AIRCONDITIONING SCHEDULE OF EQUIPMENT

A. WINDOW TYPE AIR CONDITIONER

DESIGNATIO CAPACITY ( kj/hr ) m³/min kW AMPERE VOLTS PHASE HERTZ BREAKER WIRE
N
W 1 hp 9496 1.84 8 230 Single 60 20 AT 2-5.5 mm²
W 1.5 hp 12660 12.9 2.1 12 220 Single 60 30 AT 2-5.5 mm²
W 2 hp 18990 15.05 3.6 15 220 Single 60 40 AT 2-5.5 mm²

B. SPLIT TYPE AND PACKAGE TYPE OF AIR CONDITIONERS

DESIGNATIO CAPACIT COMPRESSOR EVAPORATOR CONDENSER VOLTS PHASE HERTZ BREAKER WIRE
N Y
kj/hr TYPE FLA m³/min FLA FLA 220
SP 1.0 12660 Hermetic 11 12.64 1 1 220 Single 60 30 AT 2-5.5 mm²
SP 1.5 18990 do 11.8 15.2 1.35 1.35 220 Single 60 30 AT 2-5.5 mm²
SP 2.0 25320 do 15.4 19.83 1.5 1.5 220 Single 60 40 AT 2-8.0 mm²
SP 3.0 37980 do 23 34 3.6 4.9 220 Single 60 70 AT 2-8.0 mm²
SP 5.0 63300 do 22 57 2.8 3.5 220 Single 60 50 AT 2-8.0 mm²
SP 7.5 94950 do 34 84 5 5 220 Single 60 100 AT 2-14 mm²
SP 10.5 126600 do 44 115.58 6.5 7 220 Single 60 100 AT 2-22 mm²
SP 15.0 189900 do 72 175 9 9 220 Single 60 200 AT 2-30 mm²

SIZE OF ELEVATORS IN HP PLUS SIZES OF CONDUCTORS AND CONTROLS

RATING FLA SIZE OF WIRE SIZE OF CIRCUIT BREAKER


15 HP, 3 PHASE, 230 VOLTS 52.5 3-14 mm², THW 225 AF, 125 AT, 3 PHASE, 230 V
25 HP, 3 PHASE, 230 VOLTS 68 3-22 mm², THW 225 AF, 175 AT, 3 PHASE, 230 V
35 HP, 3 PHASE, 230 VOLTS 92 3-38 mm², THW 400 AF, 250 AT, 3 PHASE, 230 V
40 HP, 3 PHASE, 230 VOLTS 104 3-50 mm², THW 400 AF, 275 AT, 3 PHASE, 230 V
50 HP, 3 PHASE, 230 VOLTS 130 3-60 mm², THW 400 AF, 350 AT, 3 PHASE, 230 V