PROJECT

OWNER:
SINGLE-LINE DIAGRAM LEGEND EREN/QUAATRO
MV Fuses ANSI PROTECTION CODES

PROJECT:
OVERVOLTAGE / Engineering, Procurement of Equipment, Construction of
59 27
Load-break switch UNDERVOLTAGE PV Station 20 MW
OVERFEQUENCY /
81H 81L
UNDERFREQUENCY

LOCATION:
Switch Disconnector

PROJECT
81R RATE OF CHANGE OF FREQUENCY
(ROCOF)
Bom Jesus da Lapa - Riacho de Santana (BJL 11 ), Brazil
Length 1000 m Length 200 m Length 450 m
AL/XLPE 35kV AL/XLPE 35kV AL/XLPE 35kV Earthing switch
BJL11_DELIVERY SUBSTATION_P10-DELCB1
INDOOR MV CUBICLES, 36kV, 630A, 6.44kA-1sec 50 INSTANTANEOUS OVERCURRENT
MAIN CIRCUIT AUX. TRANSFORMER PV PLANT CIRCUIT PV PLANT CIRCUIT PAD-MOUNTED OIL PAD-MOUNTED OIL PAD-MOUNTED OIL PAD-MOUNTED OIL PAD-MOUNTED OIL PAD-MOUNTED OIL
TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER Surge arrester
BREAKER FIELD FIELD BREAKER FIELD 2 BREAKER FIELD 1 Dy11y11 Dy11y11 Dy11y11 Dy11y11 Dy11y11 Dy11y11
2100 / 1050 /1050 KVA 2100 / 1050 /1050 KVA 2100 / 1050 /1050 KVA 2100 / 1050 /1050 KVA 2100 / 1050 /1050 KVA 2100 / 1050 /1050 KVA
51 TIME OVERCURRENT
Medium Voltage Single Line Diagram

DOCUMENT
33//0,55-0,55 kV 33//0,55-0,55 kV 33//0,55-0,55 kV 33//0,55-0,55 kV 33//0,55-0,55 kV 33//0,55-0,55 kV
3x630A 3x630A KW
KWH
50 50N 50 51 59N 50 51 59N

TITLE:
M M M
KWH
51 51N 51N 50N 51N 50N
Power energy measurement system 50N
81H 81L 27 59 27 59
KWAr INSTANTANEOUS EARTH FAULT
KWAr
Inv 6-1 Inv 6-2 Inv 6-1 Inv 6-2 Inv 6-1 Inv 6-2 Inv 6-1 Inv 6-2 Inv 6-1 Inv 6-2 Inv 6-1 Inv 6-2

PROJECT

PROJECT
PHASE:
51N 51G EARTH FAULT

SCALE:
DRAFT
DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER

CODE:
1050kVA, 550V 1050kVA, 550V
DRY TYPE

1050kVA, 550V 1050kVA, 550V 1050kVA, 550V 1050kVA, 550V


DRY TYPE

1050kVA, 550V 1050kVA, 550V 1050kVA, 550V 1050kVA, 550V


DRY TYPE

1050kVA, 550V 1050kVA, 550V


M M.V. motorized circuit-breaker -
AUXILIARY AUXILIARY AUXILIARY
10kA 10kA
UPS
T/F AN Dyn
UPS
T/F AN Dyn
UPS
T/F AN Dyn OVERVOLTAGE /
10kVA 10kVA 10kVA 59 59Ν RESIDUAL OVERVOLTAGE

DOCUMENT

REVISION:
550V/380V 550V/380V 550V/380V

VOLUME /
0%, ±2,5%, ±5% 0%, ±2,5%, ±5% 0%, ±2,5%, ±5%
Auxiliaries kiosk Auxiliaries kiosk Auxiliaries kiosk

SHEET:
AL 35kV
01 1/1

CODE:
M.V circuit-breaker
UNDERVOLTAGE /
TO 34,5kV Length 1600 m 27 27D
POSITIVE SEQUENCE UNDERVOLTAGE
Substation AL/XLPE 35kV 50kVA
34,5/0,380kV
60Hz
±2,5%, ±5%
26 63
Current transformer 79 RECLOSER REVISION 01 27/10/2016 FIRST SUBMISSION

AMENDMENTS:
ONAN Dyn11

COMMENTS:
2nd HARMONIC RESTRAINT REVISION 02 22/12/2016 SECOND SUBMISSION_DRAFT VERSION

DOCUMENT
68
(INRUSH DETECTION)
Voltage transformer REVISION 03
UPS
Length 230 m Length 280 m 78 VECTOR SHIFT REVISION 04
AL/XLPE 35kV AL/XLPE 35kV Capacitor type voltage dividers with VOLTAGE SYMMETRY / NEGATIVE
voltage presence indicator on 3 phase 47
SEQUENCE OVERVOLTAGE
PAD-MOUNTED OIL PAD-MOUNTED OIL PAD-MOUNTED OIL PAD-MOUNTED OIL THERMAL DEVICE (THERMOSTAT) /
TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER 26 63
Dy11y11 Dy11y11 Dy11y11 Dy11y11 Mechanical key lock system OIL PRESSURE RELAY (BUCHHOLZ)
2100 / 1050 /1050 KVA 2100 / 1050 /1050 KVA 2100 / 1050 /1050 KVA 2100 / 1050 /1050 KVA
33//0,55-0,55 kV 33//0,55-0,55 kV 33//0,55-0,55 kV 33//0,55-0,55 kV

ENGINEERING:
M.V. CABLE TERMINALS CONSTRUCTION COMPANY

DESIGNER /
S O L A R P O W E R
Inv 6-1 Inv 6-2 Inv 6-1 Inv 6-2 Inv 6-1 Inv 6-2 Inv 6-1 Inv 6-2
DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER DC/AC INVERTER
1050kVA, 550V 1050kVA, 550V 1050kVA, 550V 1050kVA, 550V 1050kVA, 550V 1050kVA, 550V 1050kVA, 550V 1050kVA, 550V
2-Winding Power Transformer
DRY TYPE DRY TYPE
AUXILIARY AUXILIARY
T/F AN Dyn T/F AN Dyn
UPS UPS
10kVA 10kVA
550V/380V 550V/380V
0%, ±2,5%, ±5% 0%, ±2,5%, ±5%
Auxiliaries kiosk Auxiliaries kiosk
3-Winding Power Transformer

VALIDATION:
160A
LV Circuit Breaker
50A