Professional Documents
Culture Documents
Abstract— Frequency Response Analysis (FRA) is regarded as frequency response spectrum, the HV/LV windings frequency
a robust technique to recognize transformer winding deformation. response spectra for “wet” and “dry” type test objects for
It has been implemented and used since the last decade. However, various temperatures are measured. In the meantime, DDF
its interpretation and measurement sensitivity are still under measurement is performed for each and every stage and the
development. Recent studies reveal that apart from winding
results are recorded. Deviations in FRA resonance frequencies
deformation, FRA data can also be influenced by moisture
variation in transformer paper insulation. Technically speaking, under different DDF values are discussed. For DDF
moisture variation will certainly influence the Dielectric measurements, to have precise understanding about the
Dissipation Factor (DDF) in transformer. Therefore, it is of interest moisture migration between the oil and paper insulation, the
to investigate the correlation between DDF value and FRA moisture content of the oil is measured and paper humidity can
spectrum. A model transformer was fabricated for this study and be obtained. Indeed, for each DDF value the deviation in FRA
the experiment was concentrated on the temperature changes and resonant frequencies and moisture contents in paper and oil
paper moisture variation and eventually DDF alteration on the insulations are highlighted and discussed in detail. This study
FRA spectrum deviation. DDF was measured for the “wet” and shows that the changes in dielectric dissipation factor in turn
“dry” model transformer at different temperatures. In parallel, the
can influence the FRA resonance points in the mid- and high-
FRA spectrum was also recorded. The correlation between the
transformer DDF value and FRA spectrum is highlighted and frequency bands.
discussed.
II. DIELECTRIC DISSIPATION FACTOR (DDF)
Keywords: Frequency Response Analysis, Dielectric Dissipation
Factor, Moisture Variation, Transformer, Winding Deformation. A. Single Frequency
DDF
0.15
0
Deviated Frequency Band
-10 0.1
-20
0.05
-30
Magnitude [dB]
-40 0
20 30 40 50 60 70 80 90 100
Temperature ºC
-50
Figure 4. DDF variation spectra for HV-LV windings, “wet” model test object.
-60
-70 Frequency Band: 5 kHz - 20 MHz In fact, moving to the left hand side on Bode diagram for
-80
HV winding spectrum (at 30 °C )
HV winding spectrum (at 90 °C ) FRA data potentially determines higher value for DDF. These
10
4
10
5
10
6
10
7 resonant frequencies will take opposite side (higher frequencies)
Frequency [Hz]
when DDF takes lower values. This investigation was further
studied through the “dry” model transformer in the next
subsection.
B. Study on “Dry” Model Test Object
To study the impact of the DDF on FRA trace for dry
transformer winding, the oil was drained and the model
transformer was heated up to 90 °C in the electric oven and then
vacuumed (less than 750 mTorr) to remove the moisture content
from the paper insulation. Figure 5 shows the vacuum process.
After that, the vacuum was broken through a three-way valve
and then dry transformer oil was injected into the container once
more. The moisture content of the oil was measured after 11
Figure 3. FRA spectra for HV winding due to moisture migration from paper
into the oil insulation at 30°C and 90°C, “wet” model test object.
days through KFT method and gave a result of 3 ppm at 23 °C.
The test object was heated up to 30 °C same as before to
Study on frequency response spectra when the temperature prepare for frequency response measurement. The FRA spectra
decreases from 90 to 30 ºC led to similar results. Although for HV and LV windings were then measured at 30 and 90 °C
moisture absorption for paper insulation is different with over the frequency range of 20 Hz – 20 MHz (end-to-end
desorption, the equilibria should be the same and hence similar measurement), similar to the last experiment. Also, DDF
spectra were observed in the reverse procedure. measurement at power frequency (50 Hz) was performed as in
To have precise investigation about the DDF and its relation the last experiment. Figure 6 shows the frequency response
to FRA spectra deviation, this parameter was measured for each spectra just for 30 and 90 °C.
and every temperature on the “wet” model transformer and the
results are provided in Table I and plotted in Figure 4. Table I
also shows the moisture content in oil and paper insulations at
different temperatures for the “wet” model transformer. The
maximum applied voltage for DDF measurement was 5 kV to
avoid any kind of undesirable flash-over in the test object. On
examining DDF measurement results, it is obvious that for the
“wet” model transformer as the DDF experiences higher values,
the local resonances in FRA spectrum shift to lower
Figure 5. Vacuum process of the model transformer.
frequencies.
According to Table II, DDF values for the model transformer
Table I. DDF at 5 kV, moisture content in oil and paper insulations for “wet”
type test object. are significantly reduced due to the transformer dry-out process.
In addition as far as the temperature increases, the FRA
Temp. 30 °C 40 °C 50 °C 60 °C 70 °C 80 °C 90 °C
resonant points in Figure 6 have shifted to lower frequencies. In
DDF 0.0203 0.0319 0.0484 0.0721 0.1119 0.1858 0.2849
Paper the meantime, the DDF value has increased as provided in
3.6 3.0 2.6 2.2 2.0 1.8 1.7 Table II and Figure 7. This is the same as the previous case for
MC%
Oil
18 21 25 35 52 63 95 the “wet” model transformer. Indeed, a similar relationship
MC[ppm] between the FRA resonant points and DDF in the “wet” model
-40 were illustrated. This in turn reveals that FRA resonant point is
-50 potentially initiated by winding capacitance, and of course the
latter is a function of paper humidity or even oil humidity. It is
-60
worth noting that the measurement of the DDF was performed
-70
at a single frequency (50 Hz). On the other hand, the Frequency
-80
Frequency Band:9 kHz- 20 MHz
0.012
Kinabalu, Malaysia, pp. 712-717, 2012.
0.01 [10] A. Bouaïchz, I. Fofana, M. Farzaneh, A. Setayeshmehr, H. Borsi, E.
Gockenbach, A. Beroual, Ngnui Thomas Aka, “Dielectric spectroscopy
0.008
techniques as quality control tool: A feasibility study,” IEEE Electr. Insul.
0.006 Mag., vol. 25, issue 1, pp. 6-14, 2009.
0.004 [11] IEC Standard 60076-18; Measurement of frequency response, Edition
1.0, 2012-07.
0.002
20 30 40 50 60 70 80 90 100 [12] Y. Du, M. Zahn, B. C. Lesieutre, A. V. Mamishev,S. R. Lindgren,
Temperature ºC
“Moisture equilibrium in transformer paper-oil systems”, IEEE Electr.
Figure 7. DDF variation spectra for HV-LV windings, “wet” model test object. Insul. Mag., Vol. 15, No. 1, pp. 11-20, 1999.