FireLock® V10

Models V1001, V1003, V1005, V1007, V1009, V1011, V1013 40.72


Window Sprinklers Technical Specifications:

Models: V1001, V1003, V1005, V1007, V1009,


V1011, V1013
Style: Window Sprinkler
Nominal Orifice Size: See chart on page 2
K Factor: See chart on page 2
Nominal Thread Size: See chart on pate 2
Window Sprinklers
Max. Working Pressure: 175 psi/1200 kPa
Approvals/Listings:
Material Specifications:
Body: Brass per UNS C36000

See Victaulic Publication 10.01 for more details. Sprinkler Finishes:


Plain Brass
Product Description: Proprietary Nickel Teflon1 coating2
The Model V10 Window Sprinklers are specially VC-2503
designed open style nozzles that provide a 180°
Chrome plated and other finishes available
relatively flat fan-shaped spray pattern. They are
upon request
generally used to provide a water curtain over a glass
window or other opening to prevent fire/heat penetration. For cabinets and other accessories refer to
Other uses are to provide fire exposure protection from separate sheet.
one closely located building to another and to protect 1 Teflon is a registered trademakr of Dupont Co.
steel beams and columns to preserve structural integrity. 2 UL Listed for corrosion resistance.
The water flow to the Model V10 Window Sprinklers is 3 UL Listed and FM Approved for corrosion resistance.
controlled either by a manually operated control valve or
by means of an automatically operated deluge system.
Model V10 Window Sprinklers may be installed in
various positions depending on the hazard being
protected. The Window Sprinkler installation diagram
shown on page 3 represents a typical installation for the
protection of glass windows. However, NFPA 13 should
be consulted for the proper installation and spacing of
the Model V10 Window Sprinklers.

Exaggerated for clarity

Job/Owner Engineer
System No. Spec Section

Location Paragraph

Contractor Approved

Submitted By Date

Date

victaulic.com | Sprinklers | FireLock® | V10 | Publication 40.72


40.72 3180 Rev. F Updated 6/2014 © 2014 Victaulic Company. All rights reserved.
1
victaulic.com | Sprinklers | FireLock® | V10 | Publication 40.72

Approvals/Listings:

Model
APPROVALS/LISTINGS
V1001 V1003 V1005 V1007 V1009 V1011 V1013
1/4” 5/16” 3/8” 7/16” 1/2” 17/32” 5/8”
Orifice Size (inches)
Orifice Size (mm) 7 8 10 11 13 14 16
1/2” 1/2” 1/2” 1/2” 1/2” 3/4” 3/4”
Thread Size (inches)
Thread Size (mm) 13 13 13 13 13 19 19
Nominal K Factor Imperial 1.4 1.9 2.8 4.2 5.6 8.0 11.2
Nominal K Factor S.I.4 2.0 2.9 4.0 5.9 8.1 11.5 16.3
Height (inches) 13/4” 13/4” 13/4” 13/4” 21/16” 21/16” 21/16”
Height (mm) 44 44 44 44 52 52 52
4 For K Factor when pressure is measured in Bar, multiply S.I. units by 10.0

Dimensions:

2"

12" to 15"

10'
3,0 m
Surface of Glass

10'
3,0 m 8'
2,4 m
10'
3,0 m 8'
2,4 m 6'
1,8 m
8'
2,4 m 6'
1,8 m 4'
Distribution Patterns: 1,2 m
6'
1,8 m 4'
Model V1001
1,2 m 2'
K1.4 Window Sprinkler Distribution Patterns – Plan View 0,6 m
4'
1' 1,2 m 2'
0.3 m 0,6 m 0
4' 2' 4' 6' 8' 10'
2' 0,6 m 1,2 m 1,8 m 2,4 m 3,0 m
1.2 m
0,6 m 0
8' 2' 4' 7 psi 6' 8' 10' 15 psi 12' 14' 3
2.4 m 0,6 m 1,248
m kPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 20
0
12' 2' 4' 7 psi 6' 8' 10' 15 psi 12' 14' 30 psi
3.7 m 0,6 m 1,248
mkPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207 kPa
16' 7 psi 15 psi 30 psi
4.9 m 48 kPa 103 kPa 207 kPa
20'
6.1 m
24'
7.3m 2' 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26'
0.6 m 1.2 m 1.8 m 2.4 m 3.0 m 3.7 m 4.3 m 4.9 m 5.5 m 6.1 m 6.7 m 7.3 m 7.9 m

7 PSI 15 PSI 30 PSI


48 kPa 103 kPa 207 kPa

40.72 3180 Rev. F Updated 6/2014 © 2014 Victaulic Company. All rights reserved.
victaulic.com 2
10'
3,0 m 8'
2,4 m 6'
1,8 m
8'®
victaulic.com | Sprinklers | FireLock
2,4 m | V10 | Publication 40.726'
1,8 m 4'
Distribution Patterns: 1,2 m
6'
1,8 m 4'
Model V1003 1,2 m 2'
K1.9 Window Sprinkler Distribution Patterns – Plan View 0,6 m
4'
1' 1,2 m 2'
0.3 m 0,6 m 0
4'
2' 4' 6' 8' 10'
2' 0,6 m 1,2 m 1,8 m 2,4 m 3,0 m
1.2 m 0,6 m 0
8' 2' 4' 7 psi 6' 8' 10' 15 psi 12' 14'
2.4 m 0,6 m 1,248
m kPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 2
0 10'
12' 2' 4' 7 psi 6' 8' 12'
10' 15 psi3,0 m 14' 30 psi
3.7 m 0,6 m 1,248
mkPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207 kPa

16' 7 psi 15 psi 10' 30 psi


4.9 m 48 kPa 103 kPa3,0 m 207 kPa 8'
2,4 m
20' 10'
6.1 m 3,0 m 8'
2,4 m 6'
24'
1,8 m
7.3m 2' 4' 6' 8' 10' 8' 12' 14' 16' 18' 20' 22' 24' 26'
0.6 m 1.2 m 1.8 m 2.4 m 3.0 2,4
m m3.7 m 4.3 m 4.9 m 5.5 m 6.1 m 6' 6.7 m 7.3 m 7.9 m
1,8 m 4'
7 PSI 15 PSI 30 PSI
1,2 m
6'
48 kPa 103 kPa 207 kPa
1,8 m 4'
Model V1005 1,2 m 2'
K2.8 Window Sprinkler Distribution Patterns – Plan View 0,6 m
4'
1' 1,2 m 2'
0.3 m 0,6 m 0
2' 4' 6' 8' 10'
4' 2' 0,6 m 1,2 m 1,8 m 2,4 m 3,0 m
1.2 m 0,6 m 0
8' 2' 4' 7 psi 6' 8' 10' 15 psi 12' 14'
2.4 m 0,6 m 1,248
m kPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 20
0 10'
12' 2' 4' 7 psi 6' 8' 10' 15 psi 3,0
12'm 14' 30 psi
3.7 m 0,6 m 1,248
mkPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207 kPa
10'
16' 7 psi 15 psi 3,0 m 30 psi 8'
4.9 m 48 kPa 103 kPa 207 kPa 2,4 m
10'
20' 3,0 m 8'
6.1 m 2,4 m 6'
24' 1,8 m
7.3m 8'
2' 4' 6' 8' 10'2,4 m12' 14' 16' 18' 20' 22' 24' 26'
6'
0.6 m 1.2 m 1.8 m 2.4 m 3.0 m 3.7 m 4.3 m 4.9 m 5.5 m 6.1 m 6.7 m 7.3 m 7.9 m
1,8 m 4'
1,2 m
7 PSI 6'
15 PSI 30 PSI
48 kPa
1,8 m
103 kPa 4'
207 kPa
Model V1007 1,2 m 2'
0,6 m
K4.2 Window Sprinkler 4'Distribution Patterns – Plan View
1,2 m 2'
1' 0,6 m 0
0.3 m 2' 4' 6' 8' 10'
2' 0,6 m 1,2 m 1,8 m 2,4 m 3,0 m
4' 0,6 m
1.2 m 0
2' 4' 7 psi 6' 8' 10' 15 psi 12' 14'
8' 0,6 m 1,248
m kPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 20
2.4 m 0
2' 4' 7 psi 6' 8' 10' 15 psi 12' 14' 30 psi
12' 0,6 m 1,248
mkPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207 kPa
3.7 m
7 psi 15 psi 30 psi
16' 48 kPa 103 kPa 207 kPa
4.9 m
20'
6.1 m
24'
7.3m 2' 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26'
0.6 m 1.2 m 1.8 m 2.4 m 3.0 m 3.7 m 4.3 m 4.9 m 5.5 m 6.1 m 6.7 m 7.3 m 7.9 m

7 PSI 15 PSI 30 PSI


48 kPa 103 kPa 207 kPa

40.72 3180 Rev. F Updated 6/2014 © 2014 Victaulic Company. All rights reserved.
victaulic.com 3
2,4 m
10'
3,0 m 8'
2,4 m 6'
1,8 m
8'
victaulic.com | Sprinklers | FireLock
2,4 m | V10 | Publication 40.72
®
6'
1,8 m 4'
Distribution Patterns: 1,2 m
6'
1,8 m 4'
Model V1009 1,2 m 2'
K5.6 Window Sprinkler Distribution Patterns – Plan View 0,6 m
4'
1' 1,2 m 2'
0.3 m 0,6 m 0
4' 2' 4' 6' 8' 10'
2' 0,6 m 1,2 m 1,8 m 2,4 m 3,0 m
1.2 m
0,6 m 0
8' 2' 4' 7 psi 10' 6' 8' 10' 15 psi 12' 14'
2.4 m 0,6 m 1,248 3,0 m1,8 m
m kPa 2,4 m 3,0 m103 kPa3,7 m 4,3 m 20
0
12' 2' 4' 7 psi 10' 6' 8' 10' 15 psi 12' 14' 30 psi
3.7 m 0,6 m 1,248
mkPa3,0 m1,8 m 2,4 m 3,0 m103 kPa3,78'm 4,3 m 207 kPa
16' 2,4 m
7 psi 10' 15 psi 30 psi
4.9 m
3,0 m
48 kPa 103 kPa 8' 207 kPa
20' 2,4 m 6'
6.1 m 1,8 m
8'
24' 2,4 m 6'
7.3m 2' 4' 6' 8' 10' 12' 14' 16' 18' 1,8
20' m 22' 24' 26' 4'
0.6 m 1.2 m 1.8 m 2.4 m 3.0 m 3.7 m 4.3 m 4.9 m 5.5 m 6.1 m 6.7 m 7.3 m 7.9 m 1,2 m
6'
1,8 m 4'
7 PSI 15 PSI
Model V1011 30 PSI
1,2 m 2'
48 kPa 103 kPa 207 kPa 0,6 m
K8.0 Window Sprinkler Distribution Patterns – Plan View
4'
1' 1,2 m 2'
0.3 m 0,6 m 0
2' 4' 6' 8' 10'
4' 2' 0,6 m 1,2 m 1,8 m 2,4 m 3,0 m
1.2 m 0,6 m 0
8' 2' 4' 7 psi 10'6' 8' 10' 15 psi 12' 14' 30
2.4 m 0,6 m 1,248
m kPa 3,0 1,8
mm 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207
0
12' 2' 4' 7 psi 10'6' 8' 10' 15 psi 12' 14' 30 psi
3.7 m 0,6 m 1,248
mkPa 3,0 1,8
mm 2,4 m 3,0 m103 kPa3,7 m8' 4,3 m 207 kPa
16' 2,4 m
7 psi 10' 15 psi 30 psi
4.9 m 48 kPa 3,0 m 103 kPa 207 kPa
8'
20' 2,4 m 6'
6.1 m 1,8 m
24'
8'
2,4 m 6'
7.3m
2' 4' 6' 8' 10' 12' 14' 16' 18' 1,8
20' m 22' 24' 26' 4'
0.6 m 1.2 m 1.8 m 2.4 m 3.0 m 3.7 m 4.3 m 4.9 m 5.5 m 6.1 m 6.7 m 7.3 m 7.9 m 1,2 m
6'
1,8 m 4'
7 PSI Model
15 PSI V1013 30 PSI
1,2 m 2'
48 kPa K11.2 Window Sprinkler Distribution Patterns – 207
103 kPa PlankPaView 0,6 m
4'
1' 1,2 m 2'
0.3 m 0,6 m 0
4' 2' 4' 6' 8' 10'
2' 0,6 m 1,2 m 1,8 m 2,4 m 3,0 m
1.2 m 0,6 m 0
8' 2' 4' 7 psi 6' 8' 10' 15 psi 12' 14' 30
2.4 m 0,6 m 1,248
m kPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207

12'
0
2' 4' 7 psi 6' 8' 10' 15 psi 12' 14' 30 psi
3.7 m 0,6 m 1,248
mkPa 1,8 m 2,4 m 3,0 m103 kPa3,7 m 4,3 m 207 kPa
16'
7 psi 15 psi 30 psi
4.9 m
48 kPa 103 kPa 207 kPa
20'
6.1 m
24'
7.3m
2' 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26'
0.6 m 1.2 m 1.8 m 2.4 m 3.0 m 3.7 m 4.3 m 4.9 m 5.5 m 6.1 m 6.7 m 7.3 m 7.9 m
NOTES:
7 PSI 15 PSI 30 PSI
A. Data shown 48
is approximate
kPa and can vary due
103 to
kPadifferences in installation.
207 kPa
B. These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are provided as
information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to the appropriate NFPA
National Fire Code or the Authority Having Jurisdiction for specific information regarding obstructions, spacing limitations and area of coverage requirements. Failure
to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings, Approvals and Warranties.
C. All patterns are symmetrical to the centerline of the waterway.

40.72 3180 Rev. F Updated 6/2014 © 2014 Victaulic Company. All rights reserved.
victaulic.com 4
victaulic.com | Sprinklers | FireLock® | V10 | Publication 40.72

WARNING
• Always read and understand installation, care, and maintenance instructions, supplied with each box of sprin-
klers, before proceeding with installation of any sprinklers.
• Always wear safety glasses and foot protection.
• Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping
products.
• Installation rules, especially those governing obstruction, must be strictly followed.
• Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury and/or property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For
minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pam-
phlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may
have additional maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the safe installation of this
product, contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA, Telephone:
001-610-559-3300.

Installation Note
Reference should always be made to the I-40 Victaulic FireLock Automatic Sprinklers This product shall be manufactured by Victaulic or to Victaulic specifications. All products
Installation and Maintenance Sheet for the product you are installing. This installation sheet to be installed in accordance with current Victaulic installation/assembly instructions.
is included with each shipment of Victaulic products for complete installation and assembly Victaulic reserves the right to change product specifications, designs and standard
data, and is available in PDF format on our website at victaulic.com. equipment without notice and without incurring obligations.
Warranty Trademarks
Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic is a registered trademark of Victaulic Company.

40.72 3180 Rev. F Updated 6/2014 © 2014 Victaulic Company. All rights reserved.