You are on page 1of 1

Routine test report

Job Data: Device Data


Plant name: Testname: Close nom
Plant ID: LINEA GRANADA Device Type:
Location: Device ID:
Built: Manufacturer:
Manufacturer: Built:

50,0 4,0 A /DIV

CMAIN A1
CMAIN B1
CMAIN C1

CAUX NO A1
CAUX NC A1
CAUX WI A1

S MAIN A1

I COIL A

-50.00 ms 0.00 ms 50.00 ms 100.00 ms 150.00 ms 200.00 m

Component No. Result Pole A Pole B Pole C Unit


Contacto principal 1 V CIERRE 0,00 - - m/s

Contacto principal 1 Carrera 0,00 - - mm

Contacto principal 1 SobrecaC 0,00 - - mm

Contacto principal POLO TMed CIE 68,0 69,0 68,0 ms

Contacto principal BRK DTI C 1,0 ms

Contacto principal 1 OPS CIE 1 1 1


Contacto auxiliar
1 Tiempo NO CIE n.op. - - ms
Normalmente Abierto
Contacto auxiliar
1 Tiempo NC CIE n.op. - - ms
Normalmente Cerrado
Contacto auxiliar
1 Pulse Dur (pole) 0,0 - - ms
conmutado
Bobina de cierre 1 I bobina CIE med 6,11 - - A

Date: Tester: Signature:


08/10/2017 12:38:12
KoCoS
p.m.
ACTAS Advanced circuit breaker test system KoCoS Messtechnik AG Südring 42, D-34497 Korbach, Tel.: +49 (0)5631-9596 -0 Fax. -16