You are on page 1of 3

MAU/AHU FAN TEST REPORT

Design Condition /
Actual Remarks
Specs.
Designation MAU1-PH1

Brand: Daikin Daikin Photo :

Assembly 1, Office ph1 Assembly 1, Office ph1


Area Served
Adobe Acrobat
Document

Air Quantity, cmh 35100 31556 (Actual requirements 16,000 cmh)

Duct Size, W x D, mm 2000x1400 2000x1400

Air velocity, m/s 11.27

ESP,Pa 500 500

Taken by: Inspected by: Witnessed by:

Name : Rino Liong Name : Thendy Kumala Name : Riko Efendi

Company : PT. SKSB Company : AEA Company : WIK Batam

Date : 24/11/2020 Date : 24/11/2020 Date : 24/11/2020

WIK BATAM LEED CERTIFICATION


MAU/AHU FAN TEST REPORT

Design Condition /
Actual Remarks
Specs.
Designation MAU2-PH2

Brand: Daikin Photo :

Area Served Assembly 2 and 3, Office ph2 Not available for measurement-

Air Quantity, cmh 16,000 Inoperative (due for repair)

Duct Size, W x D, mm 1200x1000

Air velocity, m/s

ESP,Pa 600

Taken by: Inspected by: Witnessed by:

Name : Rino Liong Name : Thendy Kumala Name : Riko Efendi

Company : PT. SKSB Company : AEA Company : WIK Batam

Date : Date : Date :

WIK BATAM LEED CERTIFICATION


MAU/AHU FAN TEST REPORT

WIK BATAM LEED CERTIFICATION