SCHEDULE OF LOADS AND COMPUTATION ONE LINE DIAGRAM

CKT No. LOAD DESCRIPTION QTY VOLT VA AMP SIZE OF CONDUCTOR AND CONDUIT AT POLE KAIC
1 LIGHTING OUTLET 6 230 600 2.61 USE 2-2.0mm 15 2 10 SERVICE ENTRANCE

2 LIGHTING OUTLET 6 230 600 2.61 USE 2-2.0mm 15 2 10 M KILOWATT-HOUR METER

3 LIGHTING OUTLET 4 230 400 1.74 USE 2-2.0mm 15 2 10


75 AT MAIN PROTECTIVE DEVICE
4 LIGHTING OUTLET 5 230 500 2.17 USE 2-2.0mm 15 2 10
5 LIGHTING OUTLET 5 230 500 2.17 USE 2-2.0mm 15 2 10 1 15AT 15AT 2

6 LIGHTING OUTLET 4 230 400 1.74 USE 2-2.0mm 15 2 10 3 15AT 15AT


4
7 LIGHTING OUTLET 7 230 700 3.04 USE 2-2.0mm 15 2 10 5 6
15AT 15AT

8 CONVENIENCE OUTLET 6 230 1080 4.70 20 2 10 7 8


15AT 20AT

9 CONVENIENCE OUTLET 6 230 1080 4.70 20 2 10


9 20AT 20AT
10
10 CONVENIENCE OUTLET 5 230 600 2.61 20 2 10
11 20AT 30AT
12
11 CONVENIENCE OUTLET 6 230 1080 4.70 20 2 10
13 30AT 30AT
14
12 1 Hp AIRCON OUTLET 1 230 1000 4.35 30 2 10
13 SPARE 1 230 1000 4.35 30 2 10
14 SPARE 1 230 1000 4.35 30 2 10
TOTAL 10540 45.84
LEGENDS
TOTAL A = 45.84 A
M
TOTAL VA = 10540 VA METER CONVENIENCE OUTLET SERVICE ENTRANCE

I = 45.84 x 1.25 = 57.30 Amperes PINLIGHT S Sa SINGLE GANG SWITCH


or
GROUND

SIZE OF SERVICE ENTRANCE : WALL LAMP Sab TWO-GANG SWITCH


CIRCUIT HOMERUN
1
LIGHT OUTLET Sabc THREE GANG SWITCH

RATING OF PROTECTIVE DEVICE : CHANDELIER SWITCH LINE


PANEL BOARD

USE 75 AMPERE MOLDED AIR CIRCUIT BREAKER, AIRCONDITION OUTLET


FLOURESENT LAMP POWER LINE
230 VOLTS, 2 POLE
COURSE AND YEAR
CAGAYAN STATE UNIVERSITY SUBMITTED BY: BSCE-5 PROPOSED PROJECT TITLE:
SUBJECT
CARIG CAMPUS
COLLEGE OF ENGINEERING ELOISA F. FABROA
DATE SUBMITTED
CIVIL ENGINEERING "TWO-STOREY RESIDENTIAL HOUSE"
DEPARTMENT 15-00926 SUBMITTED TO:

C:\Users\LENOVO\Desktop\AUTOCAD FILES\for bd 2.dwg, 29/01/2030 7:13:29 PM, DW