Professional Documents
Culture Documents
Chapter 1
Introduction to Power System Analysis
Lecture by
Zetty Nurazlinda Zakaria
Announcements
For lectures 1 please be reading Chapter 3
Tutorial#1 3.28, 3.41, 3.42, 3.45, 3.46, 3.49;
1
The knowledge that students can
obtain from this topic are:
1. Explain the major problem in electric power
system such as load flow, optimal power flow,
symmetrical fault, unsymmetrical fault and
stability.
2. To representation the components on electric
power system
3. Design the single-line diagram, impedance
diagram and admittance diagram of the electric
power system
4. Calculate the per-unit of the electric power system
components
3
Y Y-Y ∆-Y
SINGLE LINE DIAGRAM
4
Electric Power
Generation,
Transmission &
Distribution
3 main/core business of TNB :-
Generation
Transmission
Distribution
Energy delivered to customers
are managed by :-
Transmission Division (Grid)
Power Generation
Transmission System
Distribution Division
Distribution System
2
Power System Notation
• Power system components are usually shown as
‘Single Line Diagram’:
Generator Transformer CB TL Bus bar Load
Y Y-Y ∆-Y
Notation - Power
• Power: Instantaneous consumption of energy
• Power Units:
▫ Watts = voltage x current for dc (W)
kW – 1 x 103 Watt
MW – 1 x 106 Watt
GW – 1 x 109 Watt
• Power generation capacity connected to the
Malaysian National Grid is 19,023 MW, with a
maximum demand of 13,340 MW.
Notation - Power
• Energy: Integration of power over time; energy is
what people really want from a power system
• Energy Units
Joule = 1 Watt-second (J)
kWh – Kilowatthour (3.6 x 106 J)
Btu – 1055 J;
1 MBtu=0.292 MWh
3
Power System Examples
• Electric utility: can range from quite small, such as an
island, to one covering half the continent there are four
major interconnected ac power systems in North
American, each operating at 60 Hzac; 50 Hz is used in
some other countries.
Utility Restructuring
• Driven by significant regional variations in
electric rates
• Goal of competition is to reduce rates through
the introduction of competition
• Eventual goal is to allow consumers to choose
their electricity supplier
• Restructure by bidding
10
4
• But, the problems are:
Y Y-Y ∆-Y
6 lectures 5 lectures
•Fault Calculation •Power Flow Solution
2 lectures
• Stability 13
Generator 2
Load B
1 a) Single Line Diagram for an Electrical Power System
Load A T1 Trsm T2
Load B
5
System Modeling
• Systems are represented on per-phase basis
2. Transformer model
16
17
6
3. Load models
18
4. The circuit law are valid in per-unit systems, and the power and
voltages equations are simplified since the factor of √3 and 3 are
eliminated in the per-unit system
19
20
7
• Almost all power system analysis are performed
in per-units
21
22
23
8
Per Unit Conversion Procedure, 1φ
1. Pick a 1φ VA base for the entire system, SB
2. Pick a voltage base for each different voltage
level, VB. Voltage bases are related by
transformer turns ratios. Voltages are line to
neutral.
3. Calculate the impedance base, ZB= (VB)2/SB
4. Calculate the current base, IB = VB/ZB
5. Convert actual values to per unit
Note, per unit conversion on affects magnitudes, not
the angles. Also, per unit quantities no longer have
units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts)
24
25
Original Circuit
26
9
Per Unit Example, cont’d
8kV 2
Z BLeft = = 0.64Ω
100 MVA
80kV 2
Z BMiddle = = 64Ω
100MVA
16kV 2
Z BRight = = 2.56Ω
100MVA
1.0∠0°
I = = 0.22∠ − 30.8° p.u. (not amps)
3.91 + j 2.327
VL = 1.0∠0° − 0.22∠ − 30.8° × 2.327∠90°
= 0.859∠ − 30.8° p.u.
2
VL
S L = VL I L* = = 0.189 p.u.
Z
SG = 1.0∠0° × 0.22∠30.8° = 0.22∠30.8° p.u.
28
10
Three Phase Per Unit
Procedure is very similar to 1φ except we use a 3φ
VA base, and use line to line voltage bases
1. Pick a 3φ VA base for the entire system, S B3φ
2. Pick a voltage base for each different voltage
level, VB. Voltages are line to line.
3. Calculate the impedance base
VB2, LL ( 3 VB , LN ) 2 VB2,LN
ZB = = =
S B3φ 3S1Bφ S 1Bφ
Exactly the same impedance bases as with single phase!
30
31
32
11
3φ Per Unit Example, cont'd
1.0∠0°
I = = 0.22∠ − 30.8° p.u. (not amps)
3.91 + j 2.327
VL = 1.0∠0° − 0.22∠ − 30.8° × 2.327∠90°
= 0.859∠ − 30.8° p.u.
2
VL
S L = VL I L* = = 0.189 p.u.
Z
SG = 1.0∠0° × 0.22∠30.8° = 0.22∠30.8° p.u.
34
Example
Given a 100-V sinusoidal source in series with a 3-Ω resistor, a
8-Ω inductor and a 4-Ω capacitor. Solve the problem in per-unit
on base of Vbase = 100V and Sbase = 500VA. Calculate the
complex power delivered to each of the four elements in the
circuit in per-unit
12
We convert the circuit values to per-unit :-
0
V 100 0 0
V pu = = = 1 0 = 1+ j0
V base 100
R 3
R pu = = = 0 . 15
Z base 20
XL 8
X Lpu = = = 0 . 40
Z base 20
XC 4
X Cpu = = = 0 . 20
Z base 20
36
37
2 2
SCpu = - jI XC = - j(4)(0.2) = 0 - j3.2
38
13
Example Change of Base
The reactance of the generator designated X” is
given as 0.25 per-unit based on the generator
nameplate rating of 18 kV, 500 MVA. The base for
calculation is 20 kV, 100 MVA. Find X” on the
new base.
Solution:
100
X e = 0.0369 × = 0.0683 p.u.
54
40
Transformer Reactance
Transformer reactance is often specified as a
percentage, say 10%. This is a per unit value
(divide by 100) on the power base of the
transformer.
Example: A 350 MVA, 230/20 kV transformer
has leakage reactance of 10%. What is p.u. value
on 100 MVA base? What is value in ohms (230
kV)? 100
X e = 0.10 × = 0.0286 p.u.
350
230 2
0.0286 × = 15.1 Ω
100 41
14
PER-UNIT IMPEDANCES IN SINGLE
PHASE TRANSFORMER CIRCUIT.
For transformer:
Example
A single-phase transformer is rated 110/440 V, 2.5 kVA.
Leakage reactance measured from the low-voltage side
is 0.06 Ω. Determine leakage reactance in per-unit.
Solution:
43
44
15
So, a great advantage in making per-unit computations
is realized by the proper selection of different bases for
circuits connected to each other through a transformer.
45
Example
Three parts of a single-phase electric system are
designated A, B and C and are connected to each other
through transformers, as shown in Fig. The transformers
are rated as follows:
A-B: 10,000 kVA, 13.8/138 kV, leakage reactance 10%
B-C: 10,000 kVA, 138/69 kV, leakage reactance 8%
If the base in circuit b is chosen as 10,000 kVA, 138kV,
find the per-unit impedance of the 300 resistive load in
circuit C referred to circuit C, B, and A. Draw the
impedance diagram neglecting magnetizing circuit,
transformer resistances and line impedances.
46
Solution:
Base voltage for circuit A: 0.1x 138 = 13.8 kV
Base voltage for circuit C: 0.5 x 138 = 69 kV
Base impedance of circuit C:
1-10 2-1
A B C 300
A-B B-C
Fig 1. Circuit example.
47
16
• Per-unit impedance of load in circuit C:
300
= 0.63 p.u.
476
300 x 22 x 0.12 = 12
50
17
j0.1 j0.08
0.63+j0
Remember:
1. Y-Y
2. Y-∆
3. ∆-Y
4. ∆-∆
18
Distribution Transformer
LTC
Radiators
W/Fans
115 – 35 kV distribution transformer
Source: Tom Ernst, Minnesota Power 54
230/115 kV Transformer
230 kV surge 115 kV surge
arrestors arrestors
Oil Cooler
Oil
Radiators
pump
W/Fans
Source: Tom Ernst, Minnesota Power 55
19
3φ Transformer Interconnections
∆-Y ∆
Y-∆
57
Solution:
20
The per unit network is shown in Fig 1(a) and (b).
Use the transformer bank ratings as base
quantities, Sbase3ø = 1200 MVA, VbaseHLL = 345 kV
and IbaseH = 1200/(345 ) = 2.008 kA. The per
unit load voltage and load current are then
60
61
Example
Three transformers, each rated 25 MVA, 38.1/3.81
kV, are connected Y-∆ with a balanced load of
three 0.6 Ω, Y-connected resistors. Choose a base
of 75 MVA, 66 kV for the high-voltage side of the
transformer and specify the base for the low-
voltage side. Then, determine the load resistance
RL in ohms referred to the high-voltage side and
the per-unit value of this resistance on the chosen
base.
62
21
Solution
63
s Zs
p s
t
p
Zp
Zt
t
64
Schematic diagram Equivalent circuit
Note:
65
22
• Three impedances may be measured by the
standard short-circuit test, as follows:
Zps = Zp + Zs
Zpt = Zp + Zt
Zst = Zs + Zt
Where:
67
68
23
Example #1(a)
The three phase ratings of a three winding transformer are:
Find the per unit impedances of the per phase equivalent circuit for
a base of 15 MVA, 66 kV in the primary circuit.
69
Solution
• With a base of 15 MVA, 66 kV, in the primary circuit, the proper
bases for the per unit impedances of the equivalent circuit are 15
MVA, 66 kV for primary-circuit quantities, 15 MVA, 13.2 kV for
secondary-circuit quantities, and 15 MVA, 2.3 kV for tertiary-circuit
quantities.
• Since Zps and Zpt are measured in the primary circuit, they are
already expressed on the proper base for the equivalent circuit. No
change of voltage base is required for Zst is made as follows:
70
71
24
Example #1(b)
A constant voltage source (infinite bus) supplies a
purely resistive 5MW, 2.3kV three-phase load and a
7.5MVA, 13.2 kV synchronous motor having a
subtransient reactance of X” = 20%. The source is
connected to the primary of the three-winding
transformer described in Fig. The motor and the
resistive load are connected to the secondary and
tertiary of the transformer. Draw the impedance
diagram of the system and mark the per-unit
impedances for a base of 66kV, 15 MVA in the primary.
Neglect exciting current and all resistance except that
of the resistive load.
72
Solution
The constant-voltage source can be represented by
a generator having no internal impedance.
73
Solution
74
25
Per unit computations
The following points should be kept in mind:
76
26
Phase Shifting Transformers
Phase shifting transformers are used to control
the phase angle across the transformer
Since power flow through the transformer
depends upon phase angle, this allows the
transformer to regulate the power flow through
the transformer
Phase shifters can be used to prevent
inadvertent "loop flow" and to prevent line
overloads.
78
79
80
27
Northern & Eastern Regional Control
Centre (NERCC)
81
Autotransformers
Autotransformers are transformers in which
the primary and secondary windings are
coupled magnetically and electrically.
This results in lower cost, and smaller size
and weight.
The key disadvantage is loss of electrical
isolation between the voltage levels. This can
be an important safety consideration when a
is large. For example in stepping down
7160/240 V we do not ever want 7160 on the
low side!
82
28