Earth Resistivity Test Report: Name of The Project: Location
Earth Resistivity Test Report: Name of The Project: Location
1. INTRODUCTION:
The Earth Resistivity Test (ERT) of soil was carried out at site for STUDIES WORK FOR
ANDHRAPRADESH MEDTECH ZONE (AMTZ), VISHAKHAPATNAM, ANDHRAPRADESH. with
the aim to determine an average value of electrical resistivity of soil for design of safe
earthing system. The Earth resistivity field test was done in 06/07/2017 at one location
given as directed by the client.
2. PURPOSE OF INVESTIGATION:
The purpose of this investigation is to determine an average value of electrical
resistivity of subsurface for design of safe earthing system with the help of
Microprocessor based electrical resistivity meter model DET-Auto.
3. GEOPHYSICAL INVESTIGATION:
Geophysical investigation was carried out as per IS: 3043-1987 on the basis of Earth
Resistivity meter model no. DET-Auto. Wenner’s four-electrode method is used to
determine the earth resistivity.
4. WENNER’S CONFIGURATION:
This is one of the most commonly used arrays proposed by Wenner in 1916. Four
electrodes A, B, M, and N are placed at the surface of the ground along a straight
symmetrically about a point O. The observation point in such a way that the distance
between AM = MN =NB = a., Where ‘a’ is called electrode separation see fig. 1.
Current ‘I’ is sent generally through outer electrodes A and B and the potential
difference (V) is measured between M and N. The instrument multification factor is f.
Apparent Resistivity, = 2aR (As per IS: 3043 – 1987, Clause No. : 36.3.1.2)
A M N B
a a a
5. Survey Procedure:
Resistivity sounding is used to make investigations along the depth. In this method
the center of configuration is kept fixed and measurements are made by successively
increasing electrode spacing. The apparent resistivity values obtained with increasing
values of electrode separations are used to estimate the thickness and resistivity of
the subsurface formations. In Wenner’s configuration all the four electrodes are
arranged in a line at a equal distance ‘a’ between the consecutive electrodes.
Measurements were taken at 1m,2m,3m & 5.0m. Current is sent through the outer
electrodes and the potential difference is measured between the inner electrodes.
The Resistance (R = V/I) is measured for each electrode separation and apparent
resistivity is calculated by multiplying value of ‘R’ with Wenner configuration factor
(2a), where ‘a’ is the uniform distance between the elctrodes. The computation of
the sounding data is discussed in the subsequent section.
7. Results:
I. The electric resistivity test of the site were performed in 06/07/2017 at one location as
suggested by client.
III. Average Resistivity / Equivalent Radius from polar curve is 14.927 ohm-m.
8. LIMITATION
The Electrical resistivity testing has been carried out at the location chosen by the
client. In general resistivity values are influenced by water, presence of dissolved ions
in soil media and nature of strata. Recommendations made in the report are hence
valid only for tested locations only. However if there is any change in subsoil
conditions and properties at places beyond chosen test locations, the soil consultants
to be contacted for further guidance.
Direction: North
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f '' = 2aRf
1.50 0.50 1.00 2.460 1 15.457
3.00 1.00 2.00 1.000 1 12.566
4.50 1.50 3.00 1.000 1 18.850
7.50 2.50 5.00 0.360 1 11.310
Direction: North-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f '' = 2aRf
1.50 0.50 1.00 2.000 1 12.566
3.00 1.00 2.00 0.860 1 10.807
4.50 1.50 3.00 0.590 1 11.121
7.50 2.50 5.00 0.300 1 9.425
Direction: East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f '' = 2aRf
1.50 0.50 1.00 1.120 1 7.037
3.00 1.00 2.00 0.770 1 9.676
4.50 1.50 3.00 0.490 1 9.236
7.50 2.50 5.00 0.390 1 12.252
Direction: South-East
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f '' = 2aRf
1.50 0.50 1.00 0.990 1 6.220
3.00 1.00 2.00 0.910 1 11.435
4.50 1.50 3.00 0.750 1 14.137
7.50 2.50 5.00 0.470 1 14.765
Direction: South
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f '' = 2aRf
1.50 0.50 1.00 0.930 1 5.843
3.00 1.00 2.00 1.270 1 15.959
4.50 1.50 3.00 0.860 1 16.211
7.50 2.50 5.00 0.830 1 26.075
Direction: South-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f '' = 2aRf
1.50 0.50 1.00 1.410 1 8.859
3.00 1.00 2.00 1.400 1 17.593
4.50 1.50 3.00 0.680 1 12.818
7.50 2.50 5.00 0.540 1 16.965
Direction: West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f '' = 2aRf
1.50 0.50 1.00 2.110 1 13.258
3.00 1.00 2.00 1.170 1 14.703
4.50 1.50 3.00 0.600 1 11.310
7.50 2.50 5.00 0.390 1 12.252
Direction: North-West
Test Electrodes Test Electrodes Distance Apparent
Resistance, Ohm Current Factor
AB / 2 MN / 2 'a' Resistivity
in m in m in m R=V/I f '' = 2aRf
1.50 0.50 1.00 2.520 1 15.834
3.00 1.00 2.00 1.690 1 21.237
4.50 1.50 3.00 0.770 1 14.514
7.50 2.50 5.00 0.550 1 17.279
Project: STUDIES WORK FOR ANDHAPRADESH MEDTECH ZONE (AMTZ), VISHAKHAPATNAM, ANDHAPRADESH
Direction of Test
Avg. Maximum Minimum
Electrodes Electrodes Distancs
North North-East East South-East South South-West West Nourth West Resistivity Resistivity Resistivity
AB / 2 MN / 2 'a'
Sr. No. at Depth at Depth at Depth
m m m R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) R (Ω) f ρ(Ω.m) ρavg(Ω.m) ρmax(Ω.m) ρmin(Ω.m)
1 1.50 0.50 1.00 2.460 1 15.457 2.000 1 12.566 1.120 1 7.037 0.990 1 6.220 0.930 1 5.843 1.410 1 8.859 2.110 1 13.258 2.520 1 15.834 10.634 15.834 5.843
2 3.00 1.00 2.00 1.000 1 12.566 0.860 1 10.807 0.770 1 9.676 0.910 1 11.435 1.270 1 15.959 1.400 1 17.593 1.170 1 14.703 1.690 1 21.237 14.247 21.237 9.676
3 4.50 1.50 3.00 1.000 1 18.850 0.590 1 11.121 0.490 1 9.236 0.750 1 14.137 0.860 1 16.211 0.680 1 12.818 0.600 1 11.310 0.770 1 14.514 13.525 18.850 9.236
4 7.50 2.50 5.00 0.360 1 11.310 0.300 1 9.425 0.390 1 12.252 0.470 1 14.765 0.830 1 26.075 0.540 1 16.965 0.390 1 12.252 0.550 1 17.279 15.040 26.075 9.425
Page 6 of 8
Average Resistivity in Direction 14.546 10.980 9.550 11.640 16.022 14.059 12.881 17.216 13.362
IDAX CONSULTING & RESEARCH PVT.LTD.