You are on page 1of 20

Supply-Air-Ceiling

for Operating Theatres


Contents List

1 | Series AL-KO Supply-Air-Ceilings 3


1.1 | System description 3
1.2 | General explanation 4
1.3 | Central and decentralized systems 5
1.4 | Design criteria for AL-KO Supply-Air-Ceilings 6

2 | AL-KO Supply-Air-Ceiling Type AL-S 7


2.1 | AL-KO Supply-Air-Ceiling with vertical filters Type AL-S 7
2.2 | Technical data with sizes and dimensions 8
2.3 | Tendertext 10

3 | AL-KO Supply-Air-Ceiling Type AL-H 11


3.1 | AL-KO Supply-Air-Ceiling with horizontal filters Type AL-H 11
3.2 | Technical data with sizes and dimensions 12
3.3 | Tendertext 13

4 | AL-KO Supply-Air-Ceiling Type AL-PA 14


4.1 | AL-KO Supply-Air-Ceiling for Pathology and Anatomy Type AL-PA 14
4.2 | Tendertext 14

5 | Air Guiding Curtains 15

6 | Media Supply Elements 15

7 | Slubseparator 16

8 | Lighting system 17

9 | Air Handling Units for hygienic applications 18


9.1 | AT4 AHU for Hygienic Application 18
9.2 | AL-KO solutions 19
1 | Series
AL-KO Supply-Air-Ceilings

1.1 System description

State-of-the-art – solutions
• Low germ number in the opera- Results of the inquiry concerning the degree of contamination
ting of a Supply-Air-Ceiling-System with Size 1,8 m x 2,4 m:
area and in the supply air flow
• Low germ sedimentation Degree of contamination (µs) / Air velocity (m/s)
• Low air speeds in the working 0,4
area
• Low harmful gas concentration µs
also in the anaesthetics work
area 0,3
• Good screening of the operating
area in case of disturbances µs
by opening doors
• Minimum requirements accor- 0,2
ding
to DIN 1946/4 are exceeded by 0,15 m/s 0,20 m/s 0,25 m/s 0,30 m/s
far
• Examination according to DIN • degree of contamination
4799 degree of contamination (exponential)
by the Hermann Rietschel
Institute Prof. Dr.-Ing. K. Fitzner – University of Technology Berlin
of the TU Berlin H. Rietschel – Institute of heating engineering and air-conditioning technology
• Contamination-proof sealing
3
1 | Series
AL-KO Supply-Air-Ceilings

1.2 General Explanation for Series AL-KO Supply-Air-Ceilings

The AL-KO Supply-Air-Ceiling for examination and measuring con-


ope-ration theatres Type AL is a necting pieces are well acces-
supply air system with constant sible, easy to assemble and ex-
laminar flow change without special tools. The
for all types of operating theatre. maintenance work can be
It is characterised by particularly accomplished
low germ numbers in the opera- within the AL-KO Supply-Air-
tion field and Ceiling without intervention into
low harmful gas concentrations the room
in the working area of the opera- ceiling. Easy connection to the
tion team duct system by duct flanges.
with a high thermal comfort. The Manually adjustable or dampers
AL-KO Supply-Air-Ceiling fulfils with actuators are available as an
requirements necessary for option.
clean-room technology. The low, Supply air box and ceiling hou-
predominantly laminar air veloci- sing are made of galvanised steel
ty at the patient’s location must with disinfectantresistant coating
be emphasised from the medical or of stainless steel, material No.
point of view. The cooling down 1.4301. The AL-KO Supply-Air-
of the Ceiling, type AL, also fulfils the
patient is less than with turbulent requirement of low germ num-
flow systems. The ceiling bers in the operation area in spite
system is disinfectantresistant of high thermal loads. The conta-
and consists of a large output mination degree of less than 0.1
field, equipped with is substantially lower than the
patented laminarisators. These minimum requirement
consist of aluminium frames of JJLS = 0.67 according to DIN
covered with 1946/4 for operating theatres of
flow-optimised special profiles the type A, highly aseptic. The
with minimised frame width, examination according to DIN
covered with 4799 was accomplished
a tear-proof, monofilament poly- by the Hermann Rietschel lnstitu-
ester tissue. te for Heating and Air Condition
Technology of the Technical
The laminarising effect practically University of Berlin. The outstan-
excludes a secondary air conta- ding temporal particle reduction
mination. characteristic of the laminar flow
The support leadthrough is aero- system protects the patient
dynamically designed, so that no against air germs much better
wake areas or flow deflections than operating theatre supply air
occur. Installation tolerances of systems with turbulent mixed
the ceiling and support can be flows. Only the operating
compensated at the same time. theatre supply air ceiling with
The HEPA-filter units in stable laminar displacement flow offers
mounting frames with clamping protection, since the so-called
device, test groove for the seal fit protection retention cannot pre-

4
1.3 Central and decentralized systems

Centralized Air Handling


Unit
within the technical room
for total supply of the OP-
theatre

Decentralized system
with outside air intake
AHU, exhaust AHU
and circulation AHU
(as various options
are possible, only one
schematic drawing
is shown)

5
1 | Series
AL-KO Supply-Air-Ceilings

1.4 Design criteria for AL-KO Supply-Air-Ceilings

Type AL-S
with vertical filters

Type AL-H
with horizontal filters

Type AL-PA
for pathology

6
2 | AL-KO Supply-Air-Ceiling
Typ AL-S

2.1 AL-KO Supply-Air-Ceiling with vertical filters Typ AL-S

Smooth internal surfaces without cor- Lamp shaft with maintenance plate
ners for better sevice

Easy and safe maintenance of filters Operation Lamp for installation through
including OP-Ceiling
test procedure for tightness

7
2 | AL-KO Supply-Air-Ceiling
Typ AL-S

2.2 Technical Data with sizes and dimensions Type AL-S

Height H = 400 mm
Item no. Length Width Air volume Type Scheme Pressure loss Weight Duct connection
L B 0,20 m/s0,25 m/s 0,20 0,25 Kg St. a b
mm mm m /h
3
m /h
3
Pa Pa mm mm

1 2.400 1.200 2.074 2.592 24124 186 233 170 2 873 263

2 2.400 1.400 2.419 3.024 24144 215 269 190 2 873 263

3 2.400 1.800 3.110 3.888 24184 212 265 235 4 568 263

4 2.400 1.800 3.888 4.860 30184 210 262 270 4 720 263

2 720 263
5 2.400 2.400 4.147 5.184 24244 202 253 295
2 873 263
4 568 263
6 3.000 2.400 5.184 6.480 30244 201 251 320
2 873 263

8
Options:
Casing made out of galvanized
steel with painting (resistant
against disinfection) or stainless
steel 1.4301

Filter frame made out of reinfor-


ced fiber material or galvanized
steel

Duct connecti-
ons with or wit-

Height H = 300 mm
Item no. Length Width Air volume Type Scheme Pressure loss Weight Duct connection
L B 0,20 m/s0,25 m/s 0,20 0,25 Kg St. a b
mm mm m /h
3
m /h
3
Pa Pa mm mm

1 2.400 1.200 2.074 2.592 24123 182 227 175 4 720 161

2 2.400 1.400 2.419 3.024 24143 210 262 195 4 720 161

4 568 161
3 2.400 1.800 3.110 3.888 24183 210 262 240
2 720 161
4 720 161
4 2.400 1.800 3.888 4.860 30183 210 263 280
2 873 161
2 720 161
5 2.400 2.400 4.147 5.184 24243 210 263 305
4 873 161
4 720 161
6 3.000 2.400 5.184 6.480 30243 204 255 330
4 873 161

9
2 | AL-KO Supply-Air-Ceiling
Typ AL-S

2.3 Tendertext Type AL-S

Supply air ceiling consisting of: sec-


for operating theatres ondary air contamination, consi-
sting
Particularly suitable for genera-
ting a laminar clean air flow,
Ceiling housing of aluminium frames with minimi-
sed
while avoiding as a pressure box according to
frame width, without lee areas
secondary air contamination, for the over-pressure principle to
between the ceiling panels, with
the creation of a sterile operating prevent leak
a monofilament polyester tissue
area, air flows, housing ready for
covering, flame and disinfectant-
complying with the test report assembly, suitable for transporta-
resistant, colour white, simple
according to DIN 4799, for cei- tion through
disassembly of the air distribution
ling-flush normal doors
frame without tools
installation, in a flat design,
Material ceiling housing and
= optional, please select
filter frame:
galvanised steel sheet with Support leadthrough
disinfectantresistant coating
Aerodynamically designed to
stainless steel, material No. avoid
1.4301 airflow disturbances to a large
extent
and thus contamination, built in
HEPA-filter dead centre into the air outlet,
with tolerance compensation for
According to DIN EN 1822, class
the support position
H13 with both-way handle pro-
tection, on stable mounting
frame with clamping device and
test groove for the filter
Accessories
seal fit examination, complete Duct connecting piece made
with pressure measuring connec- of galvanised steel sheet
ting piece, Frame material:
Galvanised airtight damper
medium densified fibre board according to DIN 1946-4,
manually operated
Aluminium
Airtight damper with electrical
servo motor with spring return
Laminarisators Airtight damper with pneuma-
According to the European tic servo motor
patent
Pressure monitoring with
0 355 517 B1, as large-area cei-
remote display
ling
panels, whose good laminari- Spare filters
sing
Basic lighting
characteristics almost exclude a

Performance and dimensi-


ons
Please refer to page 8 and 9.

Supply air volume flow


10 m3/h
Exit speed
3 | AL-KO Supply-Air-Ceiling
Type AL-H

3.1 Supply-Air-Ceiling with horizontal filters Type AL-H

Typical design of AL-H with air guiding


curtains and media supply

Layout of OP-ceiling with and without


laminarisator

11
3 | AL-KO Supply-Air-Ceiling
Type AL-H

3.2 Technical data with sizes and dimensions Type AL-H

Pressure loss Scheme 1 Scheme 2+3


Item LengthWidth Type Air Lamp
Weight

0,20 0,25
L B m/s m/s c d H h b H h b H h b
mm mm m /h m /h mm
3 3
mm mm mm mm mm mm mm mm mm mm Kg

1 2660 2660 2626 5.095 6.370 618 508 415 175 800 520 340 800 415 504 710 315

2 2810 2810 2828 5.685 7.110 768 658 415 175 900 520 340 900 415 504 800 360

3 2960 2960 2929 6.720 8.400 618 508 415 175 1000 520 340 1000 415 669 710 400

4 3055 3055 3030 6.310 7.885 660 660 415 175 1120 520 340 1120 415 669 800 440

5 3265 3265 3232 7.675 9.595 636 564 415 175 1250 520 340 1250 415 834 710 520

12
3.3 Tendertext Type AL-H

Supply air ceiling consisting of: frame width, without lee areas
for operating theatres between the ceiling panels, with
a monofilament polyester tissue
Particularly suitable for genera-
ting a laminar clean air flow,
Ceiling housing covering, flame and disinfectant-
resistant, colour white, simple
while avoiding as a pressure box according to
disassembly of the air distribution
secondary air contamination, for the over-pressure principle to
frame without tools
the creation of a sterile operating prevent leak
area, air flows, housing ready for = optional, please select
complying with the test report assembly, suitable for transporta-
according to DIN 4799, for cei- tion through
ling-flush normal doors Support leadthrough
installation, in a flat design,
Material ceiling housing and Aerodynamically designed to
filter frame: avoid
airflow disturbances to a large
galvanised steel sheet with
extent
disinfectantresistant coating
and thus contamination, built in
stainless steel, material No. dead centre into the air outlet,
1.4301 with tolerance compensation for
the support position

HEPA-filter
According to DIN EN 1822, class
Accessories
H13 with both-way handle pro- Duct connecting piece made
tection, on stable mounting of galvanised steel sheet
frame with clamping device and
Galvanised airtight damper
test groove for the filter
according to DIN 1946-4,
seal fit examination, complete
manually operated
with pressure measuring connec-
ting piece, Frame material: Airtight damper with electrical
servo motor with spring return
medium densified fibre board
Airtight damper with pneuma-
Aluminium
tic servo motor
Pressure monitoring with
Laminarisators remote display
According to the European Spare filters
patent
Basic lighting
0 355 517 B1, as large-area cei-
ling
panels, whose good laminari-
sing
Performance and dimensi-
characteristics almost exclude a
ons
sec- Please refer to page 12.
ondary air contamination, consi-
sting Supply air volume flow
of aluminium frames with minimi- m3/h
sed Exit speed
m/s

13
4 | AL-KO Supply-Air-Ceiling
Type AL-PA

4.1 AL-KO Supply-Air-Ceiling for Pathology and Anatomy Type

300
800
Nhìn töø döôùi Nhìn töø treân

300
300 300

400
1800

4.2 Tendertext AL-PA

Description fitting
The Supply-Air-Ceiling Type AL-
of lighting devices can be done Construction
very easily.
PA ensure a continuous laminar • Air supply chamber made of
flow for the total area according galvanised steel with optimum
to DIN1946-4
Technical data disinfection
(March 1999). This warranties • Air supply volume 1040 surface and for concealed
optimum working conditions as m3/h installation
f.e. protection against infection • Air velocity 0,2 • Duct connection to the side
and a better thermal comfort. m/s or to the top
The particles and the amount of • Pressure loss 25 • Diffusor for air intake on top
gas will be reduced. Pa • Patented laminarisator accor-
Also the required values for • Value of contamination accor- ding to European patent
MAK- ding to: DIN 1946-4 0.355.517 made of
guidelines are ensured. The > 0,1 polyester fixed on aluminium
installation of the ceiling and the Temperature difference R- profiles
tZU <=3K • both sides of the chamber are
equipped with lighting system
with glas cover and wired to a
terminal box
14
5 | Air Guiding Curtains
6 | Media Supply Elements

5. Air Guiding Curtains

Air curtains are stabilizing the


laminar
flow, minimizing the entry of
germs
and enlarging the entire zone.
Curtains
are most efficient if the air supply
field
is close to the curtain and the
length
of the curtain is done accordingly. Air curtain with 8 mm safety glass,
fixed at the Media Supply Elements
Air curtains are mechanically gaps are sealed
strong,

Air curtain 8 mm safety glass for sus- Air curtain 8 mm safety glass, for sus-
pended installation with profile, gaps pended installation, framed with alumi-
are sealed nium profiles

6. Media Supply Elements

Media supply elements are fore-


seen to provide electricity and
medical gases. They can further
include lighting systems, commu-
nication systems and can be
used for the installation of other
equipment as f.e. air curtains with
safety glass. Media elements can
be fixed on all four sides of the

15
7 | Separator for slubs

7. Separator for

Separators protecting the ducts


and
the components against sedi-
mentation and provide better
economic and service operation
of the entire air handling
system. There are various soluti-
ons for ceiling and wall installati-
on available.

Wall installation Type RAC-A Ceiling installation Type RAC-D

Lint Ball Precipator RAC:

Construction Type RAC-E Construction Type RAC-A Construction Type RAC-Z

2,5 1
A/B A/B A/B

25 25 20 25
16,5

17,5

16,5

16
8 | Lighting System

8. Lighting System

3m

2m

1m

0m

1m
2000 lx
2m
Typical installation of the lighting 1500 lx
system is done close around the 1000 lx 3m
laminar
3m 2m 1m 0m 1m 2m 3m
flow ceiling. In this case the diffe-
rence Intensity of illumination in lux
of the luminous density in the
field of operation and the room
has to be considered accordin-
gly. In the field of
operation the the luminous power
has to be at least 1000 lux at the
height
of 1 m above the surface. Better

17
9 | Air Handling Units for Hygienic Application

9.1 AT4 AHU for Hygienic Application

The VDI guideline 6022, General requirements


part 1 and 3 … of VDI 6022 for manufactur-
… defines the hygienic require- ers of AHU:
ments for AHU with regard to:
• All materials must comply with easily
• planning
health accessible and equipped with
• design
requirements and prevent lighting
• operation
microbio where necessary and sight
• service
logical growth glasses
• maintenance
• Sandwich panel construction (possible to darken)
• Low condensation tendency • Continuous and complete con-
… according to highest technical
• Smooth internal surfaces densate
standard
• Grooves easily cleanable drainage
• Bottom panel surface powder • Use of fans with access for
… represents a qualified hygienic
coated cleaning
standard providing planning
or made in stainless steel • Sealing materials must be clo-
security and avoidance of prob-
• All units and components are
lems

AL-KO AHU comply to these


requirements

We recommend a design check


(Institut für Lufthygiene)

18
9.2 AL-KO solutions

Construction (1) • The use of a direct driven fan or • avoidance of corrosive tin-plated
a panel surfaces with unprotected
• Providing enough maintenance
fan with flat belt drive requires cutting edges
space
only filter class F7 for the sup- • door and panel seals are foa-
• Consideration of excellent air
ply air med seamlessly, have a high
flow conditions for connections
density, and
and air dampers
Not approved (e.g.) are non-ageing
• The outside air dampers have to
• Filter or silencer downstream • all sections are easily accessi-
be installed internally to avoid
a humidifier ble, have the necessary
condensation
• Cooling coil without eliminator lighting, access doors, and sight
• A drain pan under outside air fil-
ter
Housing construction (2) glasses
• Possibility of cabling mainly out-
ensure better cleaning • sandwich panels
side
• All relevant components are • no condensation tendency
the casing: no additional dirty
available (category T3 / TB 3 or T2 / TB 2)
corners
either fully powder coated or in • smooth internal surfaces wit-
stainless steel hout
• Various design for all applicati- corners and edges
Filter (3)
ons • powder coated panels or inter- Filter construction:
with AL-KO software KlimaSoft nal • microbiological inert filter mate-
panels in stainless steel rials
Examples 2 2 3
• Place silencer immediately
downstream the fan, eliminator
always
behind cooler. Alternative: Fan
and cooler in the direction of air
flow

1 4 5

1 Sealing materials (4) Fans (5)


all used materials: Prevention of belt wear through:
• have been tested extensively • use of direct driven fans (plug
• prevent microbacterial growth fans)
• are resistant to disinfectants • use of flat belts for belt driven
• permit physical and chemical fans
disinfection
Casing with water drainage and

19
The AL-KO
Business Divisions

Translation Error Translation Error Translation Error


No Disk File No Disk File No Disk File

Vehicle Garden + Hobby Air Technology


Technology

With its special knowledge and skills the divisions of Vehicle


Technology,
Gardening + Hobby as well as Air Technology, the AL-KO Kober Group
intentions
are to serve society. al-
AL-KO operates with more than 40 companies und 4000 employees in

AL-KO Air Technology at a Comfort-climate

glance
Industrial applications

Chemical /
pharmaceutical industries

Hygienic applications

Recreation and leisure centres

AL-KO THERM GMBH


Marine applications
Hauptstraße 248-250
89343 Jettingen-Scheppach
Germany Refurbishments
Fon (+49) 8225/39 -176
Fax (+49) 8225/39 - 55176
E-Mail: ruediger.froehning@dc- Dust extraction
vis.net

You might also like