6.

SETTING PROFI
MEASURING MODE > T/C

Type “T/C”

T/C B T/C E T/C J T/C K >


MODE 
T/C N T/C R T/C S T/C T T/C L

>

MODE Selection of the type of


  thermocouple
Menu Type of thermocouple
T/C B B
T/C E E
DEF = Type “J” T/C J J

MODE
T/C K K
T/C N N
T/C R R
T/C S S
T/C T T
T/C L L

Type of thermocouple “K” Example

J K CONECT.

CONECT.

INT.1TC INT. 2TC EXT.1TC EXT. 2TC

CONECT. Selection of the type of


  sensor connection
Ref.
Menu Connection T/C
DEF = EXT. 1TC measuring C.J. at instru-
INT.1TC ment brackets 
measuring C. J. at
CONECT.

INT.2TC instrument brackets with 


anti-series connected
ref. TC
the entire measuring set
EXT.1TC is working under invaried 
and constant temperature

EXT.2TC when using compensa-


tion box 

Type of connection > CONECT. = EXT. 2TC Example

EXT.1TC EXT. 2TC C. J . TEM.