Professional Documents
Culture Documents
1. Introduction
− In any electric system, the active power has to be generated at the same time as it is
consumed.
− Power generated must be maintained in constant equilibrium with power consumed /
demanded, otherwise a power deviation occurs.
− Disturbances in this balance, causing a deviation of the system frequency from its set‐
point values, will be offset initially by the kinetic energy of the rotating generating sets
and motors connected.
− The electric frequency in the network (the system frequency) is a measure for the
rotation speed of the synchronised generators
− By increase in the total demand the system frequency (speed of generators) will decrease,
and by decrease in the demand the system frequency will increase, i.e.
If system generation < system demand ⇒ frequency falls
If system generation > system demand ⇒ frequency rises 1
The Hong Kong Polytechnic University Control of Frequency & Power
‐ Regulating units will then perform automatic primary control action in order to re‐establish
the balance between demand and generation
− Primary control allows a balance to be re‐established at a system frequency other than the
frequency set‐point value (at a quasi‐steady‐state frequency deviation Δf)
− The function of secondary control (also known as load‐frequency control) to restore the
system frequency f to its set‐point value of 50 (or 60) Hz (in addition to scheduled power
interchanges with adjacent control areas) thus ensuring that the full reserve of primary
control power activated will be made available again.
− Tertiary control is any automatic or manual change in the working points of generators or
loads participating, in order to:
• guarantee the provision of an adequate secondary control reserve at the right time
• distribute the secondary control power to the various generators in the best possible way, in
terms of economic considerations
‐ Time deviation is the time integral of the frequency deviation. In practice, an electrical clock
(synchronous time) is compared with the astronomical time (UTC)
‐ Time control is a control action carried out to return an existing time deviation between
synchronous time and UTC time to zero 2
1
The Hong Kong Polytechnic University Control of Frequency & Power
seconds
minutes
minutes/hours
days
Control scheme and actions in frequency control
3
The Hong Kong Polytechnic University Control of Frequency & Power
Overview of AGC logic
4
2
The Hong Kong Polytechnic University Control of Frequency & Power
Frequency Restoration under AGC
5
The Hong Kong Polytechnic University Control of Frequency & Power
3
The Hong Kong Polytechnic University Control of Frequency & Power
The Hong Kong Polytechnic University Control of Frequency & Power
2. Fundamentals of Speed Governing
4
The Hong Kong Polytechnic University Control of Frequency & Power
The Hong Kong Polytechnic University Control of Frequency & Power
3. Load Response to Frequency Deviation
10
5
The Hong Kong Polytechnic University Control of Frequency & Power
11
The Hong Kong Polytechnic University Control of Frequency & Power
12
6
The Hong Kong Polytechnic University Control of Frequency & Power
4. Isochronous Governor
13
The Hong Kong Polytechnic University Control of Frequency & Power
14
7
The Hong Kong Polytechnic University Control of Frequency & Power
5. Governors with Speed‐Droop Characteristics
15
The Hong Kong Polytechnic University Control of Frequency & Power
16
8
The Hong Kong Polytechnic University Control of Frequency & Power
17
The Hong Kong Polytechnic University Control of Frequency & Power
6. Load Sharing by Parallel Units
18
9
The Hong Kong Polytechnic University Control of Frequency & Power
19
The Hong Kong Polytechnic University Control of Frequency & Power
7. Composite Regulated Power Systems
20
10
The Hong Kong Polytechnic University Control of Frequency & Power
21
The Hong Kong Polytechnic University Control of Frequency & Power
22
11
The Hong Kong Polytechnic University Control of Frequency & Power
Example
Installed Capacity Percent Speed Total Generation Primary (Spinning)
Droop (R%) Reserve
PP‐1 5x100 MW 4% 4x75 MW 100 MW
PP‐2 8x60 MW 4% 5x50 MW 50 MW
PP‐3 3x300 MW 5% 3x250 MW 150 MW
TOTAL 1880 MW ‐ 1300 MW 300 MW
Load varies 1.5% for every 1% change in frequency
1 4 100
200 MW Hz
Find speed‐changer setting for each unit R1 4 100 50
Hz 1 5 60
150 MW Hz
fi R2 4 100 50
1 3 300
50 360 MW Hz
R3 5 100 50
P1 300MW f1 51.500 Hz
MW P2 250MW f 2 51.667 Hz
0 Pi Pimax P3 750MW f 3 52.083 Hz
23
The Hong Kong Polytechnic University Control of Frequency & Power
D
1.5 100 1200 36 MW Hz
1 100 50
1
D 746 MW Hz PL
f ss 0.134 Hz
Req
24
12
The Hong Kong Polytechnic University Control of Frequency & Power
D
1.5 100 1300 39 MW Hz PL 1300 MW
1 100 50
1 PG
D 699 MW Hz f ss 0.1073 Hz
Req
25
The Hong Kong Polytechnic University Control of Frequency & Power
D
1.5 100 1300 39 MW Hz PL 1300 MW
1 100 50
1 P
D 629 MW Hz f ss G 0.3975 Hz
Req
13
The Hong Kong Polytechnic University Control of Frequency & Power
8. Response rates of turbine governing systems
Block diagram of a generating unit with a reheat steam turbine
Block diagram of hydraulic unit 27
The Hong Kong Polytechnic University Control of Frequency & Power
Special characteristics of hydraulic turbine
For a step change in gate opening, the initial value theorem
gives
1 1 Tw s
P m (0) lim s s 2
s 1 0.5 Tw s
the final value theorem gives
1 1 Tw s
P m () lim s 0 s 1
s 1 0.5 Tw s
the complete time response is given by
2 Tw t
P m (t ) 1 3e G Change in turbine mechanical power
following a unit step change in gate position
28
14
The Hong Kong Polytechnic University Control of Frequency & Power
Hydraulic turbine response to a step change and a ramp change in gate position (gate opening reduced
0.1 pu), with initial values of head, power, velocity, and gate position equal to 1 pu (Tw = 1.0s)
29
The Hong Kong Polytechnic University Control of Frequency & Power
* Hydro turbines have a peculiar response due to water inertia: a change in gate position produces an
initial turbine power which is opposite to that sought. For stable control performance, a large transient
(temporary) droop with long resetting time is required.
30
15
The Hong Kong Polytechnic University Control of Frequency & Power
Steam Turbines
Single reheat tandem‐compound steam
turbine model
Ignore TCO (TCO<<TRH) for simplified
transfer function
The Hong Kong Polytechnic University Control of Frequency & Power
Response of units to a small step increase in load demand
(values are shown in per unit of the step change)
32
16
The Hong Kong Polytechnic University Control of Frequency & Power
Consider the previous example
System dynamic data
PP‐1 (Hydraulic Units)
R p 0.04; TG 0.2s; M 7.5s; TW 2.0 s; RT 0.40; TR 5.0s
Simulated Scenarios
‐ S1: 100 MW load loss
‐ S2: Loss of a unit in PP‐1 (75 MW generation loss)
‐ S3: Loss of a unit in PP‐3 (250 MW generation loss)
33
The Hong Kong Polytechnic University Control of Frequency & Power
760
PP-3 Total Power Generation (MW)
740
50.5
680
50.4
660
System Frequency (Hz)
0 20 40 60 80 100
t (s)
50.3
Total power generation in PP‐3
50.2
310
PP-1 Total Power Generation (MW)
305 50.1
300
295 50
0 20 40 60 80 100
t (s)
290
285 System Frequency
280
275
270
0 20 40 60 80 100
t (s)
Total power generation in PP‐1 34
17
The Hong Kong Polytechnic University Control of Frequency & Power
810
P P -3 Total P ow er O utput (M W )
800
790
S2 (Loss of a unit in PP‐1
780
– 75 MW generation loss)
770
50
760
49.95
240 49.7
49.65
235
49.6
0 20 40 60 80 100
t (s)
230
System Frequency
225
220
0 20 40 60 80 100
t (s)
Total power generation in PP‐1 35
The Hong Kong Polytechnic University Control of Frequency & Power
620
PP-3 Total P ower Generation (MW )
600
580
S3 (Loss of a unit in PP‐3
560 – 250 MW generation loss)
540
520
500 49.8
49.6
System Frequency (Hz)
480
0 20 40 60 80 100 49.4
t (s)
49.2
Total power generation in PP‐3 49
420 48.8
P P -1 Total P ow er G eneration (M W )
400 48.6
380 48.4
0 20 40 60 80 100
360 t (s)
340
System Frequency
320
300
280
0 20 40 60 80 100
t (s)
Total power generation in PP‐1 36
18
The Hong Kong Polytechnic University Control of Frequency & Power
37
The Hong Kong Polytechnic University Control of Frequency & Power
Overview of AGC logic (isolated system)
38
19
The Hong Kong Polytechnic University Control of Frequency & Power
Frequency Restoration under AGC (isolated system)
39
The Hong Kong Polytechnic University Control of Frequency & Power
P12 T 12
20
The Hong Kong Polytechnic University Control of Frequency & Power
Effect of change in area 1 load
41
The Hong Kong Polytechnic University Control of Frequency & Power
‐ Basic objectives:
‐ maintain frequency at scheduled value
‐ maintain interchange power with neighbouring areas at
scheduled values
‐ AGC in a given area ideally corrects only for changes in that area
‐ The control signal (Area Control Error, ACE) is made up of tie line
flow deviation added to frequency deviation weighted by a
bias factor (B).
‐ A suitable bias factor for an area is its frequency response
characteristic β.
21
The Hong Kong Polytechnic University Control of Frequency & Power
Example
‐Area 1 is operating with spinning reserve of 1000 MW
spread uniformly over 5000 MW capacity (R = 0.05)
The Hong Kong Polytechnic University Control of Frequency & Power
Area 1 has a generating capacity of 5000 MW (with 1000MW spinning reserve) on supplementary
control and this will reduce generation so as to bring ACE1 to zero.
44
22
The Hong Kong Polytechnic University Control of Frequency & Power
Example
‐Consider loss of 500 MW generation area 1 (lost unit/units are not carrying spinning reserve)
1 1 5000 1 1 10000 1 1 1
2000 MW Hz ,
R2 0.05 50
4000 MW Hz 6000 MW Hz
R1 0.05 50 R R1 R2
D1 1
20000
400 MW Hz , D2 1
40000
800 MW Hz D D1 D2 1200 MW Hz
50 50
PG 500
f 0.0694Hz
1 R D 6000 1200
Changes in loads in two areas due to increase in frequency:
1 1
PG1 f 2000 0.0694 139MW PG 2 f 4000 0.0694 278MW
R1 R2
45
The Hong Kong Polytechnic University Control of Frequency & Power
Area 1 Area 2
Load = 19972 MW Load = 39945 MW
Generation = 18639 MW Generation = 41278 MW
P21 = 1333 MW
Area 1 has a generating capacity of 5000 MW (with 1000MW spinning reserve) on supplementary
control and this will reduce generation so as to bring ACE1 to zero.
46
23
The Hong Kong Polytechnic University Control of Frequency & Power
Example
‐Consider loss of 500 MW generation area 1 (lost unit/units are carrying spinning reserve)
1 1 4500 1 1 10000 1 1 1
1800 MW Hz ,
R2 0.05
50
4000 MW Hz 5800 MW Hz
R1 0.05 50 R R1 R2
D1 1
20000
400 MW Hz , D2 1
40000
800 MW Hz D D1 D2 1200 MW Hz
50 50
PG 500
f 0.0714Hz
1 R D 5800 1200
Changes in loads in two areas due to increase in frequency:
1 1
PG1 f 1800 0.0714 129MW PG 2 f 4000 0.0714 286MW
R1 R2
47
The Hong Kong Polytechnic University Control of Frequency & Power
Area 1 Area 2
Load = 19971 MW Load = 39943 MW
Generation = 18629 MW Generation = 41286 MW
P21 = 1343 MW
Area 1 has a generating capacity of 4500 MW (with 900MW spinning reserve) on supplementary
control and this will reduce generation so as to bring ACE1 to zero.
48
24
The Hong Kong Polytechnic University Control of Frequency & Power
Example
‐Consider loss of 2000 MW generation area 1 (lost unit/units are not carrying spinning reserve)
Half of the generation will be made up by the 1000 MW spinning reserve on supplementary
control in area 1. When this limit is reached, area 1 is no longer able to control ACE.
Supplementary control signal in area2, however, is able to control its ACE.
f 0.1923Hz
49
The Hong Kong Polytechnic University Control of Frequency & Power
Area 1 Area 2
Load = 19923 MW Load = 39846 MW
Generation = 18000 MW Generation = 41769 MW
P21 = 1923 MW
50
25
THE HONG KONG POLYTECHNIC UNIVERSITY
Department of Electrical Engineering
1. An isolated 50 Hz power station has the load frequency control system as shown in Fig.1
with the following parameters.
Governor and turbine time constant, T = 1 sec
Generator inertia constant, H = 5 sec
Governor speed regulation, R = 0.04 pu
It is observed that a sudden increase of load (ǻPL) by 0.1 pu has brought about steady
state frequency drop (ǻZ) of 0.188 Hz.
a) Determine the load-damping constant D.
b) Determine the mechanical power change (ǻPref) needed to restore the nominal
frequency.
c) Obtain an approximated expression for the variation of frequency with time if the
effects of the governor-turbine time constant can be ignored.
d) Plot the system frequency deviation for a period of 10 seconds.
Fig.1
Fig.2
Fig.3
5. A 50Hz power system consists of three interconnected areas with the characteristics
tabular below:
Area 1 2 3
Generation Capacity (MW) 1000 2000 3000
Area frequency response characteristic (MW/Hz)
_ 350 700 950
Each area is initially generating at half of its generation capacity at 50 Hz without any
tie-line flow when the load in area 1 suddenly increases by 100MW. Neglecting losses
and the dependence of load on frequency, determine
a) the new steady-state frequency in Hz, and
b) the change tie-line flows in MW.
a) Determine the steady state operating frequency of the combined system and the
power flow of the tie-line which connected the systems together.
b) A new load is added to A in order return the system frequency of the combined
system to its nominal value. What are the size of this new load and the new tie-line
flow?
1. a) +w 0.188 Hz 0.00376 pu
§ 1 +P · § 1 0.1 ·
D ¨ L ¸ ¨ ¸ 1.6 pu
© R +w ¹ © 0.04 0.00376 ¹
b) nominal frequency => +w 0
i.e. + Pref + PL 0.1 pu
1 1
c) +w( s ) +PL ( s ) + PL ( s )
( D 2 Hs )
1 26.6 10s
R
1
sudden load increase of 0.1 pu => + PL ( s )
10s
§ 1 ·§ 1 · 1 § 1 1·
+w( s ) ¨ ¸¨ ¸ ¨ ¸
© 26.6 10s ¹ © 10s ¹ 266 © s 2.66 s ¹
1
+w(t ) >exp( 2.66t ) 1@
266
-0.05
-0.1
Full system
-0.15
Approximated
-0.2
-0.25
-0.3
10 50 10 A B
2. 'f ǻPT = 0
EA EB
f1 f1
EB 4E A
f3 f1 'f B A B
ǻPT = 10
'f B f1 f3 0.125 Hz f1-'f f1-'f
50MW
50
and 'f B EB 400
EB A B
ǻfȕ = 0.125Hz
E A 100 MW/Hz f3 50MW
f1
o P1 = 181.82 MW
o P2 = 218.18 MW
o f = 49.18 Hz
0.09
i.e. 0.003 pu (2)
EB
PT PT
'f B u 50 u 50
EB 20
PT 0.0533 pu
f 50.0333 Hz
b) Let PL be the new load needed to restore the system frequency back to 50Hz.
PL PL P’T
'f u 50 u 50 0.0333
E A EB 40 20 A
50Hz
B
PL 0.04 pu PL
Now consider system A which returns to 50Hz from the initial 50.1Hz.
PL PT' 0.04 PT'
'f '
u 50 u 50 0.1 Hz
B
EA 40
PT' 0.04 pu