Manual

for
LEAKAGE COST.xls
Made by Mats Lundgren

The background
LEAKAGE COST is a spread sheet to theo- these indata some outdata.
retically and approximately estimate the To give a better understanding and overview
losses in a ventilation system from the as- there is two very simple sketches over the sys-
pect of different tightness classes. tem which are located so that the details of the
The spread sheet gives the possibility to vary sketches and the corresponding data in the
some indata for the system and calculates from spread sheet lines up opposite each other.

The explanations and general information


CELLS with blue figures and with light blue fill All cells except those for input are locked. You
colour are intended for input. Note that also the can anyhow simple remove the protection of the
tightness classes can be changed. sheet (no password) and you then have full
Cells with green figures shows calculated in- freedom to under own responsibility experiment
termediate results. with texts and formulas.
Cells with red figures shows calculated final The columns O, P, Q and S, T, U plus W, X
results. and Y are hidden. They contain detail calcula-
Cells and bars with green fill colour shows tions for different pressure parts (high, middle
what is delivered from the system. and low) of the system.
Cells and bars with yellow fill colour shows the Printout generates three lying A4.
leakage from the system.

The layout of the ventilation system


THE SYSTEM could have existed of only a fan In order to get a reasonable fair adoption to
and a duct. The introduction of an air heater reality the duct system is divided into three
means that you can work with a bigger cost pressure parts (high, medium and low) with
spent on the air. An air cooler can be calculated their respective area automatically put to 40, 35
in the same way as a heater. and 25 %.

The calculation
THE CALCULATION is set on automatic. This easiest to give the efficiency of the heater an
means that the sheet is recalculated at once an absurdly high value (e.g. 10 000 000 %) and
input cell is changed. If you want to do this dif- neglect the warning. The same goes for the fan.
ferent you can choose Tools/Alternative…/ Cal- If you want to calculate with the same pres-
culation/Manual. The calculation is then done sure in the whole system it is easiest to give the
first when you press F9. different parts the same value.
If you input data outside the recommended The fact that the specific heat capacity of the
value ranges you get an enlightening warning. air (also called heat capacitivity) and its density
The calculation is however done with the values changes at different temperatures has not been
you put in. involved in the formulas due to its negligible ef-
If you want to calculate without heating it is fect on the result.

The calculation in short


1. FIRST the amount of air that is delivered needs to be fed in to the system. The calcu-
from the system is set. This is taken for lation is in other words done from bottom
granted to be the same for both tightness and upwards in the spread sheet.
classes. 4. At last the difference between the two tight-
2. Then the leakage for each tightness class is ness classes is calculated, in the column to
calculated. It will differ. the right. Since what is delivered according
3. Then the delivered and the leakage for re- to paragraph 1 was assumed to be the same
spective tightness class are summed. This there will always be zeroes at the bottom in
will then also differ and is consequently what this column.