Professional Documents
Culture Documents
Distance protection
The basic principle of distance protection involves the division of the voltage at the
relaying point by the measured current. The apparent impedance so calculated is
compared with the reach point impedance. If the measured impedance is less than
the reach point impedance, it is assumed that a fault exists on the line between the
relay and the reach point. When a fault occurs in an electrical transmission line,
the distance relays detect the faulty line and type of fault but they may under
reach/over reach depending upon pre-fault loading, fault resistance and remote
end in-feeds. The impedance estimated by a digital distance relay reduces with
the increase in the speed at which the estimate is obtained [4].
The algorithm developed for distance protection is simply presented in figure
XX.
Figura 2 Distance protection
When fault occurs at t=t 0 at point F, the voltage and current detected by point M
are:
(3)
u ( t )=( 1+ ρmu ) ub ( t−t 0−τ mf ) +γ mu γ m 2u ρmu u ( t −t 0 −τ mf −2 τ mn ) + ( 1+ ρmu ) ρ fu ρmu ub ( t−t 0 −τ mf −3 τ m n ) …
b
(4)
i ( t )=( 1+ ρmi ) i b ( t−t 0−τ mf ) +γ mi γ m 2 i ρmi u ( t−t 0−τ mf −2 τ mn ) + ( 1+ ρmi ) ρfi ρmi ub ( t−t 0−τ mf −3 τ mn ) …
b
In order to produce the electrical system more realistically, the system equivalents
used are only in the second bar adjacent to the study transmission line. The data
are presented in Tables 1, 2 3 and 4.
Table 1Impedance data for region lines
Voltage [kV]
Substation Rp [ohm] Rs [ohm] Xp [ohm] Xs [ohm]
P S T
Nossa
Senhora 230 Y 69 D 13,8 Y 0.43 0.04 21.5 1.94
do Socorro
Penedo 230 Y 69 Y 0.69 0.06 34.46 3.1
Table 3:Data equivalent sources
Disturbances are created along the transmission line in order to validate the
algorithms embedded in the software. After the generation of the COMTRADE
Standard C37.111 files, the data obtained from the systems is inserted into the
application as can be seen in figure X
The POINT FAULT ANALYSIS application program supports the analysis of failure
events in your network. It provides a graphical display of the data recorded during
the failure event and can use the measured values to calculate other variables
such as impedances, outputs or RMS. values, which facilitates analysis of the fault
log and the performance of a protection. In this application, the software is firstly
used to analyze the behavior of the distance protection for faults applied in the
transmission line. A single-phase short-circuit with no resistance in the middle of
the transmission line is the first case under study. For the case elucidated, the
instantaneous values of the current and the current in the line are shown in figure
X.
In both terminals of the transmission line, the protection is based and an IED that
contains the protection to the distance (quadrilateral characteristic) with the
following characteristics
Table 5: Distance protection setting
Function Settings
R1
Distance X (Ω/) K0
(Ω/phase)
Zone 1 (ph-ph) 43.759 43.759 --
After the step of elaborating the protection settings, the software parameterization
is executed and the following quadrilateral characteristic shown in figure X is
obtained.
REFERENCES