You are on page 1of 6

Electrical Engineering 83 (2001) 187±192 Ó Springer-Verlag 2001

A new approach to arc resistance calculation


V. V. Terzija, H.-J. Koglin

187
Contents Arc resistance is an important macroscopic arc arc can be considered as an element of an electrical power
parameter, which describes the complex nature of arcs. As system having a resistive nature, i.e. as a pure resistance.
it is known, the fault arc resistance can be calculated by the The length variation is an important factor in describing
Warrington formula. Authors investigated the results of the arc behavior and arc resistance. The nature of arc
Warrington's tests. Warrington derived a relation for the elongation effects are dif®cult and extremely non-station-
arc voltage by using the measured arc voltage gradient and ary, so they are not simple to model. Results presented in
arc current as input data. By analyzing these measure- this paper are limited to the calculation of the resistance of
ments and by taking into account the conditions under the long arc in free air. Suitable similar new approaches for
which they are obtained (inaccurate measurement devic- short arcs, existing in circuit breakers, could be also de-
es), it is unquestionable that the results are highly em- veloped.
pirical and not accurate and general enough. Laboratory In the case of short-circuits occurring on lines within
testing, provided in the high-power test laboratory FGH- medium- and high-voltage networks, distance protection
Mannheim (Germany), in which long high current arcs are has to locate precisely the fault point for a selective in-
initiated, was the base for the research results presented. terruption of the fault. In most cases (over 90%) short
In this paper a new approach to arc resistance calculation circuits in a network are followed by an arc (arcing faults),
is given. Two independent approaches delivered the same so an impedance evaluation, i.e. fault location, is disturbed
equation. Both approaches are based on a suitable and a by the arc voltage arising at the fault point. In other words,
simple arc model assuming the rectangular wave form of the arc is the source of errors, if it is not taken into con-
the arc voltage, which is in phase with the arc current wave sideration when locating the fault. To avoid these errors,
form. The new formula for arc resistance is compared with the well-known Warrington formula [2] for arc resistance
the Warrington formula. The in¯uences of arc elongation calculation is used.
are also investigated. Empirically obtained results play an important role in
investigating the nature of electrical arcs. One of the ear-
1 liest experimental studies considering the long arc in still
Introduction air is presented in [2±4]. Nowadays modern transient re-
Arc discharge is encountered in the everyday use of power corders with fast A/D converters are available.
equipment. Permanent faults in a transformer, machine, In this paper the results derived by Warrington [2] are
cable, or transmission line always involve an arc. When- investigated and compared with the results obtained from
ever a circuit breaker is opened while carrying a current, laboratory tests provided in a high-power test laboratory
an arc strikes between its separating contacts. In Fig. 1, an FGH-Mannheim (Germany). It is concluded that the
example of a three-phase arcing fault on a 20 kV overhead Warrington formula is not quite correct, so the new for-
transmission line is presented [1]. The arc existing at the mula for arc resistance calculation is derived and com-
fault point is a high power long arc in still air. It does not pared with the old, Warrington formula.
have the same properties as the much shorter arc existing Two independent approaches delivered the same new
in circuit breakers. All arcs possessing a highly complex equation for arc resistance. In the ®rst, the de®nition of
nonlinear nature, in¯uenced by a number of factors. An resistance in a-c circuits was the starting point for the for-
mula derivation, whereas in the second, the spectral analysis
approach is used. Obvious absolute relative differences be-
Received: 27 December 2000 tween the formulae, in particular for the wide range of
currents, can be noticed. The results obtained are discussed.
V. V. Terzija (&), H.-J. Koglin In this paper, ®rst Warrington results are tested, eval-
UniversitaÈt des Saarlandes uated, discussed and criticized. Second, the results ob-
Lehrstuhl fuÈr Energieversorgung tained in FGH-Mannheim are presented and a new
gebaÈude 13, D-66123 SaarbruÈcken, Germany ``macroscopic arc model'' is derived. Third, a new formula
e-mail: terziia@lev.ee.uni-sb.de
for arc resistance is derived. Two independent approaches
The authors gratefully acknowledge the Alexander von Humboldt delivered the same formula. Fourth, the new formula is
Foundation for supporting this research and the high-power compared with the Warrington formula. Before conclud-
test laboratory FGH-Mannheim (Germany) for providing the ing remarks, the aspects of arc elongation effects and its
authors with the laboratory data records. in¯uences on arc resistance are investigated.
Electrical Engineering 83 (2001)

188

Fig. 1. Three-phase arcing fault on a 20 kV overhead trans-


mission line

2
Discussion of the Warrington formula
In [2] Warrington presented his remarkable results of ®eld
tests on the high-voltage systems of the New England and Fig. 2. The original measurements and results obtained by
the Tennessee Electric Power Company. Through these Warrington [2]
tests he investigated the in¯uence of arc resistance on
protective devices and derived his well-known and widely where voltage is in volts (V), current in amperes (A) and
applied general formula for arc resistance calculation: arc length in meters (m).
K In [2] a table with all measurements obtained by War-
Ua ˆ Ea L ˆ n L …1† rington is given. Based on the full measurement set from
I
[2], in this paper parameters K and n are estimated and
where Ua is arc voltage (V), Ea is arc voltage gradient (V/ft, new estimated curves Ea over ia are derived. In Fig. 3 both
or V/m), 1 ft = 0.3048 m, L is arc length (ft, m), I is arc the full measurement set and the estimated curve for arc
RMS current (A) and K and n are the unknown constants. voltage gradient are presented. Parameters estimated in
The unknown parameters K and n are estimated from this case are:
measurements. In [2] Warrington expressed the arc length
in feet (ft). 1
K ˆ 3460:49; n ˆ 0:225333; ˆ 4:437877
In Fig. 2 the third Fig. from [2], scanned and incorpo- n
rated into this paper, is presented. In this ®gure the Both parameters are essentially different from the
measured arc voltage gradient, Ea expressed in (kV/ft), is parameters obtained by Warrington.
presented over currents in amperes. Only the selected By observing Fig. 3, it is apparent that for one current
measurement set is depicted. Bad measurements are there follow various values for arc voltage gradient. This
omitted. In [2] it is not explained how the measurements variety is probably the consequence of arc elongation
are omitted. In the same ®gure, a curve de®ning the re- occurring during the tests?
lationship between Ea and current is plotted. The curve is Under the assumption that some measurements were
obtained using the following parameters included in (1): not correct, i.e. that some of them could be treated as bad
1 data, in this paper a reduced measurement set is selected
K ˆ 8750; n ˆ 0:4; ˆ 2:5 and presented in Fig. 4. From the reduced measurement
n
set the following unknown parameters are estimated:
Parameters are valid if length is expressed in (ft). In Fig. 2,
in the Warrington formula given below the graph, the arc
voltage is expressed in volts. In other words, from the
selected measurement set, Warrington determined pa-
rameters K and n, and by using (1) obtained the curve
showing the relationship between arc voltage gradient and
arc current. By including K and n into (1), one obtains the
following formula for the arc voltage:
8750 8750 28688:5
p Lˆ 0:4 L‰…V/ft)ftŠˆ 0:4 L‰(V/m)mŠ
Ua ˆ 2:5 …2†
I I I
From (2) the next equation for arc resistance follows:
Ua 28688:5 Fig. 3. Full measurement set and estimated arc voltage gradient
Ra ˆ ˆ L‰X=mŠ …3†
I I 1:4 curve
V. V. Terzija, H.-J. Koglin: A new approach to arc resistance calculation

1 expected short-circuit currents today reach values over


K ˆ 11387:4; n ˆ 0:427663; ˆ 2:338289 60 kA), motivated the authors to investigate the possibil-
n
ities for deriving a new formula for arc resistance. The new
The new curve for Ea is depicted in the same plot.
formula should be used as an alternative to the Warring-
In Fig. 5 the full measurement set from [2] and three arc
ton one. The response of the international scienti®c society
voltage gradient curves (the Warrington, the full and the
to the new approach, which will be presented, should
reduced measurement set curves) are presented.
evaluate it and investigate whether it is suitable for prac-
It is obvious that two new independent and different
tical applications.
equations for arc voltage resistance calculation are ob-
tained. From the above results, the following general ob-
3
servations regarding Warrington ®eld tests are formulated:
Laboratory testing and modeling of long arc in still air
189
1. Measurement devices used during Warrington testing The nature of long arc in still air is investigated in the high
were relatively inaccurate, so the conclusions derived power test laboratory FGH-Mannheim (Germany), in
are not reliable enough. which a series of laboratory tests are provided. Voltage
2. During the arc life the arc length changes. These changes u…t†, current i…t† and arc voltage ua …t† are digitized from
are not considered when the Warrington formula is the laboratory test circuit depicted in Fig. 6. Arcs between
derived. arcing horns of vertical and horizontal insulator chains are
3. A criterion used in [2] by which some bad data are initiated by means of a fuse wire, when switch S in Fig. 6 is
rejected, i.e. omitted from the consideration, is not closed. The distance between electrodes is varied in the
described. It seems that the selection of the measure- range of 0.17±2 m. The range of arc currents varied be-
ments processed is provided quite arbitrarily. This task tween 2 and 12 kA.
should be solved by using the known standard robust In Fig. 7 the recorded arc voltage ua …t†, current i…t†,
estimators, that are not sensitive to bad data (outliers). which is at the same time the arc current ia …t† and the re-
4. The method describing the Warrington formula is calculated instantaneous electrical power of the arc are
derived is not mentioned in the text. plotted. Arc voltage and arc current are in phase, con®rming
5. The range of arc currents observed is rather small the resistive arc nature. The wave form of arc power is dis-
(<1 kA). torted and, from the amplitude point of view, proportional
6. The Warrington formula cannot be accepted as abso- to arc current. The long high current a-c arc voltage am-
lutely correct, so the new formulae should be derived, plitude is proportional to arc voltage length. Here the co-
compared with it and applied. ef®cient of proportionality is arc voltage gradient Ea . It is
almost independent of the arc current, so the voltage am-
The 6-th observation that the Warrington formula is not
plitudes of long high current arcs are determined by the arc
absolutely correct, as well as the fact that the formula is
length L. Over the range of currents, 100 A to 20 kA, the
not derived by analyzing a wide range of currents (the
average arc voltage gradient lies between 1.2 and 1.5 kV/m
[4±6]. In [3] it is shown that for long arcs almost all the total
arc voltage appears across the arc column.
The quantitative expression of signal distortion is the
total distortion factor THD, calculated as follows:

Fig. 4. Reduced measurement set and estimated arc voltage


gradient curve
Fig. 6. Laboratory test circuit

Fig. 5. Full measurement set from [2] and three arc voltage
gradient curves Fig. 7. Recorded arc wave forms
Electrical Engineering 83 (2001)

v
u M A. Derivation using the classical resistance de®nition
100 uX
THD ˆ t Xh2 % …4† Let us assume that arc voltage u…t† and current i…t† are
X1 hˆ2
modeled as follows:
u…t† ˆ Ua sgn‰i…t†Š …6†
where Xh …h ˆ 1; . . . ; M† is the amplitude of the h-th p
harmonic. Spectral analysis of arc voltages and currents is i…t† ˆ 2I sin xt …7†
provided through the application of Fast Fourier Trans-
form (FFT). From the calculated amplitude spectra, the The resistance R of an element belonging to an a-c circuit
corresponding THD factors for arc voltage and current are is de®ned as:
calculated. The average THD factors for arc voltage and ZT ZT
current are approximately 30 and 2%, respectively. 2 1 1
190 RI ˆ P ˆ p…t†dt ˆ u…t†i…t†dt …8†
It can be concluded that arc voltage is a distorted wave T T
form, whereas arc current is not. Thereby, arc current can 0 0
be modeled as a pure sine wave, whereas arc voltage must where I is the RMS of current and p…t† is the instantaneous
be modeled in a such a way that its distortions are taken power. By including (6) and (7) into (8), one obtains:
into account realistically enough.
By observing the arc voltage and current waveforms ZT=2
22Ua
plotted in Fig. 7, one concludes that the voltage signal has a RI ˆ i…t†dt …9†
distorted rectangular form. Additionally, it is in phase with T
0
the arc current. Thus, an arc can be represented through the
following equation, modeling the arc voltage [7, 8]: Since
ZT=2 p
p Z
T=2
ua …t† ˆ Ua sgn…ia † ‡ n …5† 2 2I
where ua …t† and ia …t† are voltage and current of an arc i…t†dt ˆ 2I sin xt dt ˆ …10†
x
having the constant length L and Ua is the amplitude of the 0 0
rectangular signal. In (5), sgn is a sign function de®ned as: Equation (9) becomes:
sgn…x† ˆ 1 if x  0 and sgn…x† ˆ 1 if x < 0 and n…t† is p p
zero-mean Gaussian noise. The value of Ua can be ob- 2 2Ua 2 2I 2 2IUa
tained as the product of arc-voltage gradient Ea and the RI ˆ P ˆ ˆ …11†
T x p
actual arc length, L.
From (11) follows the explicit expression for the arc re-
The arc voltage model (5) has already been successfully
sistance:
used for the purpose of overhead lines protection (see Ref. p
[9, 10]). In this paper, it will be the starting point for the 2 2Ua
derivation of the new formula for arc resistance calcula- Rˆ …12†
pI
tion. In Fig. 8, the simulated arc voltage (Eq. (5)) and
current from the circuit depicted in Fig. 6, as well as the Suppose that there exists a linear relationship between arc
recalculated instantaneous electrical power of the arc are voltage magnitude and arc voltage gradient:
presented. Simulation is provided using a software pack- Ua ˆ Ea L …13†
age presented in [11].
Hence
p
4 2 2 Ea L
Rˆ …14†
New formula for arc resistance p I
In this section a new formula for arc resistance calculation Equation (14) is the new formula for arc resistance cal-
is derived. One formula is derived in two independent culation. It requires a suitable selection of the value/ex-
ways: a) by using the classical de®nition of electrical re- pression for the arc voltage gradient Ea .
sistance in a-c circuits and b) by using the spectral domain
analyses approach. B. Derivation using spectral domain analyses approach
A pure square wave (Eq. (6)) can be expressed by Fourier
series containing odd sine components only, as follows:
X 1
41
u…t† ˆ Ua sgn…i† ˆ Ua sin…hxt ‡ hu1 † …15†
hˆ1
p h
where h ˆ 1; 3; 5; 7; . . . is the harmonics order, u1 is the
phase angle of the fundamental harmonic and x is the
fundamental angular frequency. From (15) follows that the
maximal and RMS values of the h-th harmonics can be
respectively calculated by using the following formulae:
4
Uah ˆ Ua …16†
Fig. 8. Simulated arc wave forms ph
V. V. Terzija, H.-J. Koglin: A new approach to arc resistance calculation

 
h 1 4 855:3 4501:6
Ua;rms ˆ p Ua …17† R2 ˆ ‡ L …28†
2 ph I I2
Hence, for the ®rst harmonic, one obtains: In (27), constant 1080.4 follows if Ea ˆ 1200 V/m, whereas
1 4 constant 1350.5 follows if Ea ˆ 1500 V/m.
1
Ua;rms ˆ p Ua …18† In the next section formulae (27) and (28) will be
2p compared with the Warrington formula:
By de®ning the arc resistance as: 28688:5
1 RW ˆ L …29†
Ua;rms I 1:4
Rˆ 1
…19†
Ia;rms The comparison will be provided by comparing the values
for a wide range of currents. 191
and by including (18) into (19), one obtains:
1 p1 4 Ua
p 5
Ua;rms 2p 2 2Ua
Rˆ 1 ˆ ˆ …20† Comparison between Warrington and new formula
Ia;rms I pI Three formulae: the Warrington formula (29) and two new
Finally, by including (13) into (20), follows the same for- formulae (27) and (28), derived in this paper, are compared
mula for arc resistance, derived by using the classical arc by changing the RMS values of arc current in the expressions
de®nition (Eq. (14)): for arc resistances, for the arc length assumed in advance.
p Here it is assumed that an 1 m long arc is analyzed
2 2 Ea L (L = 1 m). The current RMS values are changed in a wide
Rˆ …21† range: from 100±50.000 A. By using formulae (27), (28) and
p I
(29), the values for arc resistances RW , R1;1200 V=m
C. Arc voltage gradient selection …R1 for Ea ˆ 1200 V/m†, R1;1500 V=m …R1 for Ea ˆ 1500 V/m†
As already mentioned, in the new formula for arc resis- and R2 are calculated and clearly presented in Fig. 9. By
tance a suitable value/expression for the arc voltage gra- observing Fig. 9, it can be concluded that in some ranges of
dient should be included. From the electrical properties of currents RW is greater than R1 and R2 , and vice versa. In
an arc under steady conditions (u±i characteristic) point of Fig. 10, curves depicted in Fig. 9 are zoomed and presented
view, a number of equations are derived from the exper- for currents between 2 and 5 kA, so that the points at which
imental studies. The ®rst and best known is [3]: ``new arc resistances'' are equal to Warrington resistance are
observable. For example, for I ˆ 6:64 kA it follows that
C ‡ DL R1;1200 V=m ˆ RW . The ``Warrington curve'' crosses all three
Ua ˆ A ‡ BL ‡ …22†
I other curves. The currents at which the new resistances are
If in (22) L is made suf®ciently large, the terms involving equal to Warrington resistance can be simply detected in
parameters A and C may be neglected, and the charac- Fig. 11, in which the absolute relative errors, e…%†, calcu-
teristic equation becomes approximately: lated for R1 and R2 , with regard to RW , are presented re-
  spectively. For currents greater than 3.64, 2 and 6.5 kA
D respectively, Warrington resistance is smaller than
Ua ˆ B ‡ L …23†
I R1;1200 V=m , R1;1500 V=m and R2 , respectively.
If in (23) current is suf®ciently large, the arc voltage be-6
comes a function only of the arc length, according to the Extension of arc resistance equation
equation with the arc elongation model
Ua ˆ BL …24† As a matter of fact, the arc length changes during the arc
life. The elongation of the long arc is determined by
Parameter B represents the voltage gradient Ea in the arc
the magnetic forces produced by the supply current, the
column. The arcs occurring on the fault point can be
convection of the plasma and the surrounding air, the
treated as long high current arcs, so the aforementioned
discussion holds. In the open literature the following val-
ues/expressions for Ea calculation are used:
1. In accordance with (24) and from Refs. [4±6]:
Ea ˆ …1200  1500† …25†
2. In accordance with (23) and from Ref. [12]:
Ea ˆ 950 ‡ 5000=I …26†
In (26) I is expressed in amperes (A). Equations (25) and
(26) can be now included in (21), so one obtains the fol-
lowing two new equations:
L Fig. 9. Resistances obtained using Warrington and new formulae
R1 ˆ …1080:4  1350:5† …27†
I for L = 1 m
Electrical Engineering 83 (2001)

where Ra0 is the initial arc resistance, Ti is the inception of


arc ignition, h…t† is Heaviside function and a and b are
parameters de®ning the arc elongation dynamics. Natu-
rally, some other ``elongation functions'' can be used for
modeling elongation effects of an arc, as well.

7
Conclusion
Through the investigation of Warrington results it is
concluded that his well-known formula for arc resistance
192 Fig. 10. Curves from Fig. 9 for 2 kA < I < 5 kA calculation is not absolutely correct. Based on experi-
mental testing in the high-power test laboratory FGH-
Mannheim (Germany), a new formula for arc resistance is
derived. Two independent procedures of its development
are presented. The new formula requires a suitable selec-
tion of arc voltage gradient value. Two approaches for arc
voltage gradient are presented, so that two new formulae
are derived. The new formula is compared to the War-
rington formula. Obvious differences are observed. The
authors are now expecting the response of the scienti®c
audience to the results presented.

References
Fig. 11. Absolute relative errors 1. Oeding D, Speh R (1983) Test eines Digitalen Dist-
anzschutzrelais im 20-kV-Netz. etzArchiv 5: 171±173
2. Warrington AR, Van C (1931) Reactance relays negligibly
atmospheric effects (wind, humidity, pressure), i.e. affected by arc impedance. Electrical World 19: 502±505
the medium in which the arc is initiated, etc. Based on the 3. Ayrton H (1902) The Electric Arc, The Electrician, London
experimental studies provided in the high-power test 4. Strom AP (1946) Long 60-cycle arc in air. Trans. Am. Inst.
laboratory FGH-Mannheim, and assuming that arc voltage Elec. Eng. 65: 113±117
amplitude is proportional to the arc length and indepen- 5. Browne TE Jr (1955) The electric arc as a circuit element.
J. Electrochem. Soc. 102(1): 27±37
dent form the arc current (Eq. (13)), it is concluded that 6. Maikapar AS (1960) Extinction of an open electric arc.
the speed of the arc elongation reaches values over Elektrichestvo 4: 64±69
120 km/h. These speeds are greater than the speed of 7. Terzija V, Koglin HJ (2000) Long Arc in Free Air: Testing,
common winds. The previous conclusion indicates that Modelling and Parameter Estimation: Part 1. Proceedings of
from the arc elongation point of view the in¯uence of the UPEC 2000 Conference, Belfast, UK, 6±8 September
electrodynamics forces is essential. 8. Terzija V, Koglin HJ (2000) Long Arc in Free Air: Testing,
Arc model (5) does not model the arc elongation effects. Modelling and Parameter Estimation: Part 2. Proceedings of
the UPEC 2000 Conference, Belfast, UK, 6±8 September
Generally speaking, the arc elongation can be integrated into 9. Djuric M, Terzija V (1995) A new approach to the arcing
the model (5) by multiplying it with a suitable selected arc faults detection for autoreclosure in transmission systems.
elongation function L…t†. The same is valid for the arc IEEE Trans. on Power Delivery 10(4): 1793±1798
resistance. Since the elongation effects are not deterministic, 10. Radojevic ZM, Terzija VV, Djuric MB (1999) Multipurpose
but extremely stochastic, it is relatively dif®cult to model all Overhead Lines Protection Algorithm. IEE Proc.-Gener.
effects exactly. For example, the elongation function L…t† Transm. Distrib. 146(5): 441±445
can be selected in the form of an exponential function and in 11. LoÈnard D, Simon R, Terzija V (1992) Simulation von Netz-
modellen mit zweiseitiger Einspeisung zum Test von Netzs-
this form included in the arc resistance formula as follows: chutzeinrichtungen, TB-157/92 Univ. Kaiserslautern
j k
12. Goda Y et al Arc Voltage Characteristics of High Current
Ra …t† ˆ Ra0 …t Ti † 1 ‡ a eb…t Ti †
h…t Ti † …30† Fault Arcs in Long Gaps, IEEE Paper No. PE-186PRD

You might also like