
D. Before final inspection, remove protective coverings and rinse neutral cleaner from tile surfaces.
Part 1 Products
1.01 PAINTING SCHEDULE: All color samples shall be submitted for approval.
1. Plain or textured finish (semi-gloss latex type). Masonry neutralizer or approve equal.
1st coat: Concrete Sealer
Latex
Patching compound
2nd coat: Semi-gloss compound
3rd coat: Same as 2nd coat
1. Plain Painted surfaces (Walls & Partitions): Semi-gloss finish (alkyd type).
1st coat: Interior primer and sealer
2nd coat: Semi-gloss finish
3rd coat: Same as 2nd coat
C. Metal surfaces:
1. Epoxy Paint Gloss Finish for G.I. pipes, grille, structural steel, etc.
1st coat: quick dry red lead primer
2nd coat: epoxy paint
3rd coat: same as 2nd coat
PART 1 General
1.02 SUMMARY
A. Provide epoxy flooring and epoxy painting system for the following areas:
1. Electrical Rooms
2. Mechanical Equipment Rooms
3. Pump rooms
4. Transformer Room
5. Fire Exit Stairs
6. Switch Gear Room
7. Genset Room
8. Garbage Rooms
1.03 SUBMITTALS
A. Product Data: Submit manufacturer's technical data, installation instructions, and general
recommendations for each resinous flooring material required. Include certification indicating
compliance of materials with requirements.
B. Provide samples of each color and material to be applied, with texture to simulate actual
conditions, on representative samples of the actual substrate.
1. Concrete/plastered surfaces: Provide two 200mm square samples for each type of color and
finish; define prime and finish coats.
A. Single Source Responsibility: Obtain primary epoxy coating materials including primers, resins,
hardening agents, finish or sealing coats from a single manufacturer with not less than 3 years of
successful experience in supplying principal materials for work of type described in this section.
WTA Architecture And Design Studio Page 60 of 68
TECHNICAL SPECIFICATIONS
Provide secondary materials only of type and from source recommended by manufacturer of primary
materials.
B. Installer Qualifications: Engage an Installer who has successfully completed within the last three
years at least three resinous flooring applications similar in type and size to that of this project and
who will assign mechanics from these earlier applications to this project, of which one will serve as
lead mechanic.
A. Deliver materials to the jobsite in the manufacturer's original, new, unopened packages and
containers bearing manufacturer's name and label and the following information:
B. Store materials to comply with manufacturer's directions to prevent deterioration from moisture,
heat, cold, direct sunlight or other causes.
PART 2 Products
2.01 MANUFACTURERS
A. Acceptable Manufacturers:
1. Sika.
2. Fosroc.
3. Jotun.
4. Other approved equivalent by the Architect.
2.02 PRODUCTS
PART 3 Execution
B. Concrete Surfaces: Comply with ASTM C 811 unless otherwise required by manufacturer's
instructions.
A. Carefully mix and prepare materials to be used in compliance with manufacturer's instructions.
3.03 APPLICATION
A. General: Apply each component of epoxy system in compliance with manufacturer's directions to
produce a uniform monolithic surface of thickness required as per the product's application
requirement.
B. Prime Coat: Apply primer over prepared substrate at manufacturer's recommended spreading
rate. Coordinate timing of primer application with application of topping mix to insure optimum
adhesion between coating materials and substrate.
D. Finish or Sealing Coat: After topping mix has cured sufficiently, apply finish or sealing coat of
type required by the manufacturer to produce required finish indicated and in number of coats and
spreading rates recommended by manufacturer.
E. Cove Base for areas with epoxy wall bases: Apply epoxy system to wall surfaces at locations
indicated to form base with cove or radius shown unless otherwise indicated. Round nterior corners.
A. Cure Epoxy Coating materials in compliance with manufacturer's directions, taking care to prevent
contamination during stages of application and prior to completion of curing process.
B. Protect Epoxy Coating materials from damage and wear during construction operation. Where
temporary covering is required for this purpose comply with manufacturer's recommendations for
protective materials and method of application. Remove temporary covering and clean epoxy coating
just prior to final inspections. Use cleaning materials and procedures recommended by epoxy coating
manufacturer.
PART 1 General
1.01 SUMMARY
A. This section includes food-quality epoxy coating system for domestic potable concrete water tank,
on top of capillary type waterproofing, for walls, floors, and ceiling.
1.02 SUBMITTALS
A. Submit manufacturer's complete technical product data including basic materials analysis and
application instructions for each coating material specified.
B. 100mm square samples of each color and material to be applied, with texture to simulate actual
conditions, on representative samples of the actual substrate. Resubmit samples as requested by
Architect until the required sheen, color and texture is achieved. Define prime and finish coats by
using different colors or tints.
C. Certification from Food and Drug Administration that product is acceptable for use as potable
water container lining.
A. Obtain primary chemical-resistant epoxy coating materials including primers, resins, hardening
agents, finish or sealing coats from a single manufacturer with not less than 3 years of successful
experience in supplying principal materials for work of type described in this section. Provide
secondary materials only of type and from source recommended by manufacturer of primary
materials.
B. Coordination of Work: Review sections in which other coatings are provided to ensure
compatibility of the total systems for various substrates. Upon request, furnish information on
characteristics of specified finish materials, to ensure that compatible prime coats are used.
C. Provide the best quality grade of the various coatings as regularly manufactured by
acceptable coating manufacturers. Materials not displaying manufacturer's identification as a
best-grade product will not be acceptable.
A. Deliver materials to the job-site in the manufacturer's original, new, unopened packages and
containers bearing manufacturer's name and label and the following information:
PART 2 Products
2.01 The physical property requirements of the Trowel-Applied Epoxy Coating System for interior
application (floor, walls and ceiling) of the Concrete Water Tanks are based on a specific product
indicated. Other products by other manufacturers having equal performance characteristics may
be considered provided deviations are minor and do not change the intended performance as
judged by the Architect.
WTA Architecture And Design Studio Page 63 of 68
TECHNICAL SPECIFICATIONS
A. Acceptable Products:
1. "DEVRAN 207 Potable Water Tank Lining"; Devoe Coatings.
2. Other approved equivalent by the Architect.
PART 3 Execution
A. Perform preparation and cleaning procedures in compliance with manufacturer's instructions for
particular substrate conditions involved, and as herein specified.
B. Concrete Surfaces: Comply with ASTM C 811 unless otherwise required by manufacturer's
instructions.
A. Carefully mix and prepare materials to be used in compliance with manufacturer's instructions.
3.03 APPLICATION
A. Apply each component of epoxy system in compliance with manufacturer's directions to produce a
uniform monolithic surface of thickness required as per the product's application requirement.
B. Apply primer over prepared substrate at manufacturer's recommended spreading rate. Coordinate
timing of primer application with application of topping mix to insure optimum adhesion
between chemical-resistant epoxy coating materials and substrate.
D. Finish or Sealing Coat: After topping mix has cured sufficiently, apply finish or sealing coat of
type required by the manufacturer to produce required finish indicated and in number of coats and
spreading rates recommended by manufacturer.
A. The Owner reserves the right to invoke the following material testing procedure at any time, and
any number of times during period of epoxy application.
1. The Owner will engage service of an independent testing laboratory to sample materials being
used. Samples of material will be taken, identified and sealed, and certified in the presence of
Contractor.
2. Testing laboratory will perform tests for any of characteristics specified, using applicable
testing procedures referenced herein, or if not referenced, in manufacturer's product data.
B. If test results show materials being used do not comply with specified requirements, Contractor
may be directed by Owner to stop work; remove non-complying materials; pay for testing; reapply
epoxy coating materials to properly prepared surfaces which had previously been coated with
unacceptable materials.
A. Cure Epoxy Coating materials in compliance with manufacturer's directions, taking care to
prevent contamination during stages of application and prior to completion of curing process.
B. Protect Epoxy Coating materials from damage and wear during construction operation. For this
purpose comply with manufacturer's recommendations for protective materials and method of
application. Remove temporary covering and clean epoxy coating just prior to final inspections. Use
cleaning materials and procedures recommended by epoxy coating manufacturer.
Part1 SCOPE
Drawings and general provisions of the contract, including General and Supplementary Conditions
and Division 1 Specification Sections, apply to this section.
1.02 SUMMARY.
1.03 SUBMITTALS.
A. General: Submit each item in this Article according to the Conditions of the Contract and Division 1
Specifications Sections.
B. Product Data for each type of ACCESORY, including details of installation, dimensions of individual
components, profiles, textures, and colors as well as sealant intended for use in this project before
procurement..
C. Shop Drawings showing locations of each item, dimensioned plans and elevations, large scale
details, attachment devices, and other components.
Delivery of materials shall be so scheduled as to allow for immediate installation. Products shall be
protected and kept under cover both during transit and at the jobsite. Handle products carefully to
prevent damage.
Check dimensions by field measurement before fabrication to ensure proper fitting of work. Show
measurements on final shop drawings. Coordinate fabrication schedule with construction progress to
avoid delay in work.
1.06 WARRANTY.
Submit a written warranty, executed by the Contractor, Installer and Manufacturer, agreeing to repair
or replace units which fail in materials or workmanship within the specified warranty period.
Drawings indicate sizes, profiles and dimensional work. Minor deviations will be accepted in order to
utilize manufacturer’s standard products when, in the Architect’s sole judgment, such deviations do
not materially detract from the design concept or indicated performances.
1.08 PRODUCTS.
1.09 MODELS.
Models specified shall be as specified herein and shall be provided with color as indicated or as
approved. Contractor shall install all indicated toilet accessories including all required fittings to be
supplied by others or the Owner itself.
Part 3 INSTALLATION.
Toilet accessories shall be installed on locations as shown. Surfaces of fastening devices exposed after
installation shall have the same finish as the attached accessory. Exposed screw head shall be oval.
Installed heights shall be as shown on the drawings. Upon completion of the installation, accessories
shall be protected with strippable plastics or by other approved means until the installation are
accepted. The manufacturer’s accessory mounting details shall be coordinated with other trades as
their work progresses.
Toilet accessories shall be in accordance with “HCG” by HOCHENG Philippines catalog or brochures.
WTA Architecture And Design Studio Page 66 of 68
TECHNICAL SPECIFICATIONS
10101: Included Works. The work scope in this section includes all toilet partitions, cubicle doors,
and stainless steel accessories and fittings. Although all toilet partitions shall be Owner
supplied, coordination work with the Owner’s specialty contractor shall be part of the
responsibility of the Contractor.
.
10102: Materials. All materials to be used under this section shall conform to manufacturer’s
specifications and/or acceptable construction standards. Technical shop drawings and
material samples shall be submitted by the specialty contractor to the Architect for
approval prior to implementation on site. All materials not specifically described but
required for a complete and proper installation of all toilet partitions shall be provided and
installed by the specialty contractor.
10103: Workmanship. Work under this section may be implemented only by the properly skilled
tradesman under the direct supervision of a technical superintendent. Proper site
preparations and actual measurements must be done on site prior to fabrication and
installation of toilet partitions.
A. Included Works. The work scope in this section includes all lighting fixtures and
wiring devices as indicated on the Electrical Plans. Although supply and installation
of all lighting fixtures and wiring devices are Owner supplied, coordination work
with the Owner’s specialty contractor shall be part of the responsibility of the
Contractor.
.
B. Materials. All materials to be used under this section shall conform to
manufacturer’s specifications and/or acceptable construction standards. Technical
shop drawings, brochures and material samples shall be submitted by the specialty
contractor to the Architect for approval prior to implementation on site. All
materials not specifically described but required for a complete and proper
installation of all lighting fixtures and wiring devices shall be provided and installed
by the specialty contractor.
C. Workmanship. Work under this section may be implemented only by the properly
skilled tradesman under the direct supervision of a technical superintendent. Proper
site preparations and actual measurements must be done on site prior to
fabrication and installation of all lighting fixtures and wiring devices. Should any
perforations on existing surfaces be required, particularly for recessed and
embedded lighting fixtures and wiring, the specialty contractor shall implement the
required perforations. The Contractor shall ensure that said adjustments are
properly and correctly restored.
D. The Contractor shall also coordinate with the specialty contractor as to locations of
lighting fixtures that may need additional frames, hangers or supports that are
within ceiling or wall enclosures; and, shall provide the necessary additional items
without any cost adjustments.
END OF SECTION